| Plan Review Stops For Permit 02090639 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-12-02 |
Time |
08:12 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2003-12-02 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-09-30 |
Time |
10:15 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-09-30 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-30 |
Time |
08:58 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-09-29 |
Time |
09:58 |
Sent To |
B |
|
| Notes |
| 2003-09-29 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE SUBMIT TWO SEALED SETS OF PLANS | | | FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-07-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-09-26 |
Time |
07:27 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-07-16 |
Time |
16:24 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-14 |
Time |
09:24 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-12-09 |
Time |
07:42 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-09-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-23 |
Time |
07:06 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-23 |
Time |
06:53 |
Sent To |
Z |
|
| Notes |
| 2002-10-29 00:00:00 | 10/29/02 SPOKE WITH THE "DESIGNER" ON | | | THE PHONE WHO INFORMED ME HE IS NOT | | | REGISTERED,THEREFORE DOES NOT REQUIRED | | | A SEAL WITH THE SIGNATURE./WRT | | 2002-09-23 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E | | | | | | 2} THE PLANS ARE REQUIRED TO BE SEALED | | | PER 61G1-16.001 FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-24 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-24 |
Time |
12:40 |
Sent To |
B |
|
| Notes |
| 2003-11-24 00:00:00 | TO RM DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-30 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-30 |
Time |
08:58 |
Sent To |
E |
|
| Notes |
| 2003-09-30 00:00:00 | TO BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-16 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-16 |
Time |
14:41 |
Sent To |
B |
|
| Notes |
| 2003-09-16 00:00:00 | TO RM DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-07-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-14 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-14 |
Time |
09:24 |
Sent To |
E |
|
| Notes |
| 2003-07-14 00:00:00 | BT DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-12-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-10 |
Time |
12:48 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2002-12-10 |
Time |
12:33 |
Sent To |
R |
|
| Notes |
| 2002-12-10 00:00:00 | PROVISO: | | | | | | MECHANICAL PERMIT REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-09 |
Time |
09:11 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-09-27 |
Time |
13:29 |
Sent To |
P |
|
| Notes |
| 2002-09-27 00:00:00 | DENIED: | | | | | | MECHANICAL PERMIT REQUIRED. | | | | | | PLEASE PROVIDE DUCT SIZE AND CFM | | | DISTRIBUTION. | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | AS PER 2001 FBC(M) 1108.1, REFRIGERANT | | | LINES SHALL BE TESTED.TEST SHALL BE | | | PERFORMED WITH AN INERT DRIED GAS | | | INCLUDING, BUT NOT LIMITED TO, NITROGEN | | | & CARBON DIOXIDE 2001 FBC(M) 1108.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-09-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-10 |
Time |
12:50 |
Rev Time |
0.75 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-30 00:00:00 | FBC 2001,NO PLBG ISOMETRIC, PES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
7 |
Status |
P |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-12-01 |
Time |
15:59 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
2003-12-01 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2003-12-01 00:00:00 | RESTAMP/ LOST PLAN 12-1-03 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
6 |
Status |
P |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-10-01 |
Time |
14:51 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
2003-10-01 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2003-10-01 00:00:00 | STAMP AND FILE REVISION 10-1-03 RM |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-09-30 |
Time |
12:40 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
2003-09-30 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2003-09-30 00:00:00 | REVISION WAS DENIED BY S. PILAND WITH | | | HISTORIC PRESERVATION. YOU WILL BE | | | REQUIRED TO TAKE THE PLANS TO HISTORIC | | | PRESERVATION AND HAVE THEIR APPROVAL | | | BEFORE THE REVISIONS CAN BE APPROVED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-09-26 |
Time |
07:01 |
Rev Time |
1.50 |
| Received By |
rmcdouga |
Date |
2003-09-26 |
Time |
07:01 |
Sent To |
E |
|
| Notes |
