Plan Review Details - Permit 02091075
Plan Review Stops For Permit 02091075
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-23 Cont ID  
Sent By jgomez Date 2003-01-09 Time 14:24 Rev Time 0.25
Received By dpalmer Date 2002-12-23 Time 16:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-10-02 Cont ID  
Sent By jgomez Date 2002-12-23 Time 14:30 Rev Time 0.25
Received By dpalmer Date 2002-10-02 Time 10:09 Sent To B
Notes
2002-10-02 00:00:00NOTE REDLINED FOR KITCHEN COUNTERSPACE
 TO MEET 210-52-C-1.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:40 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 15:40 Sent To P
Notes
2003-10-08 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-03 Cont ID  
Sent By btrobaug Date 2003-01-03 Time 16:36 Rev Time 0.00
Received By btrobaug Date 2003-01-03 Time 16:35 Sent To B
Notes
2003-01-03 00:00:00TO JULIO./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-13 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 17:04 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 17:04 Sent To R
Notes
2002-12-13 00:00:00TO JULIO./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-30 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 17:43 Rev Time 0.00
Received By btrobaug Date 2002-10-29 Time 17:43 Sent To R
Notes
2002-10-30 00:00:00TO JULIO./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-28 Cont ID  
Sent By jleech Date 2002-09-28 Time 13:28 Rev Time 0.33
Received By jleech Date 2002-09-28 Time 13:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-18 Cont ID  
Sent By kstevens Date 2003-10-18 Time 07:05 Rev Time 0.50
Received By kstevens Date 2003-10-18 Time 07:05 Sent To  
Notes
2003-10-18 00:00:00REVISION OK - SANT. RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-07 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:40 Rev Time 0.50
Received By kstevens Date 2003-01-07 Time 08:24 Sent To  
Notes
2003-01-07 00:00:00PASSED/PROVISO
  
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN. FLOOR PLAN DOES NOT SHOW A BIDET
 IN MASTER BATH, A BAR SINK, OR A FOURTH
 BATHROOM WITH A SHOWER. A REVISION IS
 REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-28 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 16:02 Rev Time 0.33
Received By jleech Date 2002-09-28 Time 13:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2003-01-16 Cont ID  
Sent By jgomez Date 2003-01-16 Time 08:54 Rev Time 1.00
Received By jgomez Date 2003-01-16 Time 08:54 Sent To  
Notes
2003-01-16 00:00:00LIVING ROOM REVISION.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2003-01-09 Cont ID  
Sent By jgomez Date 2003-01-07 Time 15:08 Rev Time 0.50
Received By jgomez Date 2003-01-07 Time 15:08 Sent To  
Notes
2003-01-07 00:00:00NEED CORRECT IMPACT FEES PAID RECEIPT
 FOR LOT 34 AND STAMPED DRAWINGS.
 SEE PROVISO DATED 12-23-02 FOR ITEMS TO
 BE PROVIDED PRIOR TO CONSTRUCTION OR
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-01-09 Cont ID  
Sent By jgomez Date 2002-12-23 Time 13:34 Rev Time 3.00
Received By jgomez Date 2002-12-23 Time 13:34 Sent To E
Notes
2002-12-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE SOIL TEST REPORT WITH
 SOIL PREPARATION, FOOTING RECOMMENDA-
 TIONS AND SOIL BEARING CAPACITY.
 2-CALCULATIONS FOR HIGH STRENGTH PRECAST
 SOLID LINTELS: ENGINEER TO PROVIDE
 DOCUMENT WITH ORIGINAL SIGNATURE, SEAL
 AND DATE AS REQUIRED BY CHAPTER 471
 FL. STATUTES WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
 3-SPECIFY SAFETY GLASS FOR WINDOWS AT
 MASTER BATH AND BATH #2. SEC. 2405.2
 FBC 2001.
 4-PROVIDE COMPLETE & CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT AS PER CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
 5-PRODUCT APPROVAL FOR SINGLE SWING DOOR
 AT 2ND FLOOR DECK:
 A)DRAWINGS TO HAVE THE DADE COUNTY STAMP
 OF APPROVAL WITH LATEST NOA NUMBER.
 B)FRONT PAGE OF PRODUCT APPROVAL TO HAVE
 DADE COUNTY LOGO AT BOTTOM OF PAGE AS
 REQUIRED BY DADE COUNTY.
 C)VERIFY THAT THE DESIGN PRESSURES MEET
 THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
  
 6-PROVIDE FIREBLOCKING AT ALL CONCEALED
 SPACES, INCLUDING AT STAIRS AS REQ'D
 BY SEC. 2305.1.4 FBC 2001.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-12-13 Time 17:04 Rev Time 3.50
Received By jgomez Date 2002-11-04 Time 18:48 Sent To  
Notes
2002-11-04 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-IMPACT FEES: NEED STAMPED DRAWINGS AND
 PAID RECEIPT.
