Plan Review Details - Permit 02091196
Plan Review Stops For Permit 02091196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-31 Cont ID  
Sent By hpiskura Date 2002-10-31 Time 09:17 Rev Time 0.00
Received By hpiskura Date 2002-10-31 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-30 Cont ID  
Sent By hpiskura Date 2002-09-30 Time 14:07 Rev Time 0.00
Received By hpiskura Date 2002-09-30 Time 14:07 Sent To  
Notes
2002-09-30 00:00:00PROVIDE SIGNED, SEALED AND DATED PLANS.
 SEE FBC 104.2.2.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-10-17 Time 06:36 Rev Time 0.50
Received By dpalmer Date 2002-10-17 Time 06:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-26 Cont ID  
Sent By dpalmer Date 2002-09-26 Time 07:17 Rev Time 0.25
Received By dpalmer Date 2002-09-26 Time 07:17 Sent To  
Notes
2002-09-26 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE PLANS ARE COPIES OF
 SIGNED AND SEALED PLANS. PLEASE NOTE
 UNDER FS/FAC ALL PLAN S MUST CONTAIN
 AN ORIG SIGNATURE,RAISED SEAL AND DATED
 BY ARCH/ENGINEER OF RECORD. 471.025,
 481.221.
  
 2)NOTE: IT IS NOTED THAT RISER SHOWS AN
 EXISTING MAIN AND METER. PLEASE CLARIFY
 IF PANEL "A" IS NEW OR EXISTING?
 IF NEW PLEASE PROVIDE AIC RATING OF
 PANEL. 110-9
  
 3)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM/EXIT LTS PER 700-12
  
 4)NOTE: PLEASE CLARIFY IF NEW OR EXIST-
 -ING SIGN CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PALMER
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-30 Cont ID  
Sent By mcarsill Date 2002-10-30 Time 12:00 Rev Time 0.00
Received By mcarsill Date 2002-10-30 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-26 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 15:23 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:16 Rev Time 0.00
Received By shernand Date 2003-04-03 Time 16:16 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-04 Cont ID  
Sent By pkrauss Date 2003-04-04 Time 15:59 Rev Time 0.40
Received By pkrauss Date 2003-04-04 Time 15:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-29 Cont ID  
Sent By shernand Date 2003-04-03 Time 16:16 Rev Time 0.55
Received By pkrauss Date 2002-10-29 Time 11:26 Sent To  
Notes
2002-10-29 00:00:00MECHANICAL PERMIT 02091533

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-04 Cont ID  
Sent By pkrauss Date 2002-10-04 Time 12:37 Rev Time 0.40
Received By pkrauss Date 2002-10-04 Time 12:04 Sent To  
Notes
2002-10-04 00:00:00DENIED:MECHANICAL PERMIT 02091533
  
 AS PER FS/FAC PLANS SHALL HAVE RAISED
 SEAL AND BE SIGNED/DATED BY THE ENGINEER
 OR ARCHITECT OF RECORD.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.PROVIDE DUCT SIZE, MATERIAL &
 LAYOUT FOR THE OUTSIDE AIR DUCT.
  
 PLEASE NOTE, EXHAUST AIR SHALL NOT BE
 DIRECTED ONTO WALKWAYS.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 15:31 Rev Time 1.00
Received By kstevens Date 2002-11-05 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-03 Cont ID  
Sent By jleech Date 2002-10-03 Time 16:19 Rev Time 1.00
Received By jleech Date 2002-10-03 Time 16:19 Sent To  
Notes
2002-10-03 00:00:00DENIED;
 1.PLANS ARE NOT SEALED.
 2.BATHROOM TO MEET ALL HANDICAP CODES,
 SEE F.B.C CHAPTER 11. SHOW DETAIL
 DRAWING WITH ALL APPICABLE MEASURE-
 MENTS. INCLUDE 5' TURNING RADIUS.
 3.DRINKING FOUNTAIN OR BOTTLE WATER
 COOLER REQUIRED. SEE TABLE 403.1.
 MUST MEET HANDICAP CODE REQUIREMENTS.
  
 PLUMBING PLANREVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369