Plan Review Details - Permit 02090696
Plan Review Stops For Permit 02090696
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-06-05 Cont ID  
Sent By hpiskura Date 2003-06-05 Time 11:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-06-05 00:00:00REVISIONS DATED 4/16/03 ADT1 & SD5

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-02 Cont ID  
Sent By sthyng Date 2003-05-02 Time 12:22 Rev Time 1.00
Received By sthyng Date 2003-05-02 Time 12:22 Sent To  
Notes
2003-05-02 00:00:00PASSED PER BILL STAPLES
  
 SEE CONSTRUCTION BOARD OF ADJUSTMENT
 AND APPEALS MINUTES, APRIL 17, 2003 CASE
 NUMBER 1231, AND JANUARY 8, 2003 CASE
 NUMBER 1225.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-04-15 Cont ID  
Sent By hpiskura Date 2003-04-15 Time 12:03 Rev Time 0.00
Received By hpiskura Date 2003-04-15 Time 10:47 Sent To  
Notes
2003-04-15 00:00:00THIRD PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 THE FIRE PROTECTION PLANS MUST ACCOMPANY
 THE PERMIT PLANS. SEE FBC 104.3.1.1 #5.
  
 THE CONSTUCTION BOARD OF ADJUSTMENT AND
 APPEALS CASE #1225 HEARD 1/8/03 GRANTED
 A VARIANCE TO THE 50% LONG SIDE OPEN
 BALCONY REQUIREMENT OF FBC 1014.1.1.
  
 FIRE SPRINKLERS INSTALLED AS A CODE
 REQUIREMENT MUST BE A NFPA 13 SYSTEM.
 SEE FBC 903.2.
  
 THE EXITS DO NOT MEET THE 1/2 DIAGONAL
 DISTANCE SEPARATION REQUIREMENTS OF FBC
 1006.2.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-14 Cont ID  
Sent By hpiskura Date 2003-02-14 Time 09:57 Rev Time 0.00
Received By hpiskura Date 2003-02-14 Time 09:57 Sent To  
Notes
2003-02-14 00:00:00COMMENTS ARE ATTACHED TO THE REVIEW
 SHEET AND ARE CONTAINED UNDER REVIEW
 #020695

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-10-02 Cont ID  
Sent By hpiskura Date 2002-10-02 Time 15:14 Rev Time 0.00
Received By hpiskura Date 2002-10-01 Time 14:18 Sent To  
Notes
2002-10-02 00:00:00PAID PLAN REVIEW NOT A PERMIT
 APPLICATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 ON PROJECTS OF THIS SCOPE THE BUILDING
 OFFICIAL WILL REQUIRE A RESIDENT
 INSPECTOR.CONTACT DON NEELY,
 561-659-8096 X 8333, FOR MORE
 INFORMATION.
  
 AT TIME OF PERMIT APPLICATION, IF THE
 TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS, FOR THE WINDOWS, DOORS AND
 ROOF COVERING ARE NOT INCLUDED, SEPARATE
 PERMITS AND FEES WILL BE REQUIRED.
  
 SHEET AS-1 DECLARES 13,864 SQUARE FEET
 FOR A TYPE III BUILDING AND SHEET
 A-T3.1 16,016.PLEASE CLARIFY.SEE
 FBC 202, "AREA, BUILDING"
  
 THE DETAIL 17/A-DT2 DOES NOT AGREE WITH
 FBC FIGURE 709.5.1C FOR THE ONE HOUR
 FIRE RATED COLUMN.
  
 THE NOTES ON SHEET A-DT1 DECLARE THE USE
 OF HURRICANE SHUTTERS.SEE THE
 BUILDING OFFICIAL'S POLICY STATEMENT
 ATTACHED.HURRICANE MISSILE IMPACT
 RESISTANT GLAZING IS REQUIRED
 THROUGHOUT.
  
 THE DROPPED SOFFIT DETAIL 14/ADT-2 NEEDS
 SPECIFIC FRAMING AND FASTENER DETAILS.
 SEE FBC 104.2.
  
