Plan Review Details - Permit 02090764
Plan Review Stops For Permit 02090764
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-18 Cont ID  
Sent By hpiskura Date 2002-12-18 Time 08:56 Rev Time 0.00
Received By hpiskura Date 2002-12-17 Time 16:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-11 Cont ID  
Sent By btrobaug Date 2002-12-17 Time 13:16 Rev Time 0.00
Received By hpiskura Date 2002-11-26 Time 16:17 Sent To  
Notes
2002-11-27 00:00:00THE PREVIOUSLY REQUESTED INFORMATION FOR
 THE BUILT UP BEAMS HAS NOT BEEN
 PROVIDED.SEE FBC 104.2
  
 THE PREVIOUSLY REQUESTED CALCULATIONS
 FOR THE SHEARWALLS HAS NOT BEEN
 PROVIDED.THE STRUCTURAL PLANS DECLARE
 WIND DESIGN TO 110 MPH.WEST PALM BEACH
 IS IN 140 MPH WIND ZONE. NOTE IF FBC
 1606.2, ASCE 7-98 SIMPLIFIED,OR
 ANALYTICAL METHOD OF WIND DESIGN WAS
 USED FOR THIS BUILDING.
  
 HOW WERE THE PRESSURES OF -36 +48 FOR
 THE WINDOWS DETERMINED?HOW WILL THE
 STRUCTURAL ADEQUACY OF THE RELOCATED
 WINDOWS BE DEMONSTRATED?
  
 PRESSURES AND ZONES FOR THE ROOF ARE NOT
 PROVIDED. (COMPONENTS AND CLADDING)
  
 THE SHEET STAMPED FOR THE IMPACT FEES
 MUST BE INCLUDED WITH THE PERMIT SET.
  
 THE VENT AREA FOR THE ATTIC IS NOT
 ESTABLISHED, NOTES SUCH AS "MATCH
 EXISTING WITH ADDITIONAL VENTS IF
 NECESSARY" AND QUOTING THE CODE ARE NOT
 ACCEPTABLE SUBSTITUTES FOR SPECIFIC
 DESIGN INFORMATION.
 SEE FBC 104.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-10 Cont ID  
Sent By kmcvey Date 2002-11-26 Time 14:50 Rev Time 0.00
Received By hpiskura Date 2002-10-10 Time 12:12 Sent To  
Notes
2002-10-10 00:00:00PROVIDE THE INFORMATION REQUIRED BY FBC
 1606.1.7 AND FBC 104.2.1.1 ON THE PLANS.
  
 SHEET S1.WHAT IS THE DESIGN SOIL
 BEARING PRESSURE?
  
 PROVIDE TERMITE PROTECTION. SEE FBC
 1816.1.7.
  
 IN ACCORDANCE WITH FBC 104.2 PROVIDE THE
 FOLLOWING:
  
 SHOW A CONSTRUCTION DETAIL FOR THE
 TRELLIS.
  
 SPECIFY THE ROOF SHEATHING AND FASTENING
 METHOD.
  
 SHOW THE ATTIC ACCESS AND VENTILATION,
 SEE FBC 2309.6 AND 2309.7.
  
 PROVIDE AN STRUCTURAL ANALYSIS OF THE
 SHEAR WALLS FOR THE NEW CONSTRUCTION.
  
 SHOW THE METHOD OF HURRICANE MISSILE
 IMPACT RESISTANCE FOR THE GLAZING IN
 THE EXTERIOR WALLS. SEE FBC 1606.1.4.
  
 PROVIDE TEST AND/OR NOTICE OF ACCEPTANCE
 REPORTS FROM A RECOGNIZED AGENCY FOR
 THE EXTERIOR DOORS, WINDOWS AND ROOF
 COVERING.IF THE INFORMATION IS NOT
 INCLUDED WITH THIS PERMIT APPLICATION A
 SEPARATE PERMIT AND FEES WILL BE
 REQUIRED FOR THAT WORK.
  
 WHAT IS THE HEIGHT ABOVE GRADE OF THE
 PROPOSED PATIO DECK?WILL THERE BE
 STEPS?
  
 WHAT WILL THE SUB FLOOR BE SHEATHED
 WITH?SEE FBC 2307.6.
  
 SHOW A CONSTRUCTION DETAIL FOR THE STEM
 WALL, INCLUDING BEAM OR CAP.
  
 SPECIFY THE NAILING FOR THE BUILT UP
 BEAMS, SUCH AS THE 4 2X10'S AT THE
 SECOND FLOOR.
  
 SHOW THE CONNECTION DETAILS FOR THE 6X6
 WOOD COLUMNS.
  
