Plan Review Details - Permit 02090639
Plan Review Stops For Permit 02090639
Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-12-02 Cont ID  
Sent By btrobaug Date 2003-12-02 Time 08:12 Rev Time 0.33
Received By btrobaug Date 2003-12-02 Time 08:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-09-30 Cont ID  
Sent By btrobaug Date 2003-09-30 Time 10:15 Rev Time 0.50
Received By btrobaug Date 2003-09-30 Time 09:56 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:58 Rev Time 0.50
Received By btrobaug Date 2003-09-29 Time 09:58 Sent To B
Notes
2003-09-29 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SUBMIT TWO SEALED SETS OF PLANS
 FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-16 Cont ID  
Sent By rmcdouga Date 2003-09-26 Time 07:27 Rev Time 0.50
Received By btrobaug Date 2003-07-16 Time 16:24 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-09 Cont ID  
Sent By shernand Date 2003-07-14 Time 09:24 Rev Time 0.50
Received By btrobaug Date 2002-12-09 Time 07:42 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-23 Cont ID  
Sent By btrobaug Date 2002-09-23 Time 07:06 Rev Time 0.50
Received By btrobaug Date 2002-09-23 Time 06:53 Sent To Z
Notes
2002-10-29 00:00:0010/29/02 SPOKE WITH THE "DESIGNER" ON
 THE PHONE WHO INFORMED ME HE IS NOT
 REGISTERED,THEREFORE DOES NOT REQUIRED
 A SEAL WITH THE SIGNATURE./WRT
2002-09-23 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 2} THE PLANS ARE REQUIRED TO BE SEALED
 PER 61G1-16.001 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 12:40 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 12:40 Sent To B
Notes
2003-11-24 00:00:00TO RM DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:58 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 08:58 Sent To E
Notes
2003-09-30 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 14:41 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 14:41 Sent To B
Notes
2003-09-16 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 09:24 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 09:24 Sent To E
Notes
2003-07-14 00:00:00BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-10 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 12:48 Rev Time 0.25
Received By pkrauss Date 2002-12-10 Time 12:33 Sent To R
Notes
2002-12-10 00:00:00PROVISO:
  
 MECHANICAL PERMIT REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-27 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 09:11 Rev Time 0.40
Received By pkrauss Date 2002-09-27 Time 13:29 Sent To P
Notes
2002-09-27 00:00:00DENIED:
  
 MECHANICAL PERMIT REQUIRED.
  
 PLEASE PROVIDE DUCT SIZE AND CFM
 DISTRIBUTION.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 AS PER 2001 FBC(M) 1108.1, REFRIGERANT
 LINES SHALL BE TESTED.TEST SHALL BE
 PERFORMED WITH AN INERT DRIED GAS
 INCLUDING, BUT NOT LIMITED TO, NITROGEN
 & CARBON DIOXIDE 2001 FBC(M) 1108.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 12:50 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2002-09-30 00:00:00FBC 2001,NO PLBG ISOMETRIC, PES.

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2003-12-01 Cont ID  
Sent By rmcdouga Date 2003-12-01 Time 15:59 Rev Time 1.00
Received By rmcdouga Date 2003-12-01 Time 15:59 Sent To  
Notes
2003-12-01 00:00:00RESTAMP/ LOST PLAN 12-1-03

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2003-10-01 Cont ID  
Sent By rmcdouga Date 2003-10-01 Time 14:51 Rev Time 1.00
Received By rmcdouga Date 2003-10-01 Time 14:51 Sent To  
Notes
2003-10-01 00:00:00STAMP AND FILE REVISION 10-1-03 RM

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2003-09-30 Cont ID  
Sent By rmcdouga Date 2003-09-30 Time 12:40 Rev Time 1.00
Received By rmcdouga Date 2003-09-30 Time 12:40 Sent To  
Notes
2003-09-30 00:00:00REVISION WAS DENIED BY S. PILAND WITH
 HISTORIC PRESERVATION. YOU WILL BE
 REQUIRED TO TAKE THE PLANS TO HISTORIC
 PRESERVATION AND HAVE THEIR APPROVAL
 BEFORE THE REVISIONS CAN BE APPROVED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2003-09-26 Cont ID  
Sent By rmcdouga Date 2003-09-26 Time 07:01 Rev Time 1.50
Received By rmcdouga Date 2003-09-26 Time 07:01 Sent To E
Notes
2003-09-26 00:00:00REVISION IS DENIED
  
 1) TWO SETS OF IDENTICAL PLANS ARE
 REQUIRED. THE TWO SETS THAT WERE
 SUBMITTED HAVE SOME DIFFERENCES. PLEASE
 SUBMIT TWO IDENTICAL SETS OF PLANS.
  
 2) THE CHANGE TO THE EXTERIOR COLUMNS
 WILL HAVE TO BE APPROVED BY THE HISTORIC
 PRESERVATION DEPARTMENT. THERE DOES NOT
 APPEAR TO BE ANY OTHER CHANGES TO THE
 EXTERIOR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL :
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2003-07-17 Cont ID  
Sent By rmcdouga Date 2003-07-17 Time 11:27 Rev Time 2.00
Received By rmcdouga Date 2003-07-17 Time 11:26 Sent To  
Notes
2003-07-17 00:00:00REVISION DENIED BY BUILDING
  
 1) REVISED PLANS ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED BY THE DESIGNER
 OF RECORD. THE ENGINEER'S TITLE BLOCK IS
 REQUIRED ON EACH SHEET OF THE PLAN.
  
