Plan Review Details - Permit 02090928
Plan Review Stops For Permit 02090928
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-12-15 Cont ID  
Sent By dpalmer Date 2004-07-20 Time 16:00 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
2003-12-15 00:00:00APPROVED REVISIONLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-01 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:41 Rev Time 0.00
Received By hpiskura Date 2003-04-01 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-19 Cont ID  
Sent By hpiskura Date 2003-02-19 Time 14:53 Rev Time 0.00
Received By hpiskura Date 2003-02-19 Time 09:07 Sent To  
Notes
2003-02-19 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
  
 THE SPECIFICATIONS BOOKS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE SEVERAL
 DESIGN PROFESSIONALS WHEN SUBMITTED FOR
 PUBLIC RECORD.FBC 104.2.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-28 Cont ID  
Sent By hpiskura Date 2002-10-28 Time 14:52 Rev Time 0.00
Received By hpiskura Date 2002-10-24 Time 09:14 Sent To  
Notes
2002-10-28 00:00:00PAID PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 AT THE TIME OF PERMIT APPLICATION A
 RECENT PROPERTY SURVEY AND A SITE PLAN
 WITH DIMENSIONS LOCATING ALL OF THE
 STRUCTURES RELATIVE TO THE PROPERTY
 LINES AND EACH OTHER WILL BE NECESSARY.
  
 SHOW THE DESIGN INFORMATION FOR THE
 PRE-ENGINEERED BUILDINGS.
  
 ALL GLAZED PORTIONS OF THE EXTERIOR WALL
 AND ROOF OF THE BUILDING MUST COMPLY
 WITH THE HURRICANE MISSILE IMPACT
 RESISTANCE REQUIREMENTS OF FBC 1606.1.4
 INCLUDING THE TRANSLUCENT PANELS.SEE
 ALSO FBC 2604.4 RE: WALL PANELS.
  
 THE ARCHITECTURAL SHEET A6.3 DECLARES
 EXPOSURE B, AND S1 CITES EXPOSURE C.
 PLEASE CLARIFY WHO WILL BE ENGINEER OF
 RECORD AND WHAT PORTIONS OF DESIGN ARE
 TO BE DELEGATED.
  
 SHOW THE STRUCTURAL INFORMATION FOR THE
 OVER HEAD CRANE.
  
 SHEET A 4.1 SHOWS VARIOUS EXTERIOR WALL
 ASSEMBLIES.PROVIDE THE STRUCTURAL
 DETAILS AS TO THE TYPE OF CONNECTIONS
 AND THE LOADS TRANSFERRED TO THE METAL
 BUILDING SYSTEM.
  
 WHAT IS THE MATERIAL CALLED OUT AS >>1"
 MASONRY MAT CONT AS SPECIFIED<< ON
 SHEET A4.1 AND ELSEWHERE?
  
 HOW WERE THE DOOR AND WINDOW PRESSURES
 ON SHEET A6.3 DETERMINED?
  
 SHEET A6.2, HOW ARE THE VARIOUS DOOR AND
 WINDOW HEADER/SILL,ETC. ATTACHED TO
 THE BUILDING?
  
 SHEET S1 CALLS FOR FOOTINGS TO BE POURED
 WITHOUT FORMS.CITY AMENDMENTS TO FBC
 1804.1.1 REQUIRE ALL FOOTINGS AND
 CONCRETE PADS TO BE FORMED FULL DEPTH.
 PLEASE REVISE AS NECESSARY.
  
 SHOW THE DESIGN INFORMATION FOR THE
 REINFORCED MASONRY, IE F'M, GROUT
 STRENGTH, ETC.SEE FBC 2103.1.
  
 SHOW THE PROVISIONS FOR TERMITE
 PROTECTION IN ACCORDANCE WITH FBC
 1816.1.7.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2004-07-20 Cont ID  
Sent By dpalmer Date 2004-07-20 Time 16:00 Rev Time 0.50
Received By dpalmer Date 2004-07-20 Time 16:00 Sent To B
Notes
2004-07-20 00:00:00SENT TO BLDG, SOME A & S SHEETS DO NOT
 CONTAIN CITY STAMP.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-19 Time 17:08 Rev Time 0.50
Received By dpalmer Date 2004-07-16 Time 13:36 Sent To  
Notes
2004-07-16 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS
 REVIEW.
 PLEASE INCLUDE ALL INFORMATION AS REQ-
 -UIRED UNDER FAC 61G15-23.002 AND
 FS 471.023.
 PLEASE SEE THE SHEET THAT WAS CORRECTED
 E2.1 NOW ONLY HAS NAME AND ENG'S #.
  
