Plan Review Details - Permit 02091172
Plan Review Stops For Permit 02091172
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-12 Cont ID  
Sent By hpiskura Date 2002-12-12 Time 07:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-12-12 00:00:00REVISION SK 2 & SK 3 DATED 11/15/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By nmccray Date 2002-12-09 Time 11:26 Rev Time 0.00
Received By hpiskura Date 2002-11-07 Time 11:01 Sent To  
Notes
2002-11-07 00:00:00PROVISO:
  
 1 1/2 HR RATED DOORS ARE REQUIRED IN THE
 2 HR RATED OCCUPANCY SEPARATION.FBC
 705.1.2 AND STAIR ENCLOSURE.
  
 PROVIDE SIGNED AND SEALED SHOP DRAWINGS
 FOR THE "TYPICAL DECK FRAMING DETAIL" ON
 SHEET S-1.INCLUDE SPAN, SIZE OF
 FRAMING MEMBER, TYPE AND NUMBER OF
 FASTENERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-17 Cont ID  
Sent By hpiskura Date 2002-10-17 Time 15:58 Rev Time 0.00
Received By hpiskura Date 2002-10-17 Time 13:20 Sent To  
Notes
2002-10-17 00:00:00SHEET SP1 SHOWS THE DOORS SWINGING OVER
 THE RIGHT OF WAY.THIS IS PROHIBITTED
 BY FBC 3203, PLEASE REVISE AS NECESSARY.
  
 SHOW THE MIXED OCCUANCY SEPARATION
 BETWEEN THE WAREHOUSE "S" AND THE
 SHOWROOM / OFFICES "B" AS REQUIRED BY
 FBC 704.1.1 (2 HR)
  
 THE STAIRS FROM THE SECOND FLOOR ARE
 REQUIRED TO BE ENCLOSED IN A FIRE RATED
 SHAFT.SEE FBC 1006.1.1.THE SECOND
 FLOOR IS NOT A MEZZANINE AS DEFINED IN
 FBC 503.2.3.
  
 SHEET S1 SECTION 1.SPECIFY THE
 SIMPSONHB ANCHOR AND WELD TO BE USED.
  
 S1, IS THE 2X12 SPLICE SHOWN WITH 12
 NAILS OCCUR AT MID SPAN?WHAT IS THE
 ANTICIPATED LOAD VALUE?
  
 S1, WHAT IS THE 5/8" PLYWOOD DECK ON THE
 SECOND FLOOR TO BE USED FLOOR? IS IT
 ENCLOSED?
  
 THE 42" FOOTINGS SHOWN ON S1 CONFLICT
 WITH THE 36" SQUARE FOOTINGS ON A4.
 PLEASE CLARIFY.
  
 SHEET A1 PLAN "A", THE ELEVATOR DOOR
 AND THE SHOW WINDOW DOOR 4, SHOWN DO
 NOT COMPLY WITH FBC 1012.1.4.
  
 IF THE TEST REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERINGS ARE NOT
 INCLUDED WITH THIS PERMIT APPLICATION,
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED.
  
 THE GLASS BLOCK MUST BE INSTALLED IN
 ACCORDANCE WITH FBC 2112.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By dpalmer Date 2002-11-07 Time 06:52 Rev Time 0.50
Received By dpalmer Date 2002-11-07 Time 06:40 Sent To  
Notes
2002-11-07 00:00:00************* NOTES/REDLINED ******
  
 1)NOTE: PLEASE NOTE SHOW WINDOW SHOWN
 MAY REQUIRE ADDITIONAL RECEPT PER 210-62
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MAINS/ PANELS BEING INSTALLED
 BEFORE ROUGH.
  
 3)NOTE: FIELD VERIFY WATE FOUNTAIN
 SHOWN AT 2P30A?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By dpalmer Date 2002-09-24 Time 11:17 Rev Time 0.50
Received By dpalmer Date 2002-09-24 Time 11:17 Sent To  
Notes
2002-09-24 00:00:00************UNSAT *****************
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL "A", ALSO PANEL "A" AND PANEL
 "B". SIZE PER 250-122
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220-3,220-10,220-11,220-13 ETX
 PLEASE NOTE CONTINUOUS LOADS AT 125%.
 215-3,230-42
  
 3)NOTE: PLEASE NOTE LOADS SHOWN FOR
 A/C UNITS DO NOT CORRELATE W/ MECH PLANS
 PLEASE NOTE OCP FOR A/C UNITS TO BE
 SIZED PER 424-3.
 PLEASE SHOW LOCATIONS OF UNITS /AND
 DISCONNECTS ON PLANS 440-11.
 RECEPTS PER 210-63.
  
