Plan Review Details - Permit 02090835
Plan Review Stops For Permit 02090835
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-15 Cont ID  
Sent By hpiskura Date 2002-10-15 Time 13:10 Rev Time 0.00
Received By hpiskura Date 2002-10-15 Time 12:00 Sent To  
Notes
2002-10-15 00:00:00PROVISO:
 A SEPARATE PERMIT(S) WILL BE REQUIRED
 FOR THE STOREFRONT SYSTEM AND THE
 HURRICANE SHUTTERS.THE DESIGN
 PRESSURES OF THE OPENING LOCATION AND
 THE PRODUCT APPROVALS MUST ACCOMPANY
 THE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-30 Cont ID  
Sent By hpiskura Date 2002-09-30 Time 14:58 Rev Time 0.00
Received By hpiskura Date 2002-09-30 Time 15:05 Sent To  
Notes
2002-09-30 00:00:00THE DOOR SHOWN AS HAVING THE SWING
 CHANGED INTO THE WEST SIDE CORRIDOR
 MUST COMPLY WITH FBC 1012.1.4.PLEASE
 REVISE AS NECESSARY.
  
 SHOW THE ENVELOPE WIND PRESSURES, +/-,
 FOR THE STORE FRONT GLAZING BEING
 REPLACED.FBC 1606.1.7 #5.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS ARE NOT INCLUDED WITH THE
 PERMIT APPLICATION FOR THE GLAZED
 EXTERIOR PORTIONS, A SEPARATE PERMIT
 AND FEES WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-18 Cont ID  
Sent By dpalmer Date 2002-09-18 Time 13:09 Rev Time 0.25
Received By dpalmer Date 2002-09-18 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-17 Cont ID  
Sent By mcarsill Date 2002-09-17 Time 17:30 Rev Time 0.00
Received By mcarsill Date 2002-09-17 Time 17:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-10-02 Cont ID  
Sent By pkrauss Date 2002-10-02 Time 08:26 Rev Time 1.30
Received By pkrauss Date 2002-10-01 Time 16:28 Sent To  
Notes
2002-10-02 00:00:00MECHANICAL PERMIT 02090841

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-02 Cont ID  
Sent By kstevens Date 2002-11-02 Time 14:21 Rev Time 0.50
Received By kstevens Date 2002-11-02 Time 14:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By kstevens Date 2002-09-24 Time 12:45 Rev Time 0.00
Received By kstevens Date 2002-09-24 Time 12:45 Sent To  
Notes
2002-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1.1 HANDICAP TOILET ROOM,
 PLEASE SHOW CLEAR FLOOR SPACE AND 5'
 TURNING RADIUS.
 2) SHT A-1.1 BREAK ROOM, PLEASE SHOW
 CLEAR FLOOR SPACE FOR SINK. 11-4.24.5
 3) SHT A-3.0 DETAIL #4 PLEASE SHOW KNEE
 CLEARANCE 11-4.24.3, EXPOSED PIPES AND
 SURFACES 11-4.24.6
 4) SHT A-3.0 DETAIL #3(A) WATER CLOSET
 SHALL BE 18" OFF WALL TO CENTER OF FIX-
 TURE. W/C TOILET HEIGHT TO BE 17" TO 19"
 11-4.16.3. GRAB BAR HEIGHT TO BE 33" TO
 36" (FIGURE 29)PLEASE SHOW ON DETAIL.
 5) SHT P-1 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP IN CEILING AS SHOWN. PDI-WH 201
 AND MANUFACTURES INSTALLATION INSTRUCT-
 IONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377