Plan Review Details - Permit 02091027
Plan Review Stops For Permit 02091027
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-29 Cont ID  
Sent By jwitmer Date 2004-06-29 Time 16:02 Rev Time 0.33
Received By jwitmer Date 2004-06-29 Time 16:02 Sent To  
Notes
2004-06-29 00:00:00SUBMITTAL 4080 HMD-F FLUSH OUTSWING
 COMMERCIAL STEEL DOOR-IMPACT

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-29 Cont ID  
Sent By jwitmer Date 2004-06-29 Time 15:58 Rev Time 0.55
Received By jwitmer Date 2004-06-29 Time 15:58 Sent To  
Notes
2004-06-29 00:00:00SUBMITTAL 6-28-04 RE: MANAGERS OFFICE
 (NEW PARTITION)JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-29 Cont ID  
Sent By jwitmer Date 2004-06-29 Time 15:36 Rev Time 0.55
Received By jwitmer Date 2004-06-29 Time 15:36 Sent To PC
Notes
2004-06-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02091027
 ADD: 1600 PRESIDENTIAL WAY
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SUBMITTAL: FIRE RATED CHASE FOR ELECTRIC
 AL CONDUIT IN STAIR TOWER
  
 ACTION: DENIED
 1) 1006.1.3.1 PENETRATIONS INTO & OPEN-
 INGS THROUGH A STAIRWAY ENCLOSURE
 ASSEMBLY ARE PROHIBITED EXCEPT FOR
 REQUIRED EXIT DOORS, DUCTWORK & EQUIP-
 MENT NECCESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, AND ELECTRICAL CONDUIT SERV-
 ING THE STAIRWAY AND TERMINATING AT A
 STEEL BOX NOT EXCEEDING 16 SQ IN.SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH 705.4. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS,
 WETHER PROTECTED OR NOT, BETWEEN ADJA-
 CENT STAIRWAYS.
  
 2) THE SECOND ISSUE IS NO LOCATION IS
 GIVEN IN THE STAIRWAY, SEE 1007.4.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-06-28 Time 14:25 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2004-05-03 00:00:00REVISION: 2" HOLE IN ELEVATOR HEADER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-11 Cont ID  
Sent By csiegber Date 2004-05-03 Time 14:32 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-11 00:00:00REVISION : STAIR TOWER LOCATION 3 SHEETS
 8X11 FOR B- STAIR TOWERJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-26 Cont ID  
Sent By jwitmer Date 2002-09-26 Time 08:19 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-09-26 00:00:00ALL REVIEWS UNDER MASTER # 02060714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-26 Cont ID  
Sent By dpalmer Date 2002-09-26 Time 06:23 Rev Time 0.00
Received By dpalmer Date 2002-09-26 Time 06:23 Sent To  
Notes
2002-09-26 00:00:0002060714

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 10:15 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 14:25 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 14:25 Sent To B
Notes
2004-06-28 00:00:00TO JW DESK/SUBMITTAL/FIRE RATED CHASES
 FOR ELECTRICAL CONDUIT IN STAIR TOWER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 14:32 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 14:32 Sent To B
Notes
2004-05-03 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:32 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:32 Sent To B
Notes
2003-07-17 00:00:00JW DESK, 5 SUBMITTALS, PRODUCT APPROVALS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By pkrauss Date 2003-07-17 Time 16:09 Rev Time 0.35
Received By pkrauss Date 2003-07-17 Time 16:09 Sent To  
Notes
2003-07-17 00:00:00MECH REV - REVISION FILED WITH MASTER
 PERMIT 02060714