| Plan Review Stops For Permit 02090590 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-09-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-13 |
Time |
13:32 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-13 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2002-09-13 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE A LOAD CALCULATION | | | SHOWING EXISTING LOADS AND ALL NEW | | | LOADS BEING ADDED.INCLUDE THE NAMEPLATE | | | RATINGS OF THE AHU & CONDENSING UNIT. | | | ALSO INDICATE THE SIZE OF THE EXISTING | | | SERVICE. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 | | | CALLED CONTRACTOR,GOT LOAD CALC,PANEL IS | | | 200 AMP,HEAT @10K,CALC@ 152 | | | AMPS,PASSED AND PRINTED. |
|
|
|