| Plan Review Stops For Permit 02091172 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-12-12 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | REVISION SK 2 & SK 3 DATED 11/15/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-11-07 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2002-12-09 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-07 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2002-11-07 00:00:00 | PROVISO: | | | | | | 1 1/2 HR RATED DOORS ARE REQUIRED IN THE | | | 2 HR RATED OCCUPANCY SEPARATION.FBC | | | 705.1.2 AND STAIR ENCLOSURE. | | | | | | PROVIDE SIGNED AND SEALED SHOP DRAWINGS | | | FOR THE "TYPICAL DECK FRAMING DETAIL" ON | | | SHEET S-1.INCLUDE SPAN, SIZE OF | | | FRAMING MEMBER, TYPE AND NUMBER OF | | | FASTENERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-10-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-17 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-17 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2002-10-17 00:00:00 | SHEET SP1 SHOWS THE DOORS SWINGING OVER | | | THE RIGHT OF WAY.THIS IS PROHIBITTED | | | BY FBC 3203, PLEASE REVISE AS NECESSARY. | | | | | | SHOW THE MIXED OCCUANCY SEPARATION | | | BETWEEN THE WAREHOUSE "S" AND THE | | | SHOWROOM / OFFICES "B" AS REQUIRED BY | | | FBC 704.1.1 (2 HR) | | | | | | THE STAIRS FROM THE SECOND FLOOR ARE | | | REQUIRED TO BE ENCLOSED IN A FIRE RATED | | | SHAFT.SEE FBC 1006.1.1.THE SECOND | | | FLOOR IS NOT A MEZZANINE AS DEFINED IN | | | FBC 503.2.3. | | | | | | SHEET S1 SECTION 1.SPECIFY THE | | | SIMPSONHB ANCHOR AND WELD TO BE USED. | | | | | | S1, IS THE 2X12 SPLICE SHOWN WITH 12 | | | NAILS OCCUR AT MID SPAN?WHAT IS THE | | | ANTICIPATED LOAD VALUE? | | | | | | S1, WHAT IS THE 5/8" PLYWOOD DECK ON THE | | | SECOND FLOOR TO BE USED FLOOR? IS IT | | | ENCLOSED? | | | | | | THE 42" FOOTINGS SHOWN ON S1 CONFLICT | | | WITH THE 36" SQUARE FOOTINGS ON A4. | | | PLEASE CLARIFY. | | | | | | SHEET A1 PLAN "A", THE ELEVATOR DOOR | | | AND THE SHOW WINDOW DOOR 4, SHOWN DO | | | NOT COMPLY WITH FBC 1012.1.4. | | | | | | IF THE TEST REPORTS FOR THE DOORS, | | | WINDOWS AND ROOF COVERINGS ARE NOT | | | INCLUDED WITH THIS PERMIT APPLICATION, | | | A SEPARATE PERMIT AND FEES WILL BE | | | REQUIRED. | | | | | | THE GLASS BLOCK MUST BE INSTALLED IN | | | ACCORDANCE WITH FBC 2112. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-07 |
Time |
06:52 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-07 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2002-11-07 00:00:00 | ************* NOTES/REDLINED ****** | | | | | | 1)NOTE: PLEASE NOTE SHOW WINDOW SHOWN | | | MAY REQUIRE ADDITIONAL RECEPT PER 210-62 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | NEW MAINS/ PANELS BEING INSTALLED | | | BEFORE ROUGH. | | | | | | 3)NOTE: FIELD VERIFY WATE FOUNTAIN | | | SHOWN AT 2P30A? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | | -ION IS CALLED IN. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-24 |
Time |
11:17 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-09-24 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2002-09-24 00:00:00 | ************UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND PANEL "A", ALSO PANEL "A" AND PANEL | | | "B". SIZE PER 250-122 | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 220-3,220-10,220-11,220-13 ETX | | | PLEASE NOTE CONTINUOUS LOADS AT 125%. | | | 215-3,230-42 | | | | | | 3)NOTE: PLEASE NOTE LOADS SHOWN FOR | | | A/C UNITS DO NOT CORRELATE W/ MECH PLANS | | | PLEASE NOTE OCP FOR A/C UNITS TO BE | | | SIZED PER 424-3. | | | PLEASE SHOW LOCATIONS OF UNITS /AND | | | DISCONNECTS ON PLANS 440-11. | | | RECEPTS PER 210-63. | | | | | | 4)NOTE: PLEASE CLARIFY SHOW ROOM RECEPTS | | | REQ`D PER 210-62. | | | | | | 5)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2002-12-09 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2002-12-09 |
Time |
11:26 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-11-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-05 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-08 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2002-11-08 00:00:00 | 1) PLEASE PROVIDE RATED DOORS IN | | | OPENINGS WITHIN THE TWO HOUR RATED | | | WALLS. | | | | | | 2) BUILDING ADDRESS REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-10-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-04 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-04 |
Time |
13:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-02-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-12 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-10 |
Time |
16:36 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-05 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-05 |
Time |
16:57 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-31 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-10-31 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | TO COMM BOARD #1./WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-03-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-03-07 |
Time |
15:59 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-03-07 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2003-03-07 00:00:00 | PROVISO: | | | | | | DUCT IS TO BE ENCAPSULATED BY THE 1HR | | | SHAFT.ALL CLEARANCES TO BE MAINTAINED | | | AS PER 2001 FBC 1007.7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2003-02-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-14 |
Time |
11:53 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-02-14 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2003-02-14 00:00:00 | DENIED: | | | | | | REVISION STILL INDICATES DUCT RUNNING | | | THRU STAIRWELL ON THE 2ND FL & INTO | | | STAIRWELL ON THE 1ST FL. VIOLATION OF | | | 2001 FBC 1006.1.3.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-11-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-12 |
Time |
16:36 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-11-07 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2002-11-07 00:00:00 | PROVISO: | | | | | | AS PER 2001 FBC 1006.1.3.1, | | | PENETRATIOINS THROUGH A STAIRWAY | | | ENCLOSURE ARE PROHIBITED.THE ONLY | | | DUCTWORK OR EQUIPMENT ALLOWED IN A | | | STAIRWAY IS FOR INDEPENDENT STAIR | | | PRESSURIZATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-10-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-07 |
Time |
11:04 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-10-07 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2002-10-07 00:00:00 | PROVISO: | | | | | | CONDENSATE SHALL NOT GO TO SCUPPERS. | | | SEE PLUMBERS COMMENTS. | | | | | | EXHAUST AIR SHALL NOT BE DIRECTED ONTO | | | WALKWAYS AS PER 2001 FBC(M) 401.5.2 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-11-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-07 |
Time |
14:20 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-11-07 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-10-12 |
Time |
14:34 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-10-12 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2002-10-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT CS-1 PLUMBING NOTE #8, 2" AND | | | SMALLER PIPE SHALL PITCH AT 1/4" PER FT. | | | 2) SHTS CS-1 & P-1 PLUMBING NOTES #12. | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | | DELETE THEM FROM REFERENCE. | | | 3) SHT P-1 WATER RISER DIAGRAM, WHERE | | | REQUIRED BY SEC 604.9, WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE FIX- | | | TURE IN AN "EFFECTIVE RANGE", NOT AT THE | | | TOP OF THE DROP IN CEILING AS SHOWN. | | | 4) SHT P-1 WATER HEATER DETAIL. IF THERE | | | IS A RPZ BACKFLOW ON THE WATER SERVICE, | | | THAN THERMAL EXPANSION CONTROL PER SEC | | | 607.3.2 WILL BE REQUIRED. SHOW ON DETAIL | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|