Plan Review Details - Permit 02091165
Plan Review Stops For Permit 02091165
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-10-23 Cont ID  
Sent By lmartine Date 2002-10-23 Time 16:04 Rev Time 0.00
Received By ptjomsto Date   Time   Sent To  
Notes
2002-10-25 00:00:00OK BY PKRAUSS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-24 Cont ID  
Sent By dpalmer Date 2002-09-24 Time 09:11 Rev Time 0.50
Received By dpalmer Date 2002-09-24 Time 09:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By mcarsill Date 2002-09-25 Time 11:09 Rev Time 0.00
Received By mcarsill Date 2002-09-25 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-23 Cont ID  
Sent By pkrauss Date 2002-10-23 Time 15:54 Rev Time 0.00
Received By pkrauss Date 2002-10-23 Time 15:54 Sent To  
Notes
2002-10-23 00:00:00ENGINEER LETTER SUBMITTED 10-10-02.
 O.A. CALCS INDCLUDED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-09 Cont ID  
Sent By pkrauss Date 2002-10-09 Time 16:27 Rev Time 0.45
Received By pkrauss Date 2002-10-09 Time 16:27 Sent To  
Notes
2002-10-09 00:00:00PROVISO:
  
 ENGINEER TO FAX LETTER STATING AIR
 BALANCE AND OCCUPANCY.

Review Stop P PLUMBING
Rev No 2 Status N Date 2002-10-24 Cont ID  
Sent By lmartine Date 2002-10-24 Time 15:49 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-10-24 00:00:00ALL PLUMBING WORK HAS BEEN REMOVED FROM
 THIS APPLICATION, SEE LETTER SUBMITTED
 FROM DESIGNER, SEPERATE PLUMBING PERMIT
 WILL BE REQUIRED.
  
  
 L. MARTINEZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-12 Cont ID  
Sent By kstevens Date 2002-10-12 Time 13:35 Rev Time 0.75
Received By kstevens Date 2002-10-12 Time 13:35 Sent To  
Notes
2002-10-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING.
  
 1) PLEASE SUBMIT A SANITARY AND A WATER
 RISER DIAGRAM. SHOW ALL PIPE SIZES,
 WATER HAMMER ARRESTORS (REQD. 604.9) ECT
 2) ONLY THE FIXTURES OF A BATHROOM GROUP
 CAN DRAIN INTO THE WET VENTED SYSTEM OF
 A BATHROOM. WASH MACHINE AND HAIR SINK
 WILL HAVE TO DRAIN DOWNSTREAM OF THE
 BATHROOM GROUP. SEC 909.1/909.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377