 NOTE #3 ON SHEET SD-4 DECLARES DESIGN TO
 THE 1997 SBC AND 110 MPH.PLEASE
 REVISE AND INSURE COMPLIANCE WITH FBC
 1606 FOR 140 MPH WIND ZONE.
  
 SHOW THE FIRE PROTECTION DESIGN
 INFORMATION.SEE FBC 104.2.
  
 THE EXIT STAIRS ARE REQUIRED TO BE
 ENCLOSED IN FIRE RATED CONSTRUCTION IN
 ACCORDANCE WITH FBC 1006.1 OR COMPLY
 WITH FBC 1006.2 FOR EXTERIOR STAIRS.
 AS DEPICTED ON THESE PLANS THEY COMPLY
 WITH NEITHER.
  
 THE THIRD FLOOR REQUIRES TWO INDEPENDENT
 MEANS OF EGRESS.SEE FBC 1004.2.1.
  
 SHEET SD-5 HAS INCORRECTLY LABELED
 ROOF CORNER ZONES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-11 Cont ID  
Sent By dpalmer Date 2003-04-11 Time 03:57 Rev Time 0.50
Received By dpalmer Date 2003-04-11 Time 03:38 Sent To  
Notes
2003-04-11 00:00:00ELECTRICAL PLANS STAMPED, READY TO
 ISSUE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 06:03 Rev Time 0.25
Received By dpalmer Date 2003-02-27 Time 06:03 Sent To  
Notes
2003-02-27 00:00:00************** UNSAT ****************
  
 TYPE II
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
 PLEASE SEE NOTES UNDER PERMIT # 02090695
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-10-08 Cont ID  
Sent By dpalmer Date 2002-10-08 Time 05:26 Rev Time 1.00
Received By dpalmer Date 2002-10-08 Time 05:26 Sent To  
Notes
2002-10-08 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, AS PER NOTE #7 ON
 E-U1. THE LOCK OFF DEVICE MUST BE
 A PART OF THE BREAKER. PLEASE NOTE THE
 TYPE OF LOCK OFF DEVICE CHOSEN NEEDS TO
 BE REVIEWED BY THE CITY OF WEST PALM
 BEACH BEFORE INSTALLATION. PLEASE NOTE,
 MOST OF THE "SNAP ON" DEVICES ARE NOT
 PERMITTED TO BE USED AND A MEANS OF DISC
 IS REQ`D. PLEASE NOTE ON PLANS.
  
 2)NOTE: PLEASE SHOW REQ`MENTS FOR FAIR
 HOUSING ACT. FHAR 24 CFR 100.205.
  
 3)NOTE: PLEASE NOTE CLEARENCE FOR CLOSET
 LIGHT INSTALLATION PER 410-8.
  
 4)NOTE: PLEASE CLARIFY LOCATION OF
 SERVICE RECEPT FOR A/C COND UNIT. 210-63
  
 5)NOTE: PLEASE SEE 230-72 FOR GROUPING
 OF MAINS . PLEASE NOTE A SHUNT TRIP
 MAY NOT BE USED FOR GROUPING OF MAINS.
 PLEASE SEE 230-76,230-79.
 PLEASE CLARIFY HOW THIS MEETS 230-2
 AND THE ABOVE.
  
 6)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDIG BETWEEN METER/MAIN AND
 HOUSE PANEL? SIZE PER 250-122
  
 7)NOTE: PLEASE SHOW INDICATION OF MAINS
 FOR APT UNITS ON RISER DIAGRAM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By sjohnson Date 2002-10-16 Time 14:12 Rev Time 0.50
Received By mamini Date 2003-02-10 Time 08:53 Sent To  
Notes
2003-02-10 00:00:00PASSED:
 1. SEE PERMIT # 02121237 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI
2002-10-16 00:00:00PER LUIS MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-04-30 Cont ID  
Sent By nmccray Date 2003-04-30 Time 15:03 Rev Time 0.00
Received By nmccray Date 2003-04-30 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-03-06 Cont ID  
Sent By mcarsill Date 2003-03-06 Time 12:47 Rev Time 0.00
Received By mcarsill Date 2003-03-06 Time 12:47 Sent To  
Notes
2003-03-06 00:00:001) SOME PLAN REVIEW COMMENTS HAVE
 NOT BEEN PROPERLY ADDRESSED.
  
