Plan Review Details - Permit 02090252
Plan Review Stops For Permit 02090252
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-03 Cont ID  
Sent By pkrauss Date 2003-01-31 Time 16:31 Rev Time 1.00
Received By jwitmer Date 2003-02-03 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-27 Time 11:46 Rev Time 2.00
Received By jwitmer Date 2002-09-30 Time 14:15 Sent To  
Notes
2002-09-30 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02090252
 ADD: 230 WRENA DR
 CONT: O/B STILLS, JAMES
 TEL: (561)615-9101
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE DESIGN CERTIFICATION FORM USED
 WAS FOR THE SBC 1997 CODE. THIS FORM IS
 NO LONGER IN USE AS OF NEW STATE LAW
 REQUIRING THIS INFORMATION TO BE ON THE
 DRAWINGS THEMSELVES.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 2)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) EXTERIOR SWING DOOR, SINGLE/ DOUBLE
 B) MULLIONS
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 4)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
  
 5) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
  
 6)1606.1.1 EXC (4) AF&PA WOOD FRAME
 CONSTRUCTION MANUAL FOR ONE & TWO
 FAMILY - 1995 SBC HIGH WIND EDITION
 1996 SHALL BE PERMITTED FOR APPLICABLE
 WOOD FRAME BUILDINGS OF GROUP 3 OCCU-
 PANCY FOR A BABIC WIND SPEED OF 146 MPH
 OR LESS IN EXPOSURE B AND 124MPH OR LESS
 IN EXPOSURE C IN ACCORDANCE WITH FIGURE
 1606 AND SECTION 1606.1.8.
  
 7)905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 8)905.2.1 RESIENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1(B) ALL SMOKE DETECTORS
 SPECIFIED IN A-8-1.2.1(A) FOR EXISTING
 CONSTRUCTION ARE REQUIRED, AND, IN ADD-
 TION, A SMOKE DETECTOR IS REQUIRED IN
 EACH SLEEPING ROOM.
  
 9) TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
  
 10)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 11)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 MASTER BATH,
  
 12)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 13)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-03-31 Cont ID  
Sent By btrobaug Date 2004-03-31 Time 17:24 Rev Time 0.50
Received By btrobaug Date 2004-03-31 Time 17:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-03-27 Cont ID  
Sent By alange Date 2004-03-30 Time 10:27 Rev Time 0.33
Received By btrobaug Date 2004-03-27 Time 09:30 Sent To  
Notes
2004-03-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE, ALL PLANS DRAWN
 BY AN ARCHITECT/ENGINEER CONTAIN-
 -ING A TITLE BLOCK: MUST BE SIGNED,
 DATED AND SEALED BY THAT ARCH/ENG.
 PER FS 481.221 471.025
 FAC 61G15-23.002, 61G1-16.004
  
 2} PLEASE CLOUD, TRIANGLE , HIGHLIGHT,
 OR INDICATE IN SOME MANNER(EXPLAINED ON
 REVISION SUBMITTAL FORM) THE CHANGES TO
 THE PLANS.
  
 3} PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210.8A-6
  
 4} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-18 Cont ID  
Sent By csiegber Date 2004-03-22 Time 10:36 Rev Time 0.25
Received By dpalmer Date 2003-02-18 Time 06:20 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 07:15 Rev Time 0.33
Received By dpalmer Date 2003-01-24 Time 07:15 Sent To P
Notes
2003-01-24 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE PLANS ARE NOW SIGNED
 AND SEALED BY AN ENGINEER. PLANS THAT
 ARE SIGNED AND SEALED BY AN ENGINEER ARE
 REQ`D TO HAVE A TITLE BLOCK PER FS/FAC
 61G15-23.002
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUIT(S) ON PANEL SCHEDULE. 210-12/
 215-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:26 Rev Time 1.00
Received By btrobaug Date 2002-09-13 Time 16:30 Sent To P
Notes
2002-09-16 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 2} ANY LOW VOLTAGE WIRING TO BE
 INSTALLED MUST BE SHOWN ON A PLAN AND
 PERMITTED.IF LOW VOLTAGE SYSTEMS ARE TO
 BE PART OF THIS APPLICATION,ALL OUTLETS
 HAVE TO BE SHOWN ON THIS PLAN.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.THE ONE SHOWN ON
 THE PANEL SCHEDULE MUST BE FOR THE
 EXISTING BATH AS ONLY 2-15 AMP CIRCUITS
 ARE SHOWN AS BEING ADDED FOR THE ENTIRE
 ADDITION. PLEASE CLARIFY.
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 10:27 Rev Time 0.00
Received By alange Date 2004-03-30 Time 10:27 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 10:36 Sent To E
Notes
2004-03-22 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:26 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 17:26 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-31 Cont ID  
Sent By kstevens Date 2003-01-25 Time 08:58 Rev Time 0.35
Received By pkrauss Date 2003-01-31 Time 16:15 Sent To B
Notes
2003-01-31 00:00:00MECH PERMIT 02090253

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-27 Cont ID  
Sent By kstevens Date 2002-09-26 Time 18:22 Rev Time 0.35
Received By pkrauss Date 2002-09-27 Time 11:33 Sent To B
Notes
2002-09-27 00:00:00DENIED:MECHANICAL PERMIT 02090253
  
 PROVIDE ENERGY CALCULATIONS - SUBMIT
 FORM 600C-01 FOR COMPLIANCE.
  
 ROOMS CONTAINING BATHTUBS, SHOWERS, SPAS
 AND SIMILAR BATHING FIXTURERS SHALL BE
 MECHANICALLY VENTILATEDIN ACCORDANCE
 WITH SECTION 403.2001 FBC(M) 402.3.1.
  
 NO PLANS SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-28 Cont ID  
Sent By kstevens Date 2003-02-28 Time 10:29 Rev Time 0.50
Received By kstevens Date 2003-02-27 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-01-25 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 06:20 Rev Time 0.50
Received By kstevens Date 2003-01-25 Time 08:35 Sent To M
Notes
2003-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 6 SANITARY RISER DIAGRAM DOES NOT
 REFLECT FLOOR PLAN. THE RISER SHALL BE
 DRAWN WILL ALL BATHROOMS (3) AND SHOULD
 REFLECT HOW IT WILL BE PIPED. WASH
 MACHINE IS NOT SHOWN ON FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-26 Cont ID  
Sent By btrobaug Date 2002-09-16 Time 12:15 Rev Time 0.00
Received By kstevens Date 2002-09-26 Time 18:15 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-12 Cont ID  
Sent By sgraham Date 2002-09-12 Time 14:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***