 PLEASE SEE THAT IS IS REQUIRED OF ANY
 AND ALL SHEETS DONE BY THIS FIRM, INCLUD
 -ING OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:46 Rev Time 1.00
Received By dpalmer Date 2004-07-01 Time 13:46 Sent To  
Notes
2004-07-01 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE REVISIONS ON PLANS
 NEED TO CORRELATE WITH REVISION #'S ON
 TITLE BLOCK. PLEASE SEE MISSING REV #8?
  
 2)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE AS REQUIRED UNDER FAC 61G15-23
 .002, FS 471.023.
 PLEASE SEE LICENSE #'S ARE REQUIRED FOR
 ALL SHEETS AND TRADES.
 PLEASE ALSO SEE FAC 61G1-16.004, AND
 FS 481.219 FOR ARCH'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-11-07 Cont ID  
Sent By csiegber Date 2004-06-25 Time 11:08 Rev Time 0.75
Received By dpalmer Date 2003-11-07 Time 06:37 Sent To  
Notes
2003-11-07 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 IN TITLE BLOCK AS REQUIRED UNDER
 FAC 61G1-16.002 AND FS481
 NAMES, ADDRESS AND ALL LICENSE #'S REQ'D
 AR`S/ AA'S ETC.
 NAME OF PERSON SEALING PLANS IS ALSO
 REQ'D.
  
 PLEASE SEE THAT THIS IS REQ'D ON ALL
 SHEETS AND SETS AND WEATHER OR NOT
 COMMENT IS MADE ON OTHER REVIEWS.
  
 PLEASE SEE COMMENTS FROM OTHERE REVIEWS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-04-23 Cont ID  
Sent By dpalmer Date 2003-04-23 Time 10:14 Rev Time 0.50
Received By dpalmer Date 2003-04-23 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-15 Time 06:03 Rev Time 0.50
Received By dpalmer Date 2003-04-15 Time 05:56 Sent To  
Notes
2003-04-15 00:00:00*********** UNSAT ***************
  
 PLEASE SEE THAT NOW ONLY ONE NEW SHEET
 E-5 WAS SUBMITTED INTO ONE SET. PLEASE
 SEE PREVIOUS NOTES AND TELEPHONE CONVER-
 SATION REQUESTING TWO COMPLETED SETS
 W/ NEW SHEET E-5.
 PLANS WERE SUBMITTED FOR FORTH REVIEW
 AND 4TH PLAN REVIEW WAS WAIVED PER
 BILL STAPLES (ASST BLDG OFFICIAL)
  
 PLEASE SEETHE ABOVE NOTES. PLEASE
 SUBMIT TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 IF THERE ARE ANY QUESTIONS, ONCE AGAIN,
 PLEASE CALL. OR E-MAIL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-03-25 Cont ID  
Sent By dpalmer Date 2003-03-25 Time 15:50 Rev Time 2.00
Received By dpalmer Date 2003-03-25 Time 15:50 Sent To  
Notes
2003-03-25 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE, UNABLE TO DO COMPLETE PLAN
 REVIEW AT THIS TIME.
 PLANS HAVE COME BACK IN W/OUT SHEET E-5
 AND NOTES FROM PREVIOUS REVIEW AND
 RESPONSE LETTER CAN NOT BE VERIFIED AT
 THIS TIME.
  
 PLEASE TAKE OUT ALL OLD SHEETS AND
 INSERT NEW SHEETS FOR TWO COMPLETE SETS.
 ONE SET OF OF OLD SHEETS SHOULD BE
 SUBMITTED FOR ANY CLARIFICATION THAT
 MAY BE NEEDED. THESE WILL COME BACK
 WHEN ISSUED FOR PERMIT.
  
 1)NOTE: PLEASE SEE TRANSFORMER TX-2,
 STILL ONLY SHOWN TO COLD WATER. THIS
 CAN BE REDLINED AND DOES NOT NEED TO
 HAVE NEW E-4 SUBMITTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-21 Cont ID  
Sent By dpalmer Date 2003-02-21 Time 05:42 Rev Time 0.50
Received By dpalmer Date 2003-02-21 Time 05:42 Sent To  
Notes
2003-02-21 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 ING OF EM/EXT LTS, PLEASE CLARIFY
 SHOWING GOING THRU C2 CONTACTOR??
 MAY NOT BE SWITCHED. PLANS NEED TO
 CLARIFY OR NOTE, TO BE ON LINE SIDE OF
 CIRCUIT IN CONTACTOR.
  