 2) SUBMIT REVISED SHEETS A-3, S-1, AND
 E/M-1. CHANGES SHOULD BE CLOUDED AND
 NUMBERED. NUMBER OF REVISION AND DATE OF
 REVISION SHOULD BE LISTED IN UPPER RIGHT
 HAND SIDE OF THE SHEET.
  
 3) ROOMS NEED TO BE LABELED ON PLAN.
  
 4) PROVIDE THE WINDOW TYPE AND SIZE OF
 ALL WINDOWS THAT ARE CHANGED FROM THE
 PERMITED PLANS. EGRESS WINDOWS THAT
 COMPLY WITH FBC 1005.4 ARE REQUIRED AT
 ROOMS USED FOR SLEEPING.
  
 5) ANY CHANGES TO THE EXTERIOR (WINDOW
 LOCATION, ETC.) WILL HAVE TO BE REVIEWED
 AND APPROVED BY HISTORIC PRESERVATION
 DEPT.
  
 6) DRAWINGS AND SPECIFICATIONS SHOULD BE
 IDENTICAL TO THE PERMITTED SET EXCEPT
 FOR THE ITEMS THAT ARE BEING REVISED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-12-12 Cont ID  
Sent By rmcdouga Date 2002-12-12 Time 15:13 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-12 00:00:00BUILDING PROVISO
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRENCH DOORS WITHOUT SIDELITES (IMPACT
 RESISTANT)
 - SINGLE HUNG WINDOWS (IMPACT RESISTANT)
  
 2) SUBMIT SIGNED AND SEALED ENGINEERED
 DRAWINGS FOR THE BALCONY GUARDRAILS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-10-10 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 12:50 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE THE MINIMUM ELEVATION IS 7.5
 FEET. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED FOR ADDITION.
 THE CITY CODE OF WPB REQUIRES ALL NEW
 CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT
 OF ANY EXISTING RESIDENTIAL STRUCTURE TO
 HAVE THE LOWEST FLOOR ELEVATED TO SIX
 INCHES ABOVE THE BASE FLOOD ELEVATION.
 PLEASE INDICATE THE FLOOR ELEVATIONS ON
 THE PLANS OR SURVEY.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
  
 5) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 6) SLEEPING ROOMS ARE REQUIRED TO HAVE
 AT LEAST ONE EXTERIOR EMERGENCY ESCAPE
 AND RESCUE OPENING, PER FBC 1005.4. THE
 NET CLEAR OPENING AREA AND DIMENSIONS
 MUST COMPLY WITH FBC SEC.1005.4.4. THE
 SECOND FLOOR BEDROOMS DO NOT COMPLY.
  
 7) INDICATE ACCESS TO ATTIC SPACE AS
 REQUIRED BY FBC SEC. 2309.6.
  
 8) PLEASE CLARIFY THE WINDOWS THAT HAVE
 BEEN DRAWN IN ON THE PLANS. CHANGES MUST
 BE SIGNED AND DATED BY THE DESIGNER OF
 RECORD. INDICATE WINDOW SIZES AND TYPES.
  
 9) THE ADDITION OF THESE WINDOWS EXCEED
 THE PERCENT OF WALL AREA ALLOWED AS
 OPENINGS BY TABLE 600 FOR THE FIRST AND
 SECOND FLOOR OF THE SOUTH ELEVATION.
  
 10) THE NORTH ELEVATION ON SHEET A-3
 SHOWS A WINDOW WITH A "C" DESIGNATION
 AND THERE IS NO "C" LISTED IN THE WINDOW
 SCHEDULE. PLEASE CLARIFY.
  
 11) SHEET A-5 LISTS SLOPE ON BALCONY AS
 1/4" PER FOOT AND TOP CUT OF JOISTS IS
 INDICATED TO PROVIDE 1/8" PER FOOT SLOPE
 PLEASE CLARIFY. NOTE: 1/4":12 SLOPE IS
 REQUIRED FOR MODIFIED ROOFING.
  
 12) IF STORM PANELS ARE BEING USED,
 PLEASE NOTE ON THE PLANS THAT ADEQUATE
 SUBSTRATE WILL BE PROVIDED AT GLAZED
 OPENINGS FOR THE ATTACHMENT OF STORM
 PANELS.
  
 13) FBC SEC. 1909.3 REQUIRES WELDED WIRE
 MESH TO BE SUPPORTED AT SPACINGS NOT TO
 EXCEED 3 FEET. PLEASE INDICATE THIS ON
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-11 Cont ID  
Sent By btrobaug Date 2002-10-29 Time 15:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By btrobaug Date 2002-09-23 Time 07:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-09-24 00:00:00DENIED, SHEET A-1 MUST BE REVISED, BLDG
 IS A SINGLE FAMILY HOUSE, CAN NOT BE
 USED AS ACCESSORY STRUCTUAL IN THE
 FUTURE.
 POOL NEED A CLASSB TO BE LOCATED IN
 THE FRONT YARD