 3-PRELIMINARY SOIL REPORT SHOWS ORGANIC
 SOIL. REMOVE AS REQUIRED PER SECTION
 1804.108 FBC 2001.
 PROVIDE SOIL REPORT AT THIS LOT SHOW'G
 LOT PREPARATION AND BEARING CAPACITY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-INTERNAL PRESSURE COEFFICIENT GIVEN IN
 SHEET A1 SHALL BE GIVEN WITH PLUS AND
 MINUS SIGNS FOR PRESSURES ACTING
 TOWARD AND AWAY FROM THE INTERNAL
 SURFACES. SEE TABLE 6-7 ASCE 7-98.
 5-CLARIFY HOW'S THE GARAGE STEEL BOLLARD
 DETAIL DESIGNED TO PROVIDE VEHICLE IM-
 PACT PROTECTION TO A/C EQUIPMENT GIVEN
 THE SPECS SHOWN ON DETAIL ON SHEET A13
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE COMPLETE STRUCTURAL DETAIL AND
 SPECS FOR 4X8 SOLID LINTEL FOR DOORS
 AND WINDOWS ASSEMBLIES WITH TRANSOM
 ABOVE AS SHOWN ON PLANS. SEC 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 **OR PROVIDE PRODUCT APPROVAL SHOWING
 COMPLETE ASSEMBLIES AS SHOWN ON PLANS.
 7-PROVIDE ATTIC ACCESS AT SECOND FLOOR
 ROOF. SEC. 2309.6 FBC 2001.
 8-SPECIFY SAFETY GLASS FOR WINDOWS AT
 MASTER BATH AND BATH #2. SEC 2405.2
 FBC 2001.
 9-PROVIDE COMPLETE STRUCTURAL SECTION AT
 REAR PORCH SHOWING STRUCTURAL INSTALLA
 TION OF RAILING THAT COMPLIES WITH
 SEC. 1608.2 FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-REVISE TITLE OF DRAWING IN SHEET A7.
 THIS IS THE 2ND FLOOR FRAMING PLAN NOT
 1ST FLOOR FRAMING PLAN.
 11-REVISE NAILING SCHEDULE FOR ROOF
 SHEATHING. NEED MIN 8D RING SHANK AT
 MEAN ROOF HEIGHT GREATER THAN 25'.
 SEE TABLE 2306.1 CITY AMENDMENTS TO
 FBC 2001.
 12-STEEL HEADER DETAIL. A)CLARIFY SIZE
 ON DETAIL SHOWN ON SHEET A13: 2"X6"X
 1-1/4"?. B)SEE SIZE OF MULLIONS SPEC-
 FIED ON PLANS. C)SEE SECTION 1707.4.5
 FBC 2001 FOR REQUIREMENTS NEEDED FOR
 THE DESIGN OF MULLIONS AND PROVIDE ALL
 INFORMATION AS REQUIRED.
 13-SPECIFY SIZE OF WASHER AT STRUCTURAL
 GARAGE BUCK DETAIL. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 14-REVISE DETAIL FOR SWING DOOR JAMB.
 SEE SEC. 1707.4.4.2 FBC 2001.
 15-STORM SHUTTERS; A) PROVIDE COMPLETE
 KEY PLAN AND INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
 B)PROVIDE DADE COUNTY OR SBCCI PRODUCT
 APPROVAL OR PROVIDE COMPLETE INFORMA-
 TION FOR SITE SPECIFIC INSTALLATION.
 SEE CITY IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION.
 C)CLEARLY INDICATE ON DRWGS THE SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED (SEE INSTALLATION
 SCHEDULE ON STORM PANEL DWGS).
 16-CLARIFY WHICH GLASS BLOCK COMPANY IS
 GOING TO BE USED. THERE ARE TWO DIFFE-
 RENT COMPANIES SUBMITTED. ****NOTE:
 ONLY ONE OF THEM MEET THE DESIGN PRE-
 SSURES CALCULATED BY THE ARCHITECT.
 **ALSO, UL SPECIFICATIONS FOR ONE HOUR
 FIRE RATED ASSEMBLY.
 **PROVIDE INFORMATION SHOWING FACE THICK
 NESS OF GLASS BLOCK TO VERIFY IF SAFE-
 TY GLASS IS REQUIRED. SEC. 2405.2.2
 FBC 2001.
 17-SWING DOORS: THIS BUILDING DEPARTMENT
 DOESN'T ACCEPT BROWARD COUNTY PRODUCT
 APPROVALS. ***NOTE: ALSO, THEY DON'T
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT.