 2)NOTE: PLEASE SEE NOTE 2 OF FIRST
 REVIEW, PLEASE NOTE CLASS/DIVISION NOTE
 ON PLAN. IT IS NOTED RECEPTS TO BE AT
 24 ", BUT NEEDS TO NOTE ANY BELOW
 TO BE INSTALLED PER 511.
  
 3)NOTE: PLEASE CLARIFY LOAD SHOWN ON
 LOAD ANALYSIS FOR RECEPTS? 220-13
  
 4)NOTE: RESPONSE TO NOTE 7 FROM REVIEW
 SHOWS TRANSFORMER BEING BONDED TO COLD
 WATER. PLEASE NOTE IF ANY OF THE COLD
 WATER LINE IS BROKEN WITH THE USE OF
 PVC/CPVC OR INTERUPTED BY REPAIR, THE
 TRANSFORMER WOULD NOT HAVE A GROUND.
 PLEASE SHOW GOING TO EFFECTIVE GROUND/
 BLDG/FOOTER STEEL.THERE IS AN EXCEPT TO
 USE METAL CWP, HOWEVER, PLEASE SEE FIRST
 PART OF THIS NOTE, THIS HAS HAPPENED
 IN THE PAST AND HAS CREATED A LIFE
 SAFETY ISSUE.
  
 5)NOTE: PLEASE ALSO SHOW GROUNDING AT
 WASH BLDG. IT SHOWS AN EQUIPMENT GROUND
 FROM MAIN BLDG, PLEASE SHOW BONDING OF
 FOOTER STEEL AND COLD WATER.
  
 PLANS HAVE MOST COMMENTS ADDRESSED AND
 ARE IN GOOD SHAPE. PLEASE SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-19 Cont ID  
Sent By dpalmer Date 2002-09-19 Time 06:32 Rev Time 1.25
Received By dpalmer Date 2002-09-19 Time 06:06 Sent To  
Notes
2002-09-19 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE LABELING OF CIRCUITS
 ON PANEL SCHEDULE. PLEASE ALSO NOTE
 LABELING OF EM LTS/EXITS LTS PER 700-12.
  
 2)NOTE: IT IS NOTED THAT PLAN SHOWS/NOTE
 -S ALL RECEPTS 24" AFF. PLEASE LIST
 CLASS/DIVISION. PER ART 500.
  
 3)NOTE: PLEASE LIST/CLARIFY PANELS "H"
 AND "P1? ARE PANEL FEED-THRU? PLEASE
 SEE 384-15
  
 4)NOTE; PLEASE CLAIRY "SHOW" WINDOW
 OUTLETS REQ`D PER 210-62. PLEASE ALSO
 LIST ON PANEL SCHEDULE.
  
 5)NOTE: PLEASE NOTE THAT PER FS/FAC
 553-79 (6)(A) PLANS ARE REQ`D TO BE
 SIGNED,DATED, AND SEALED BY A PE.
 PLEASE ALSO NOTE PLANS HAVE A TITLE
 BLOCK FROM AN ENGINEER THEREFORE REQ`D
 TO BE SIGNED, DATE AND SEALED PER FAC/FS
 61G15-23.002.
  
 6)NOTE: PLEASE NOTE, PANELS ARE SHOWING
 ALL LOAD CALCS AT CONN LOADS.
 PLEASE NOTE THAT LOAD CALCULATIONS ARE
 REQ`D TO BE SHOWN PER 215-5. PLEASE
 NOTE, 220-3,220-10,220-11,220-13, PLEASE
 ALSO NOTE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. 215-3,230-42.
  
 7)NOTE; PLEASE PROVIDE INFORMATION AND/
 OR SHOW GROUNDING ELECTRODE SYSTEM PER
 250-50. BLDG/FOOTER STEEL, COLD WATER,
 GRND RODS? PLEASE ALSO NOTE GROUNDING
 ELECTRODE SYSTEM FOR DETACHED BLDG PER
 250-32.
 PLEASE SHOW DEATIL FOR GROUNDING OF
 TRANSFORMERS PER 250-31.
  
 8)NOTE:IT IS NOTED THAT AIC RATINGS ARE
 SHOWN ON PANELS. PLEASE PROVIDE AIC
 RATINGS FOR ALL NEW EQUIPMENTS.
 MAINS/PANELS/BRKRS MUST BE RATED FOR
 AVAILABLE FAULT CURRENT. 110-9.
  
 9)NOTE: PLEASE CLARIFY LOADS BEING
 SHOWN ON PANEL SCHEDULES AND NOTHING
 BEING LISTED ON PANELS SCHEDULE?
  