 2) EXIT SIGNS REQUIRED AT FIRST FLOOR
 LEVEL.
  
 3) IT APPEARS THAT ADDITIONAL FIRE
 HYDRANTS ARE REQUIRED ON THE SITE PLAN.
 BETTER PLACEMENT WITH ADDITIONAL FIRE
 HYDRANTS WOULD APPEAR TO BE PROPER.
  
 4) PLEASE INDICATE LOCATIONS OF FDC'S
 IN RELATION TO THE FIRE HYDRANTS. FDC'S
 SHALL NOT EXCEED 150 FEET TO A FIRE
 HYDRANT.
  
 5) NFPA 13R SYSTEMS SHALL NOT BE USED
 WHEN CODE REQUIREMENTS HAVE BEEN
 ALTERED. NFPA 13 SYSTEMS MUST BE USED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 16:44 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 16:44 Sent To  
Notes
2002-10-04 00:00:001) PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE BUILDING. PLEASE INDICATE
 EXIT SEPARATIONS, TRAVEL DISTANCES,
 ETC.
  
 2) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 5) WHAT PROVISIONS WILL BE MADE FOR
 FIRE AND PARAMEDICAL ACCESS THRU THE
 SECURITY GATES WHEN NORMAL POWER IS
 PRESENT. THIS OFFICE USUALLY REQUIRES
 A KNOX-BOX KEY SWITCH. WHAT HAPPENS
 WHEN LOSS OF POWER OCCURS.
  
 6) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 16:49 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 16:49 Sent To P
Notes
2003-05-28 00:00:00KSTEVENS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-07 Cont ID  
Sent By sthyng Date 2003-05-07 Time 15:25 Rev Time 0.00
Received By sthyng Date 2003-05-07 Time 15:25 Sent To P
Notes
2003-05-07 00:00:00TO PLUMB IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-29 Cont ID  
Sent By shernand Date 2003-04-29 Time 15:17 Rev Time 0.00
Received By shernand Date 2003-04-29 Time 15:17 Sent To P
Notes
2003-04-29 00:00:00KSTEVENS DESK, PLUMBING REVISION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-03 Cont ID  
Sent By sgraham Date 2003-04-17 Time 16:26 Rev Time 0.00
Received By sthyng Date 2003-04-03 Time 08:58 Sent To  
Notes
2003-04-03 00:00:00COMM BOARD #42
 PLANS NEXT TO RACK
 COVER SHEET SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 08:43 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-01 Cont ID  
Sent By pkrauss Date 2003-05-01 Time 11:23 Rev Time 0.00
Received By pkrauss Date 2003-05-01 Time 11:22 Sent To  
Notes
2003-05-01 00:00:00PLANS APPROVED 4-4-24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-02-19 Cont ID  
Sent By pkrauss Date 2003-02-19 Time 15:45 Rev Time 0.45
Received By pkrauss Date 2003-02-19 Time 15:44 Sent To  
Notes
2003-02-19 00:00:00DENIED:
 ITEMS NOT ADDRESSED ON REVIEW BY HAROLD
 MOSER DATAED 10/08/02.
 1.VERIFY OUTSIDE AIR REQUIREMENTS.
 INDICATE CALCULATIONS FOR NATURAL
 (2001 FBC(M) 402.2) OR MECHANICAL (2001
 FBC(M) TABLE 403.3).
  