 WHAT SUPPORTS THE LOWER ROOF ATOP THE
 6X6 COLUMNS?
  
 SHOW A CONSTRUCTION DETAIL FOR THE GABLE
 END AND UNDERSIDE OF THE LOWER ROOF.
  
 SECTION A9 SHOWS WIRE LATH, OTHER
 ELEVATIONS INDICATE "HORIZONTAL LAP
 SIDING" PLEASE CLARIFY THE DESIGN
 INTENT.
  
 SHOW A SPECIFIC METHOD FOR ATTACHING
 THE WINDOWS TO THE BUILDING STRUCTURE.
  
 SHOW THE CONNECTION METHOD FOR THE 4X4
 STEEL COLUMN, TOP AND BOTTOM.
  
 RE: THE WEST ELEVATION.FBC TABLE 600
 ALLOWS 20% WALL AREA OPENINGS, PER
 FLOOR FOR EXTERIOR WALLS OF TYPE VI
 CONSTRUCTION >3' - >10' FROM AN COMMON
 PROPERTY LINE.THE WINDOW OPENINGS IN
 THE SECOND STORY ADDITION WILL EXCEED
 THE ALLOWABLE PERCENTAGE.PLEASE
 REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-06 Cont ID  
Sent By btrobaug Date 2003-03-06 Time 08:51 Rev Time 0.50
Received By btrobaug Date 2003-03-06 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 10:55 Rev Time 0.00
Received By kmcvey Date 2002-11-26 Time 14:49 Sent To B
Notes
2002-11-25 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION MAKE NECESSARY REVISIONS
 AND SUBMIT FOR REVIEW BEFORE CALLING
 ANY ELECTRICAL INSPECTIONS.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS
 INCORRECTY SIZED FOR THE SERVICE
 CONDUCTORS PER 250-66.ALSO THE SYSTEM
 IS NOT IN COMPLIANCE WITH 250-50 NEC.
  
 3} SHEET "A-1" SHOWS EXISTING SERVICE TO
 REMAIN,AND ALSO SHOWS "NEW SERVICE ON
 REAR WALL",PLEASE CLARIFY.
  
 4} THE PLAN INDICATES THE SERVICE FROM
 FPL TO THE METER BEING 400 AMP/3 PHASE,
 PLEASE VERIFY SIZE AND RATING OF THE
 SERVICE.
  
 5} THE RISER DIAGRAM MUST SHOW
 COMPLIANCE WITH 225-32 &
 250-32(B)(1).ALSO NOTE 230-70(A) CWPB
 AMMENDMENTS FOR DISCONNECT
 LOCATION,LOCATE SAME ON PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-25 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 17:52 Rev Time 1.00
Received By btrobaug Date 2002-09-24 Time 16:42 Sent To P
Notes
2002-09-25 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT AN ELECTRICAL PERMIT
 IS REQUIRED FOR THE SCOPE OF THIS
 PROJECT.AT THE TIME OF APPLICATION FOR
 THAT PERMIT IT SHALL BE NECESSARY FOR
 THE ELECTRICAL CONTRACTOR TO PROVIDE A
 RISER DIAGRAM FOR THE RELOCATED SERVICE,
 INCLUDING FEEDERS TO THE PANEL IN THE
 LAUNDRY ROOM.
 ALSO INDICATE THE LOCATION OF THE
 RELOCATED SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-17 Cont ID  
Sent By btrobaug Date 2002-12-17 Time 13:16 Rev Time 0.00
Received By btrobaug Date 2002-12-17 Time 13:16 Sent To B
Notes
2002-12-17 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-18 Cont ID  
Sent By btrobaug Date 2002-11-18 Time 17:52 Rev Time 0.00
Received By btrobaug Date 2002-11-18 Time 17:52 Sent To E
Notes
2002-11-18 00:00:00TO WRT./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-09-28 Cont ID  
Sent By kstevens Date 2002-09-27 Time 18:21 Rev Time 0.33
Received By hmoser Date 2002-09-28 Time 07:01 Sent To  
Notes
2002-09-28 00:00:00NO PLANS,ENERGY CALCS,OR MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER 9/28/02

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-27 Cont ID  
Sent By btrobaug Date 2002-09-25 Time 08:15 Rev Time 0.00
Received By kstevens Date 2002-09-27 Time 18:04 Sent To M
Notes
2002-09-27 00:00:00PASSED/PROVISO
  
 SEPARATE GAS PERMIT REQD. SEE ATTACHED
 PERMIT APPLICATION REQUIREMENTS SHEET
 FOR INFORMATION REQUIRED FOR PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-24 Cont ID  
Sent By sgraham Date 2002-09-24 Time 11:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***