 10)NOTE:PLEASE SEE ANY COMMENTS FROM
 OTHER REVIEWERS THAT MAY HAVE AN AFFECT
 ON THE ELECTRICAL PLANS AND/OR LAYOUT.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-03-24 Cont ID  
Sent By mamini Date 2003-03-24 Time 13:52 Rev Time 1.00
Received By mamini Date 2003-03-24 Time 13:51 Sent To  
Notes
2003-03-24 00:00:00PASSED :
 1. SEE PERMIT # 03031769 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-02-12 Cont ID  
Sent By mamini Date 2003-02-12 Time 11:27 Rev Time 2.00
Received By mamini Date 2003-02-12 Time 10:42 Sent To  
Notes
2003-02-12 00:00:00PASSED:
 1. UNDERGROUND UTILITIES AND CIVIL SITE
 PLANS FOR THE PROPOSED PROJECT HAS BEEN
 APPROVED, HOWEVER A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL SITE WORKS AT THE
 TIME OF ACTUAL PERMITTING WILL BE
 REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By mamini Date 2002-09-24 Time 14:27 Rev Time 1.00
Received By mamini Date 2002-09-24 Time 14:27 Sent To  
Notes
2002-09-24 00:00:00FAILED :
 1. PLEASE PROVIDE CIVIL/ SITE PLANS FOR
 OUR REVIEW AND APPROVAL. PLAN MUST
 INCLUDE STORM WATER, PERVIOUS AND IMPER-
 VIOUS CALCULATIONS AND POLLUTION
 PREVENTION (BMPS) .
 2. THE NEW WASH CACILITY MUST BE
 EQUIPPED WITH OIL AND SAND SEPARATOR
 ASSEMBLIES. CALL RODNEY COMPO FOR CITY
 REQUIREMENTS AND STANDARDS, 837-4051.
 3. A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL/ SITE UNDERGROUND
 UTILITIES AT THE TIME OF ACTUAL PERMITT-
 ING WILL BE REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-11-24 Cont ID  
Sent By mcarsill Date 2003-11-24 Time 16:19 Rev Time 0.00
Received By mcarsill Date 2003-11-24 Time 16:19 Sent To  
Notes
2003-11-24 00:00:001) THE FIRE HYDRANT INSTALLED IN THE
 REAR DISPLAYS FOUR CONCRETE BOLLARDS.
 THE BOLLARDS SHALL ALLOW FOR 7'-6"
 CLEARANCE TO THE FRONT AND SIDE OF IT.
 FOUR FEET CLEARANCE IS REQUIRED TO THE
 REAR OF THE HYDRANT.
  
 2) ALL WELDING PERFORMED ON SITE MUST
 BE APPROVED BY THE BUREAU OF FIRE
 PREVENTION. ALL WELDING SHALL COMPLY
 WITH NFPA 51B, THE STANDARD FOR CUTTING
 AND WELDING. NO COMBUSTIBLE MATERIAL
 IS ALLOWED WITHIN 35 FEET OF ANY
 WELDING ACTIVITIES.
  
 3) BUILDING ADDRESS NOTE SHOWN ON
 ELEVATION DRAWINGS SHOULD INDICATE
 6" HIGH NUMERALS.
  
 4) PLEASE PROVIDE PRODUCT APPROVALS
 FOR ROLLING FIRE DOOR.
  
 5) THE EXTERIOR GATES DO NOT HAVE TO
 OPEN WHEN THE FIRE ALARM SYSTEM
 ACTIVATES.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-04-16 Cont ID  
Sent By nmccray Date 2003-04-16 Time 10:06 Rev Time 0.00
Received By nmccray Date 2003-04-16 Time 10:06 Sent To  
Notes
2003-04-16 00:00:00PLANS REVIEWED BY LT. MIKE WENNERGREN
 ON 04/15/03

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-03-28 Cont ID  
Sent By mcarsill Date 2003-03-28 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2003-03-28 Time 13:02 Sent To  
Notes
2003-03-28 00:00:001) THE EXISTING FIRE HYDRANT LOCATED
 IN THE EQUIPMENT YARD APPEARS TO BE
 LOCATED DIRECTLY NEXT TO THE BUILDING.
 THE FIRE HYDRANT LOCATED IN THE REAR
 YARD IS TO BE A SUFFICIENT DISTANCE
 FROM THE BUILDING. ALL FIRE HYDRANTS
 SHALL BE PROVIDED WITH A MINIMUM OF
 7'- 6" TO THE FRONT AND SIDES. A MINIMUM
 OF 4' IS REQUIRED TO THE REAR.
  
