Plan Review Details - Permit 02090603
Plan Review Stops For Permit 02090603
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-30 Cont ID  
Sent By hpiskura Date 2002-09-30 Time 11:03 Rev Time 0.00
Received By hpiskura Date 2002-09-30 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-13 Cont ID  
Sent By dpalmer Date 2002-09-13 Time 15:30 Rev Time 0.50
Received By dpalmer Date 2002-09-13 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-13 Cont ID  
Sent By mcarsill Date 2002-09-13 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-04 Cont ID  
Sent By pkrauss Date 2002-10-04 Time 08:22 Rev Time 0.30
Received By pkrauss Date 2002-10-04 Time 07:51 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-30 Time 14:57 Rev Time 0.40
Received By pkrauss Date 2002-09-30 Time 14:48 Sent To  
Notes
2002-09-30 00:00:00PROVISO:
  
 C.U. STANDS LOCATED ON THE ROOF - STAND
 HEIGHT SHALL COMPLY WITH 2001 FBC TABLE
 1511.7. PROVIDE MANUFACTURER SUBMITTAL
 FOR THE STANDS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-05 Cont ID  
Sent By jleech Date 2002-10-05 Time 06:54 Rev Time 1.00
Received By jleech Date 2002-10-05 Time 06:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By pkrauss Date 2002-10-04 Time 08:23 Rev Time 0.00
Received By kstevens Date 2002-09-24 Time 11:14 Sent To  
Notes
2002-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT 1, EXECUTIVE TOILET ROOM SHALL BE
 ADAPTABLE. 11-4.1.3(11) PLEASE SHOW DE-
 TAILS FOR BACKING AT W/C & SHOWER FOR
 GRAB BARS, AND SEAT. 11-4.21.3/11-4.21.4
 SHOW DETAIL FOR SHR CONTROL 11-4.21.5
 AND CURB 11-4.21.7
 2) SHT 2, ELEVATION "C", LUNCH ROOM SINK
 SHALL COMPLY WITH 11-4.24 AND ALL SUB-
 SECTIONS. (HEIGHT, KNEE SPACE, CLEAR
 FLOOR SPACE ECT.)
 3) SHT 2 PLUMBING RISER TOILET ROOM,
 LUNCH ROOM SINK SHALL DRAIN DOWNSTREAM
 FROM THE W/C AND LAV IN THE WET VENTED
 SYSTEM. SEC. 909.1
 4) PLUMBING RISER EXEC.TOILET, SHOWER IS
 NOT VENTED. SHOWER SHALL BE TAKEN OFF
 BEFORE THE LAV. STACK.
 5) SHT 2 WATER ISOMETRICE, AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMER ARRESTORS
 ARE REQUIRED AT QUICK CLOSING VALVES,
 (ICE MAKERS, DISH WASHERS, WASH MACHINES
 ECT.) PER 604.9 AND IF USED SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF DROP IN
 CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377