 4)NOTE: PLEASE CLARIFY SHOW ROOM RECEPTS
 REQ`D PER 210-62.
  
 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER
 600-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-12-09 Cont ID  
Sent By nmccray Date 2002-12-09 Time 11:26 Rev Time 0.00
Received By nmccray Date 2002-12-09 Time 11:26 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-11-08 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 16:57 Rev Time 0.00
Received By mcarsill Date 2002-11-08 Time 16:03 Sent To  
Notes
2002-11-08 00:00:001) PLEASE PROVIDE RATED DOORS IN
 OPENINGS WITHIN THE TWO HOUR RATED
 WALLS.
  
 2) BUILDING ADDRESS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 13:05 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:36 Rev Time 0.00
Received By btrobaug Date 2003-02-10 Time 16:36 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 16:57 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 16:57 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 07:16 Rev Time 0.00
Received By btrobaug Date 2002-10-31 Time 07:04 Sent To  
Notes
2002-10-31 00:00:00TO COMM BOARD #1./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-03-07 Cont ID  
Sent By pkrauss Date 2003-03-07 Time 15:59 Rev Time 0.45
Received By pkrauss Date 2003-03-07 Time 15:53 Sent To  
Notes
2003-03-07 00:00:00PROVISO:
  
 DUCT IS TO BE ENCAPSULATED BY THE 1HR
 SHAFT.ALL CLEARANCES TO BE MAINTAINED
 AS PER 2001 FBC 1007.7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-02-14 Cont ID  
Sent By pkrauss Date 2003-02-14 Time 11:53 Rev Time 0.40
Received By pkrauss Date 2003-02-14 Time 11:28 Sent To  
Notes
2003-02-14 00:00:00DENIED:
  
 REVISION STILL INDICATES DUCT RUNNING
 THRU STAIRWELL ON THE 2ND FL & INTO
 STAIRWELL ON THE 1ST FL. VIOLATION OF
 2001 FBC 1006.1.3.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:36 Rev Time 0.40
Received By pkrauss Date 2002-11-07 Time 08:54 Sent To  
Notes
2002-11-07 00:00:00PROVISO:
  
 AS PER 2001 FBC 1006.1.3.1,
 PENETRATIOINS THROUGH A STAIRWAY
 ENCLOSURE ARE PROHIBITED.THE ONLY
 DUCTWORK OR EQUIPMENT ALLOWED IN A
 STAIRWAY IS FOR INDEPENDENT STAIR
 PRESSURIZATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-07 Cont ID  
Sent By pkrauss Date 2002-10-07 Time 11:04 Rev Time 0.45
Received By pkrauss Date 2002-10-07 Time 09:38 Sent To  
Notes
2002-10-07 00:00:00PROVISO:
  
 CONDENSATE SHALL NOT GO TO SCUPPERS.
 SEE PLUMBERS COMMENTS.
  
 EXHAUST AIR SHALL NOT BE DIRECTED ONTO
 WALKWAYS AS PER 2001 FBC(M) 401.5.2
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-07 Cont ID  
Sent By kstevens Date 2002-11-07 Time 14:20 Rev Time 0.75
Received By kstevens Date 2002-11-07 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 14:34 Rev Time 0.50
Received By kstevens Date 2002-10-12 Time 14:34 Sent To  
Notes
2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT CS-1 PLUMBING NOTE #8, 2" AND
 SMALLER PIPE SHALL PITCH AT 1/4" PER FT.
 2) SHTS CS-1 & P-1 PLUMBING NOTES #12.
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE THEM FROM REFERENCE.
 3) SHT P-1 WATER RISER DIAGRAM, WHERE
 REQUIRED BY SEC 604.9, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE", NOT AT THE
 TOP OF THE DROP IN CEILING AS SHOWN.
 4) SHT P-1 WATER HEATER DETAIL. IF THERE
 IS A RPZ BACKFLOW ON THE WATER SERVICE,
 THAN THERMAL EXPANSION CONTROL PER SEC
 607.3.2 WILL BE REQUIRED. SHOW ON DETAIL
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377