 2) AN EXIT SIGN IS MISSING NEAR DOOR
 LOCATED NEAR COMPRESSOR 131.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-02-26 Cont ID  
Sent By mcarsill Date 2003-02-26 Time 16:05 Rev Time 0.00
Received By mcarsill Date 2003-02-26 Time 16:05 Sent To  
Notes
2003-02-26 00:00:001) EXISTING FIRE HYDRANT ON PAGE A0.2
 APPEARS TO BE POSITIONED DIRECTLY NEXT
 TO THE LUBRICATION TANK CONTAINMENT
 AREA. FIRE HYDRANTS ARE NOT TO BE
 POSITIONED NEXT TO POTENTIAL HAZARDS
 AND MINIMUM CLEARANCES ARE REQUIRED TO
 THEM PER STATE LAW.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW ABOVEGROUND 1000 GALLON FUEL
 TANK. WHEN SUBMITTED PRODUCT APPROVALS
 AND CUT SHEETS ARE TO BE PROVIDED.
  
 3) GATES THAT FIRE AND PARAMEDICAL
 EQUIPMENT ARE EXPECTED PASS THRU MUST
 BE AT LEAST 20 FEET IN CLEAR WIDTH.
  
 4) PLEASE BE ADVISED THAT ALL CUTTING
 AND WELDING IS TO BE PERFORMED IN
 ACCORDANCE WITH NFPA 51B, THE STANDARD
 FOR CUTTING AND WELDING. A MINIMUM OF
 35 FOOT CLEARANCE TO ANY AND ALL
 COMBUSTIBLE MATERIAL OR FLAMMABLE
 MATERIALS SHALL BE PROVIDED. NO
 CUTTING OR WELDING IS TO BE PERFORMED
 WITHOUT PRIOR FIRE DEPARTMENT APPROVAL.
  
 5) SEPARATE PLANS AND PERMITS FOR ANY
 SECURITY GATES OR FENCES.
  
 6) TYPICAL FIRE HYDRANT CONNECTION SHOWS
 A MINIMUM FROM A HYDRANT TO A BOLLARD
 AS THREE FEET. IT SHOULD BE AT LEAST
 FOUR FEET.
  
 7) ELECTRONIC SWITCHES ARE REQUIRED ON
 OS&Y CONTROL VALVES FOR FIRE LINES.
  
 8) FLOOR PLAN SHOULD IDENTIFY AREAS
 FOR POTENTIAL CUTTING AND WELDING
 OPERATIONS.
  
 9) BUILDING ELEVATION SHALL SHOW
 LOCATION OF ADDRESS.
  
 10) PLEASE INDICATE IF ANY FLAMMABLE
 OR COMBUSTIBLE LIQUIDS WILL BE STORED
 IN THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 10:05 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 10:05 Sent To  
Notes
2002-10-04 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
 IT APPEARS THAT AN ADDITIONAL FIRE
 HYDRANT WILL BE REQUIRED IN THE REAR
 YARD.
  
 2) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF SIX INCH NUMBERS ARE REQUIRED.
  
 3) HOW DOES FIRE RESCUE ACCESS THE
 MOTORIZED GATES. WHAT PROVISIONS HAVE
 BEEN MADE TO ALLOW ACCESS. WHAT HAPPENS
 WHEN LOSS OF POWER OCCURS. ARE THE
 GATES FAIL SAFE OR FAIL SECURE.
  
 4) NOTE 2 ON PAGE U2. IF THE FIRE ALARM
 SYSTEM ACTIVATES AFTER HOURS, DO YOU
 WANT THE GATES TO OPEN, IT COULD POSE A
 POSSIBLE SECURITY PROBLEM.
  
 5) A KNOX-BOX WILL BE REQUIRED TO ALLOW
 FOR FIRE RESCUE ACCESS TO THE BUILDING.
  
 6) WILL THERE BE ANY CUTTING OR WELDING
 DONE ON SITE. IF SO WHERE.
  
 7) MORE DETAILS REQUIRED FOR OIL AND
 FUEL TANK STORAGE. ALSO THE CITY OF
 WEST PALM BEACH HAS A HAZARDOUS
 MATERIALS ORDINANCE. PLEASE REVIEW
 DOCUMENT. ALSO PLEASE INDICATE ANY
 WARNING SIGNS, LABELS, AND SAFEQUARDS
 PLANNED FOR THE OIL AND GAS STORAGE.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATION.
  
