Plan Review Details - Permit 02091396
Plan Review Stops For Permit 02091396
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By btrobaug Date 2002-09-25 Time 16:13 Rev Time 1.00
Received By btrobaug Date 2002-09-25 Time 12:45 Sent To  
Notes
2002-09-25 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PAGE #2 OF THE SUBMITTALS INDICATE
 THE BALLAST FOR THE LIGHTS HAS A 277
 VOLT PRIMARY,THE RISER DIAGRAM OF THE
 PALM STREET LOCATION SHOWS THE PANELS
 BEING 120/240 VOLT.THE PANELS AT THE
 OTHER TWO LOCATIONS DON'T HAVE A
 VOLTAGE RATING.
  
 2} THE PANEL AT THE PALM STREET LOCATION
 MUST HAVE A MAIN BREAKER PER 381-14(A).
  
 3} THE PLANS INDICATE THAT THE FEEDS
 FROM FPL TO THE PANELS IS 120 VOLT.
  
 PLEASE REVISE PLANS TO CORRECT THESE
 ERRORS AND SUBMIT SAME FOR REVIEW,BEFORE
 FINAL INSPECTION.
  
  
 BILL TROBAUGH
 CITY OF WEST PALM BEACH
 ELECTRICAL PLAN REVIEW.
 561/659-8096 EXT.8392