 2.DUCTS EXTENDING MORE THAN 1 FLOOR
 ARE REQUIRED TO BE ENCLOSED BY A SHAFT
 ENCLOSURE AS PER 2001 FBC(M) 607.4.
 PROVIDE DETAIL OF UL SHAFT ASSEMBLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-10-08 Cont ID  
Sent By hmoser Date 2002-10-08 Time 17:57 Rev Time 1.00
Received By hmoser Date 2002-10-08 Time 17:57 Sent To  
Notes
2002-10-08 00:00:00PLAN/DENIED
 1) VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR.SECTION 402 NATURAL OR
 MECHANICAL SECTION 403.IF SECTION 402
 IS USED YOU NEED CALCULATIONS.
 2) NEED MANUFACTURERS INSTALLATION
 INSERUCTIONS ON CLOTHES DRYER
 3) MISSING DUCT SIZE ON UNIOT C2-P 1ST
 FLOOR
 4) REFER TO SECTION 306.1.1 CLEARANCE
 AROUND AIRHANDLER
 5) REFER TO SECTION 304.9 AREA SERVED.
 ALL IN FLORIDA BUILDING CODE
 MECHANICAL 2001
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 6 Status P Date 2003-05-28 Cont ID  
Sent By kstevens Date 2003-05-28 Time 18:22 Rev Time 0.33
Received By kstevens Date 2003-05-28 Time 18:22 Sent To  
Notes
2003-05-28 00:00:00REVISION OK, SANT./WATER REROUTED

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-28 Time 16:49 Rev Time 1.50
Received By kstevens Date 2003-05-19 Time 09:28 Sent To  
Notes
2003-05-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FULL OPEN VALVE REQUIRED AT ENTRANCE
 OF STRUCTURE. SEC 606.1(1)
 2) FULL OPEN VALVES REQUIRED AT THE BASE
 OF EACH WATER RISER. 606.1(2)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 4 Status N Date 2003-05-05 Cont ID  
Sent By sthyng Date 2003-05-07 Time 15:25 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2003-05-02 00:00:00NEW PLAN REVIEW REQ, PES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-12 Cont ID  
Sent By shernand Date 2003-04-29 Time 15:17 Rev Time 0.50
Received By kstevens Date 2003-04-12 Time 13:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-04 Cont ID  
Sent By kstevens Date 2003-03-04 Time 17:38 Rev Time 0.33
Received By kstevens Date 2003-03-04 Time 17:20 Sent To  
Notes
2003-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) WATER HEATER PAN IS NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. P/T FROM 2ND &
 3RD FLOOR WATER HEATERS CAN RUN IN THE
 CEILING OF THE FIRST FLOOR AND STUB OUT
 6" ABOVE GRADE. FIRST FLOOR P/T CAN
 DRAIN TO FLOOR.
 2) C/O REQUIRED IN BREEZEWAY TO THE
 RIGHT OF BLDG DRAIN AS IT ENTERS THE
 BLDG. 120' BETWEEN C/O'S
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-10-05 Cont ID  
Sent By kstevens Date 2002-10-05 Time 12:47 Rev Time 0.00
Received By kstevens Date 2002-10-05 Time 12:47 Sent To  
Notes
2002-10-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHTS P-U1, P-U2, P-U3, P-U4, P-U5, &
 P-U6, WATER RISER DIAGRAMS, WATER HAMMER
 ARRESTORS AT WASH MACHINES SHALL BE LO-
 CATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT THE TOP OF DROPS AS SHOWN.
 PDI-WH 201 AND MANUFACTURE INSTALLATION
 INSTRUCTIONS. 604.9
 2) SHT P-T3.1 CLEAN OUTS SHALL BE RE-
 QUIRED IN EACH BREEZE WAY. 100' MAX BE-
 TWEEN C/O'S SEC 708.3.1
 3) SHT P-T3.3 SANITARY RISER DIAGRAM,
 SEE PREVIOUS COMMENT. (#2)
 4) SHT PD-1 WATER HEATER DRAIN & P/T RE-
 LIEF RISERS. T/P LINE SHALL NOT BE TRAP-
 PED SEC 504.7.1
 5) SHT PD-1 PLUMBING GENERAL NOTES #6,
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 LINES. PLEASE DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2003-04-17 Cont ID  
Sent By sgraham Date 2003-04-17 Time 16:26 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-02-11 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:43 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-02-11 00:00:00DENIED, NEED TO AMEND PLANS TO MATCH
 APPROVED SITE PLAN

Review Stop Z ZONING
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 08:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-09-24 00:00:00DENIED, NEED CITY COMMISSION APPROVAL