 9) EXIT DOOR SHOULD BE RELOCATED AWAY
 FROM OIL TANKS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 17:08 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 17:08 Sent To E
Notes
2004-07-19 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:46 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:46 Sent To E
Notes
2004-07-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 11:08 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 11:07 Sent To E
Notes
2004-06-25 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:41 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 09:41 Sent To B
Notes
2003-12-05 00:00:00TO HP DESK/SUBMITTAL-ANCHOR BOLTS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 14:46 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 14:46 Sent To  
Notes
2003-11-06 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-07 Time 09:29 Rev Time 0.00
Received By shernand Date 2003-04-07 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-13 Cont ID  
Sent By sgraham Date 2003-03-25 Time 16:38 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 11:36 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 13:17 Sent To  
Notes
2003-02-11 00:00:00TO COMM BOARD# 18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-04 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 13:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-08-10 Cont ID  
Sent By pkrauss Date 2004-08-10 Time 11:58 Rev Time 0.30
Received By pkrauss Date 2004-08-10 Time 11:58 Sent To  
Notes
2004-08-10 00:00:00REVISED CONDENSING UNIT.ORIGINAL
 SUBMITTAL INDICATED C.U. ON CURB.
 REVISED TO STANDS.SUBMITTED ENGINEER
 DETAIL FOR THE ATTACHMENT TO THE ROOF
 AND HEIGHT OF THE STAND.
  
 PLEASE NOTE REVISION WAS SUBMITTED AFTER
 C.O. WAS ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2004-07-28 Cont ID  
Sent By hmoser Date 2004-07-28 Time 15:27 Rev Time 0.50
Received By hmoser Date 2004-07-28 Time 15:27 Sent To  
Notes
2004-07-28 00:00:00PLAN DENIED
 NEED ENGINEER DRAWING NO CONDENSOR STAND
 TIEDOWN TO ROOF.YOU SENT A ROOF CURB
 SUBMITTAL.WITH NO SEAL.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-07-26 Cont ID  
Sent By pkrauss Date 2004-07-26 Time 06:06 Rev Time 0.30
Received By pkrauss Date 2004-07-26 Time 06:00 Sent To  
Notes
2004-07-26 00:00:00REVISION TO THE CURB & PLENUM SIZE.
 SIGNED, SEALED & DATED ENGINEER LETTER
 SUBMITTED INDICATING APPROVAL OF THE
 CHANGES PROPSED BY PREFERRED A/C.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-05-24 Cont ID  
Sent By hmoser Date 2004-05-24 Time 13:13 Rev Time 1.00
Received By hmoser Date 2004-05-24 Time 13:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-05-21 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 08:52 Rev Time 0.55
Received By hmoser Date 2003-11-24 Time 08:50 Sent To  
Notes
2003-11-24 00:00:00DENIED:
 1.PER 2001 FBC(M) 307.2.3, THE
 AUXILIARY DRAIN LINE SHALL TERMINATE AT
 A CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
 PLAN P5 INDICATES AUXILIARY DRAIN
 TERMINATING AT THE SAME POINT AS THE
 PRIMARY DRAIN.THIS DOES NOT COMPLY
 WITH CODE REQUIREMENTS.PLEASE
 CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-18 Cont ID  
Sent By pkrauss Date 2003-02-18 Time 12:12 Rev Time 1.00
Received By pkrauss Date 2003-02-18 Time 10:39 Sent To  
Notes
2003-02-18 00:00:00PROVISO:
  
 MANUFACTURER SUBMITTAL - LANDA PRESSURE
 WASHER (GAS).PG 4 ITEM #32 INDICATES
 INDICATES TYPE B GAS VENT NOT SUITABLE
 SHOULD STACK TEMPERATURE EXCEED 470
 DEGREES F.ITEM #33 DRAFT HOOD SHALL
 BE INSTALLED IF THIS MACHINE IS GOING TO
 BE PERMANENTLY INSTALLED & VENTED TO THE
 OUTSIDE OF THE BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-07 Cont ID  
Sent By pkrauss Date 2002-10-07 Time 15:16 Rev Time 1.00
Received By pkrauss Date 2002-10-07 Time 14:37 Sent To  
Notes
2002-10-07 00:00:00DENIED:
  
 1.PROVIDE INFORMATION ON THE "SERVICE"
 AREA - WILL THIS BE TO REPAIR
 EQUIPMENT?PLEASE CLARIFY.
  
 2.PLAN SHEET M3 OUTSIDE AIR PROVISIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89 THE OUTSIDE AIR
 CALCULATION SHALL BE 20 CFM PER
 PERSON FOR OFFICE, CONFERENCE ROOMS,
 ETC. NOT 15 CFM AS INDICATED.
 PLEASE REVISE PLANS FOR ALL AREAS-
 OFFICE, CONFERENCE, RESTROOMS,
 LOCKER ROOM ETC.
  
 3.PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE POWER WASHER &
 FLUE.
  