 18-FIXED WINDOWS: SOME WINDOWS DON'T
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT.***NOTE: PRODUCT
 APPROVAL TO SPECIFY HOW ARE WINDOWS TO
 BE ATTACHED TO STEEL TRANSOM.
 19-SLIDING GLASS DOORS PRODUCT APPROVAL
 AND DRAWINGS DON'T MATCH.
 **ALSO, MISSING PAGE TWO OF THE REPORT
 HAVING THE LIMITATIONS ON THE PRODUCT
 APPLICATIONS.
 **NOTE: DOORS DON'T MEET THE PRESSURES
 CALCULATED BY THE ARCHITECT.
 20-PROVIDE PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS THAT MEET THE PRESSURES
 CALCULATED BY THE ARCHITECT. ***SOME
 WINDOWS DON'T MEET THOSE PRESSURES.
 21-MULLION PRODUCT APPROVAL IS FOR
 VERTICAL APPLICATIONS. NEED PRODUCT
 APPROVAL FOR HORIZONTAL MULLION (EG:
 AT SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. AND OTHER DESIGN. SEE PLANS).
  
  
 NOTE: IF YOU HAVE ANY QUESTIONS OR
 COMMENTS, PLEASE CONTACT JULIO
 GOMEZ AT (561)659-8096 X 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-15 Cont ID  
Sent By btrobaug Date 2002-10-30 Time 17:44 Rev Time 4.00
Received By jgomez Date 2002-10-15 Time 16:36 Sent To  
Notes
2002-10-15 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAID IMPACT FEES. BRING STAMPED DWGS
 AND PAID RECEIPT.
 3-PROVIDE COMPLETE SOIL TEST REPORT WITH
 ORIGINAL SIGNATURE AND ENGINEER'S SEAL
 AS REQUIRED BY CHAPTER 471 FL STATUTE.
 **NOTE: PRELIMINARY BORING SHOW ORGANIC
 SOIL. REMOVE AS REQ'D BY SEC. 1804.1.8
 FBC 2001.
 **SOIL TEST REPORT TO SPECIFY SOIL PREP.
 AND SOIL BEARING CAPACITY.
 4-DRAWINGS TO INCLUDE ALL INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 5-SHEET A-3: A)CLARIFY COLS. SPECIFIED
 FOR GARAGE DOOR. DRAWING SHOWS FILLED
 CELLS BUT NOTE CALLS FOR POURED CONC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 B)SPECIFY SUPPORTS AND SPACING FOR WWM
 ON CONCRETE SLAB. SEC. 1909.3 FBC 2001
 6-SHEET A-5: A)SPECIFY ONE HOUR FIRE
 RATED GLASS BLOCK ASSEMBLY AT ZERO LOT
 LINE. TABLE 600 FBC 2001.
 B)PROVIDE STRUCTURAL DETAIL FOR BOLLARD
 OR 3" STEEL POST AT GARAGE. SEC .
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS FOR 4X8 SOLID LINTEL FOR
 DOORS AND WINDOWS ASEMBLIES W/ TRANSOM
 ABOVE. SEC. 104.2.1.2 CITY AMENDMENTS.
 D)GARAGE VENTILATION IS NOT ALLOWED AT
 ZERO LOT LINE WALL. TABLE 600 FBC 2001
 NOT OPENINGS ALLOWED.
 E)PROVIDE ATTIC ACCESS ABOVE GARAGE.
 SEC. 2309.6 FBC 2001.
 F)CONSTRUCTION TYPE SPECIFIED IS WRONG.
 REVISE AS REQUIRED. SEE CHAPTER 6 FBC.
 7-SHEET A-6: A)PROVIDE ATTIC ACCESS.
 SEC. 2309.6 FBC 2001.
 B)SPECIFY SAFETY GLASS FOR WINDOWS AT
 MASTER BATH & BATH 2. SEC. 2405.2 FBC
 **NOTE: GLASS BLOCK IN MASTER BATH TO BE
 SAFETY GLASS IF UNIFORM FACE THICKNESS
 IS LESS THAN 0.25". SEC. 2405.2.2 FBC.
 C)SPECIFY ONE HR FIRE RATED GLASS BLOCK
 AT ZERO LOT LINE WALL. TABLE 600 FBC.
 D)WRITE ON PLAN THAT LOFT AREA IS NOT TO
 BE USED FOR SLEEPING PURPOSES OR PROVI
 DE WINDOW THAT COMPLIES WITH EGRESS
 REQUIREMENTS. SEC. 1005.4.4 FBC 2001.
 8-SHEET A-7: A)PROVIDE COMPLETE SECTION
 DETAIL AT REAR PORCH SHOWING RAILING
 INSTALLATION TO COMPLY WITH SECTION
 1608.2 FBC 2001.
 B)SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION ON 2ND FLOOR FRAMING PLAN.
