| Plan Review Stops For Permit 02090813 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-03-05 |
Time |
13:23 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-18 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-09-18 |
Time |
08:35 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-18 00:00:00 | *****************FAILED*************** | | | | | | 1.PER FBC 2001 ALL WINDOWS & DOORS MUST | | | MEET 140 MPH WIND.ALL OPENINGS MUST | | | HAVE HURRICANE PROTECTION. NO PANELS | | | SHOWN ON APPLICATION.MUST ALSO HAVE | | | HISTORIC APPROVAL FOR PANELS. | | | | | | 2. ACCORDING TO THE HISTORIC LETTER | | | ATTACHED THERE ARE SEVERAL OPENINGS | | | THAT ARE GOING TO BE CHANGED. NEED | | | DRAWINGS TO SHOW WORK TO BE DONE & | | | MATERIALS USED TO MEET CURRENT CODES. | | | | | | NOTE:ALL SUBMITTALS MUST BE IN | | | DUPLICATE. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 659-8096 EXT. 8394 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-09-18 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|