 4.CLARIFY CONDENSATE & AUXILIARY DRAIN
 ARE BEING RUN TOGETHER & TERMINATING
 AT MOP SINK ? (PLAN SHEET P-1).
 AS PER 2001 FBC(M) 307.2.1, UNITS
 GREATER THAN 6 TON SHALL DISCHARGE
 STORM DRAIN OR DRYWELL. CONDENSATE
 DRAINS MANIFOLDED TOGETHER, SHALL BE
 SIZED TOGETHER BY AN APPROVED
 METHOD.PLEASE PROVIDE CALCULATIONS
 2001 FBC(M) 307.2.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-08-13 Cont ID  
Sent By kstevens Date 2004-08-13 Time 11:35 Rev Time 3.75
Received By kstevens Date 2004-08-13 Time 11:35 Sent To  
Notes
2004-08-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 FUEL GAS
  
 1) SHT U1 REVISION #8 NOT SHOWN, NO REV-
 ISION #5 SHOWN ON THIS REVISION IS SHOWN
 ON STAMPED SET OF PLANS. PLEASE CLARIFY.
 SECTION 104.2.1
 2) SHT U1 FOLLOWING ITEMS ARE REMOVED ON
 THE REVISION THAT ARE NOT CLOUDED OR A
 REVISION NUMBER ATTACHED: OIL/SAND INTER
 CEPTOR, FUEL TANK, AND 3" SS LINE. WHY
 WERE THESE ITEMS REMOVED, AND WHY WERE
 THESE CHANGES CALLED OUT AS REVISIONS.
 SECTION 104.2.1
 3) SHT P1 CALLS FOR REVISIONS 8 & 12,
 BUT THESE REVISIONS ARE NOT SHOWN. WHAT
 ARE THESE REVISIONS? SECTION 104.2.1
 4) SHT P3 REVISIONS 7, 8, & 12 WERE NOT
 FOUND ON THIS REVISION. WHAT ARE THESE
 REVISIONS? SECTION 104.2.1
 5) SHT P5 REVISIONS 8, & 12 WERE NOT
 FOUND ON THIS REVISION. WHAT ARE THESE
 REVISIONS? SECTION 104.2.1
  
 ***THE REVISION WAS SUBMITTED AFTER THE
 CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED
 AND THE PERMIT IS CLOSED.***
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 13:26 Rev Time 2.00
Received By kstevens Date 2003-12-06 Time 14:40 Sent To  
Notes
2003-12-15 00:00:00PASSED - PROVISO - FIELD INSPECTOR TO
 VERIFY SOLINOID TIMER SYSTEM FOR TRAP
 PRIMERS. - MORE INFORMATION REQUIRED FOR
 GAS PERMIT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-15 Cont ID  
Sent By kstevens Date 2003-04-15 Time 08:03 Rev Time 2.00
Received By kstevens Date 2003-04-15 Time 08:03 Sent To  
Notes
2003-04-15 00:00:00PASSED/PROVISO
  