| 2003-09-26 00:00:00 | REVISION IS DENIED | | | | | | 1) TWO SETS OF IDENTICAL PLANS ARE | | | REQUIRED. THE TWO SETS THAT WERE | | | SUBMITTED HAVE SOME DIFFERENCES. PLEASE | | | SUBMIT TWO IDENTICAL SETS OF PLANS. | | | | | | 2) THE CHANGE TO THE EXTERIOR COLUMNS | | | WILL HAVE TO BE APPROVED BY THE HISTORIC | | | PRESERVATION DEPARTMENT. THERE DOES NOT | | | APPEAR TO BE ANY OTHER CHANGES TO THE | | | EXTERIOR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL : | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-07-17 |
Time |
11:27 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
2003-07-17 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2003-07-17 00:00:00 | REVISION DENIED BY BUILDING | | | | | | 1) REVISED PLANS ARE REQUIRED TO BE | | | SIGNED, SEALED AND DATED BY THE DESIGNER | | | OF RECORD. THE ENGINEER'S TITLE BLOCK IS | | | REQUIRED ON EACH SHEET OF THE PLAN. | | | | | | 2) SUBMIT REVISED SHEETS A-3, S-1, AND | | | E/M-1. CHANGES SHOULD BE CLOUDED AND | | | NUMBERED. NUMBER OF REVISION AND DATE OF | | | REVISION SHOULD BE LISTED IN UPPER RIGHT | | | HAND SIDE OF THE SHEET. | | | | | | 3) ROOMS NEED TO BE LABELED ON PLAN. | | | | | | 4) PROVIDE THE WINDOW TYPE AND SIZE OF | | | ALL WINDOWS THAT ARE CHANGED FROM THE | | | PERMITED PLANS. EGRESS WINDOWS THAT | | | COMPLY WITH FBC 1005.4 ARE REQUIRED AT | | | ROOMS USED FOR SLEEPING. | | | | | | 5) ANY CHANGES TO THE EXTERIOR (WINDOW | | | LOCATION, ETC.) WILL HAVE TO BE REVIEWED | | | AND APPROVED BY HISTORIC PRESERVATION | | | DEPT. | | | | | | 6) DRAWINGS AND SPECIFICATIONS SHOULD BE | | | IDENTICAL TO THE PERMITTED SET EXCEPT | | | FOR THE ITEMS THAT ARE BEING REVISED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-12-12 |
Time |
15:13 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | BUILDING PROVISO | | | | | | 1)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - FRENCH DOORS WITHOUT SIDELITES (IMPACT | | | RESISTANT) | | | - SINGLE HUNG WINDOWS (IMPACT RESISTANT) | | | | | | 2) SUBMIT SIGNED AND SEALED ENGINEERED | | | DRAWINGS FOR THE BALCONY GUARDRAILS. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2002-10-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-10 |
Time |
12:50 |
Rev Time |
6.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-10 00:00:00 | BUILDING DENIED | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) THE STRUCTURE IS LOCATED IN AN "A5" | | | FLOOD ZONE THE MINIMUM ELEVATION IS 7.5 | | | FEET. AN ELEVATION CERTIFICATE WILL BE | | | REQUIRED FOR ADDITION. | | | THE CITY CODE OF WPB REQUIRES ALL NEW | | | CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT | | | OF ANY EXISTING RESIDENTIAL STRUCTURE TO | | | HAVE THE LOWEST FLOOR ELEVATED TO SIX | | | INCHES ABOVE THE BASE FLOOD ELEVATION. | | | PLEASE INDICATE THE FLOOR ELEVATIONS ON | | | THE PLANS OR SURVEY. | | | | | | 4)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - EXTERIOR WINDOWS | | | - EXTERIOR DOORS | | | | | | 5) PROVIDE (2) PRODUCT APPROVALS, KEY | | | PLANS AND INSTALLATION SCHEDULES | | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | | TO BE USED FOR STORM PANELS. | | | | | | 6) SLEEPING ROOMS ARE REQUIRED TO HAVE | | | AT LEAST ONE EXTERIOR EMERGENCY ESCAPE | | | AND RESCUE OPENING, PER FBC 1005.4. THE | | | NET CLEAR OPENING AREA AND DIMENSIONS | | | MUST COMPLY WITH FBC SEC.1005.4.4. THE | | | SECOND FLOOR BEDROOMS DO NOT COMPLY. | | | | | | 7) INDICATE ACCESS TO ATTIC SPACE AS | | | REQUIRED BY FBC SEC. 2309.6. | | | | | | 8) PLEASE CLARIFY THE WINDOWS THAT HAVE | | | BEEN DRAWN IN ON THE PLANS. CHANGES MUST | | | BE SIGNED AND DATED BY THE DESIGNER OF | | | RECORD. INDICATE WINDOW SIZES AND TYPES. | | | | | | 9) THE ADDITION OF THESE WINDOWS EXCEED | | | THE PERCENT OF WALL AREA ALLOWED AS | | | OPENINGS BY TABLE 600 FOR THE FIRST AND | | | SECOND FLOOR OF THE SOUTH ELEVATION. | | | | | | 10) THE NORTH ELEVATION ON SHEET A-3 | | | SHOWS A WINDOW WITH A "C" DESIGNATION | | | AND THERE IS NO "C" LISTED IN THE WINDOW | | | SCHEDULE. PLEASE CLARIFY. | | | | | | 11) SHEET A-5 LISTS SLOPE ON BALCONY AS | | | 1/4" PER FOOT AND TOP CUT OF JOISTS IS | | | INDICATED TO PROVIDE 1/8" PER FOOT SLOPE | | | PLEASE CLARIFY. NOTE: 1/4":12 SLOPE IS | | | REQUIRED FOR MODIFIED ROOFING. | | | | | | 12) IF STORM PANELS ARE BEING USED, | | | PLEASE NOTE ON THE PLANS THAT ADEQUATE | | | SUBSTRATE WILL BE PROVIDED AT GLAZED | | | OPENINGS FOR THE ATTACHMENT OF STORM | | | PANELS. | | | | | | 13) FBC SEC. 1909.3 REQUIRES WELDED WIRE | | | MESH TO BE SUPPORTED AT SPACINGS NOT TO | | | EXCEED 3 FEET. PLEASE INDICATE THIS ON | | | PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-10-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-29 |
Time |
15:06 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2002-09-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-23 |
Time |
07:06 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-24 00:00:00 | DENIED, SHEET A-1 MUST BE REVISED, BLDG | | | IS A SINGLE FAMILY HOUSE, CAN NOT BE | | | USED AS ACCESSORY STRUCTUAL IN THE | | | FUTURE. | | | POOL NEED A CLASSB TO BE LOCATED IN | | | THE FRONT YARD |
|
|