| Plan Review Stops For Permit 02091196 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-31 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-31 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-30 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-30 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2002-09-30 00:00:00 | PROVIDE SIGNED, SEALED AND DATED PLANS. | | | SEE FBC 104.2.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-10-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-17 |
Time |
06:36 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-10-17 |
Time |
06:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-26 |
Time |
07:17 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-09-26 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2002-09-26 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE PLANS ARE COPIES OF | | | SIGNED AND SEALED PLANS. PLEASE NOTE | | | UNDER FS/FAC ALL PLAN S MUST CONTAIN | | | AN ORIG SIGNATURE,RAISED SEAL AND DATED | | | BY ARCH/ENGINEER OF RECORD. 471.025, | | | 481.221. | | | | | | 2)NOTE: IT IS NOTED THAT RISER SHOWS AN | | | EXISTING MAIN AND METER. PLEASE CLARIFY | | | IF PANEL "A" IS NEW OR EXISTING? | | | IF NEW PLEASE PROVIDE AIC RATING OF | | | PANEL. 110-9 | | | | | | 3)NOTE: PLEASE CLARIFY CIRCUITING FOR | | | EM/EXIT LTS PER 700-12 | | | | | | 4)NOTE: PLEASE CLARIFY IF NEW OR EXIST- | | | -ING SIGN CIRCUIT PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PALMER | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-30 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-30 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-09-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-24 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-24 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-03 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-03 |
Time |
16:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-04-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-04 |
Time |
15:59 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-04-04 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-03 |
Time |
16:16 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2002-10-29 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | MECHANICAL PERMIT 02091533 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-04 |
Time |
12:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-10-04 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2002-10-04 00:00:00 | DENIED:MECHANICAL PERMIT 02091533 | | | | | | AS PER FS/FAC PLANS SHALL HAVE RAISED | | | SEAL AND BE SIGNED/DATED BY THE ENGINEER | | | OR ARCHITECT OF RECORD. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89.PROVIDE DUCT SIZE, MATERIAL & | | | LAYOUT FOR THE OUTSIDE AIR DUCT. | | | | | | PLEASE NOTE, EXHAUST AIR SHALL NOT BE | | | DIRECTED ONTO WALKWAYS. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-05 |
Time |
15:31 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-11-05 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-10-03 |
Time |
16:19 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2002-10-03 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2002-10-03 00:00:00 | DENIED; | | | 1.PLANS ARE NOT SEALED. | | | 2.BATHROOM TO MEET ALL HANDICAP CODES, | | | SEE F.B.C CHAPTER 11. SHOW DETAIL | | | DRAWING WITH ALL APPICABLE MEASURE- | | | MENTS. INCLUDE 5' TURNING RADIUS. | | | 3.DRINKING FOUNTAIN OR BOTTLE WATER | | | COOLER REQUIRED. SEE TABLE 403.1. | | | MUST MEET HANDICAP CODE REQUIREMENTS. | | | | | | PLUMBING PLANREVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|