 SEPARATE GAS PERMIT REQUIRED - THE
 FOLLOWING INFORMATION REQUIRED AT TIME
 OF GAS APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-22 Cont ID  
Sent By kstevens Date 2003-03-22 Time 14:14 Rev Time 3.00
Received By kstevens Date 2003-03-22 Time 14:13 Sent To  
Notes
2003-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT U1 DRYWELL SHALL BE MINIMUM OF
 12" FROM BLDG SECTION 1503.4.4. SURFACE
 WATER SHALL NOT DRAIN INTO DRYWELL. A
 RELIEF VENT WILL BE REQUIRED AS LINE
 ENTERS DRYWILL OR EXITS BLDG AT GROUND.
 2) SHT P-5, WHERE THE CONDENSATE DRAIN
 PIPES FROM MORE THAN ONE UNIT ARE MANI-
 FOLDED TOGETHER , THE PIPE OR TUBING
 SHALL BE SIZED IN ACCORDANCE WITH AN
 APPROVED METHOD. CONDENSATE WASTE AND
 DRAIN LINES SHALL NOT DECREASE IN SIZE
 FROM THE DRAIN PAN CONNECTION.
 3) PLEASE CLAIRFY USE FOR DEMUCKING
 PUMP. IS THERE PIPING CONNECTED TO THE
 PUMP?
 4) BACKFLOW PREVENTORS ARE REQUIRED FOR
 EACH BLDG. ONLY ONE IS SHOWN.
 5) THREE COMMENTS CONCERNING GAS REVIEW
 WERE NOT ADDRESSED. DO YOU WISH TO NOT
 REVIEW GAS AT THIS TIME AND ADDRESS
 THESE COMMENTS WHEN GAS PERMIT IS
 APPLIED FOR?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-17 Cont ID  
Sent By kstevens Date 2002-10-17 Time 12:26 Rev Time 6.00
Received By kstevens Date 2002-10-17 Time 12:26 Sent To  
Notes
2002-10-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT P1, CONDENSATE SHALL NOT DRAIN
 INTO SANITARY. IT SHALL BE PIPED SEPAR-
 ATELY OUTSIDE OF BLDG AND TIED INTO
 STORM, CATCH BASIN, OR DRYWELL. A RELEIF
 VENT IS REQUIRED WHERE CONDENSATE EXITS
 BLDG. CONDENSATE SHALL TERMINATE MINIMUM
 OF 12" FROM BLDG. SEC 1503.4.4 FBC
 2) PLEASE SUBMIT A CONDENSATE RISER DIA-
 GRAM. CALCULATE PIPE SIZE PER SECTION
 307.2.2 FBC-2001 MECH. SHOW PIPE SIZE ON
 RISER DIAGRAM.
 3) PLEASE SUBMIT A WATER RISER DIAGRAM.
 SHOW ALL PIPE SIZES AND WATER HAMMER
 ARRESTORS REQUIRED BY 604.9. LOCATE NEAR
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 CEILING AT TOP OF DROP.
 4) PLEASE SUBMIT A SANITARY RISER DIAG-
 RAM. WITH ALL HORIZONTAL PIPING AND SIZE
 PLEASE SUBMIT IN AN ISOMETRIC FORM.
 5) SHTS P1 & P4, RISERS AND FLOOR PLAN
 DO NOT MATCH. PLEASE CLAIRFY.
 6) SHTS P1 & P4 INDIRECT WASTE FROM ICE
 MACHINE SHALL NOT DRAIN TO FLOOR DRAIN.
 FLOOR SINKS ARE REQUIRED FOR ALL INDIR-
 ECT WASTE. SEC. 802.3
 7) SHT P4 RISER P3, HORIZONTAL DRY VENTS
 ARE NOT APPROVED, (AT FLOOR DRAIN). SECS
 905.3 & 905.4
 8) SHT P4 RISER P3, DOES NOT REFLECT
 FLOOR PLAN. FITTING SHOW DIRECTION OF
 FLOW TO THE RIGHT, (3" PIPE), AND 4"
 PIPE IS TO THE LEFT. ALSO FLOOR PLAN
 SHOWS RISERS P7 & P2 TYING INTO BLDG
 DRAIN (P3) BETWEEN URNAL AND W/C BUT NOT
 REFLECTED ON RISER. THIS CAN BE CORRECT-
 ED BY SUBMITTING COMPLETE SANITARY RISER
 DIAGRAM REQUESTED IN COMMENT #4 AS THE
 RISERS SHOWN ARE NOT ACTUAL ISOMETRIC
 RISER DIAGRAMS.
 9) SHT P3 SAND/0IL INTECEPTOR DETAIL,
 PLEASE CONTACT ROD COMPO, ENVIRONMENTAL
 COMPLIANCE MANAGER FOR SIZE OF INTECEPT-
 OR. (561) 837-4074 - ALSO MINIMUM WALL
 SIZE SHALL BE 3", AND BOTTOM SHALL BE 4"
 PLEASE SHOW ON DETAIL.
 10) PLEASE CLAIRFY USE FOR DEMUCKING
 PUMP. IS THERE PIPING CONNECTED TO THIS
 PUMP.
 11) SHT P3, HORIZONTAL DRY VENT FOR
 FLOOR SINK NOT APPROVED. SECS 905.3 &
 905.4
 12) BACKFLOWS ARE REQUIRED FOR EACH BLDG
 13) FOLLOWING GAS PERMIT APPLICATION
 REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SECS.401.8 THRU
 402.5 AND TABLES 402(2) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUELGAS
 CODE SEC. 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE SEC. 402.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE SEC
 304.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2003-03-25 Cont ID  
Sent By sgraham Date 2003-03-25 Time 16:38 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-02-11 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:53 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-02-11 00:00:00DENIED, MUST SUBMIT APPROVED SITE PLAN

Review Stop Z ZONING
Rev No 1 Status F Date 2002-10-16 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 13:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-16 00:00:001.A 10X25 LOADING IS REQUIRED ON
 SITE.
 2.OUTDOOR STORAGE AND DISPOSAL OF
 GOODS MUST BE SCREENED FROM VIEW
 3.PROVIDE A DETAIL OF PROPOSED FENCE
 /WALL AND GATES
 4.PROVIDE LANDSCAPE PLAN