 SEC. 2305.2.2 FBC 2001. DO NOT CITE
 AS PER CODE. BE SPECIFIC.
 C)SPECIFY FIREBLOCKING MATERIAL & LOCA-
 TION AT STAIR SECTION. SEE SECTION
 2305.1.4 FBC FOR REQUIRED LOCATION.
 **NOTE: PROVIDE GENERAL SPECIFICATIONS
 FOR FIREBLOCKING REQUIRED AT ALL
 CONCEALED SPACES. SEE SEC. 2305.1.4
 D)REVISE TITLE OF DRAWING. THIS IS THE
 2ND FLOOR FRAMING PLAN NOT 1ST FLOOR.
 9-SHEET A-8: A)SPECIFY CONNECTORS FOR
 ALL BEAMS @ FRONT PORCH. SEC 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE UPLIFT VALUE FOR DOUBLE TA13
 CONNECTOR. SEE LATEST USP CATALOGUE
 FOR ENGINEERED VALUE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 10-SHEET A-12: A)REVISE NAILING SCHEDULE
 FOR ROOF SHEATHING. NEED 8D RING SHANK
 FOR ROOF ABOVE 25" MEAN ROOF HEIGHT.
 SEE TABLE 2306.1 CITY AMENDMENTS FBC.
 11-SHEET A-13: A)REVISE GENERAL NOTES.
 HUGHES AND SEMCO CONNECTORS ARE OUT
 OF BUSINESS.
 B)REVISE GLASS BLOCK DETAIL. SEE UL
 SPECS FOR ONE HR FIRE RATED ASSEMBLY.
 REQUIRED BY TABLE 600 FBC 2001.
 C)PROVIDE COMPLETE INFORMATION FOR 2"
 STEEL HEADER DETAIL. NEED TO SPECIFY
 WELDING FOR PLATE & COMPLETE SPECS FOR
 STEEL TUBE TO BE USED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)SPECIFY SIZE OF WASHER GARAGE DOOR
 BUCK DETAIL. SEC. 104.2.1.2 CITY AMEND
 E)SCREEN ENCLOSURE UNDER SEPARATE PERMIT
 F)REVISE DETAIL FOR SWING DOOR JAMB. SEE
 SEC. 1707.4.4.2 FBC 2001.
 12-STORM SHUTTERS:A)PROVIDE COMPLETE KEY
 PLAN AND INSTALLATION SCHEDULE (SEE
 CITY SAMPLE).
 B)PROVIDE DADE COUNTY OR SBCCI PRODUCT
 APPROVAL OR SEE ITEMS 15, 16 AND 17 OF
 CITY IMPLEMENTATION STANDARD FOR HU-
 RRICANE MISSILE IMPACT PROTECTION FOR
 SITE SPECIFIC PRODUCT APPROVALS.
 13-PROVIDE PRODUCT APPROVAL FOR:
 A)EXTERIOR SWING DOORS @ ENTRY & 2ND FL.
 BROWARD COUNTY PRODUCT APPROVAL IS NOT
 ACCEPTED. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR SITE SPECIFIC
 INSTALLATIONS. ***NOTE: SEE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 B)CLARIFY WHICH GLASS BLOCK MANUFACTURER
 IS GOING TO BE USED. PROVIDE COMPLETE
 UL SPECS FOR 1HR FIRE RATED ASSEMBLY.
 **NOTE: SAFETY GLASS REQUIRED IF FACE
 THICKNESS IS LESS THAN 0.25".
 C)FIXED WINDS PRODUCT APPROVAL: CLEARLY
 INDICATE WHICH TYPE OF WINDOWS TO BE
 USED (IMPACT, NON IMPACT).
 **SOME WINDOWS DON'T MEET THE DESIGN PRE
 SSURES CALCULATED BY THE ARCHITECT.
 **PRODUCT APPROVAL TO SPECIFY ANCHORING
 TO THE STEEL TRANSOM AS SHOWN ON PLANS
 D)SLIDING GLASS DOORS DRAWINGS DON'T
 MATCH PRODUCT APPROVAL. SEE ACCEPTANCE
 NUMBER BY DADE COUNTY.
 **MISSING PAGE TWO OF PRODUCT APPROVAL.
 **SEE DESIGN PRESSURES CALCULATED BY
 ARCHITECT.
 E)PROVIDE PRODUCT APPROVAL FOR SINGLE
 HUNG WINDOWS THAT MEET THE DESIGN PRE-
 SSURES CALCULATED BY ARCHITECT. EG:
 SEE WINDOWS J, O, LL AND MM.
 F)PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLIONS.
 14-OWES $152.92 FOR UPDTED VALUATION AND
 RADON FEES.
  
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS AE DONE TO ORIGINAL DWGS TO
 EXPEDITE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By sgraham Date 2002-09-25 Time 09:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***