Plan Review Details - Permit 02090308
Plan Review Stops For Permit 02090308
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-04 Cont ID  
Sent By nmccray Date 2002-12-04 Time 13:10 Rev Time 0.00
Received By nmccray Date 2002-12-04 Time 13:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-26 Cont ID  
Sent By pkrauss Date 2002-12-04 Time 11:14 Rev Time 0.00
Received By mcarsill Date 2002-09-26 Time 14:38 Sent To  
Notes
2002-09-26 00:00:001) PLANS DO NOT INDICATE WHAT THE SPRAY
 BOOTH WILL BE USED FOR.
  
 2) PLANS DO NOT STIPULATE TO WHAT
 TYPE OF REQUIRED FIRE PROTECTION WILL
 BE PROVIDED.
  
 3) PLANS DO NOT INDICATE HOW THE SPRAY
 BOOTH WILL BE GROUNDED.
  
 4) NO INDICATION OF ANY NO SMOKING
 SIGNS INSTALLED WITHIN THE LOCATION.
  
 5) NO INFORMATION ON PORTABLE FIRE
 EXTINGUISHERS.
  
 6) HOW IS MAKE-UP AIR BEING PROVIDED
 FOR THE SPRAY BOOTH.
  
 7) PLEASE PROVIDE MORE DETAILS ON
 FILTERS PLANNED FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-04 Cont ID  
Sent By pkrauss Date 2002-12-04 Time 11:12 Rev Time 0.40
Received By pkrauss Date 2002-12-04 Time 11:12 Sent To FIRE
Notes
2002-12-04 00:00:00ELECTICAL PERMIT REQUIRED FOR THE
 GROUNDING OF SPRAY BOOTH

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-27 Cont ID  
Sent By pkrauss Date 2002-09-27 Time 11:25 Rev Time 0.30
Received By pkrauss Date 2002-09-27 Time 11:25 Sent To  
Notes
2002-09-27 00:00:00SEE FIRE DEPT COMMENTS