Plan Review Details - Permit 02090190
Plan Review Stops For Permit 02090190
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-10-17 Time 12:51 Rev Time 0.50
Received By dpalmer Date 2002-10-17 Time 12:42 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-25 Cont ID  
Sent By dpalmer Date 2002-09-25 Time 06:35 Rev Time 0.50
Received By dpalmer Date 2002-09-25 Time 06:35 Sent To B
Notes
2002-09-25 00:00:00***********UNSAT ****************
  
 1)NOTE: PLEASE NOTE NO EQUIPMENT GROUND-
 ING CONDUCTOR BETWEEN MAIN DISCONNECTS
 AND METER. THIS WOULD BE PARALLELING THE
 NEUTRAL. PER 250-24
  
 2)NOTE: PLEASE SEE PANEL "B". PLEASE
 CORRELATE LOADS SHOWN FOR A/C #3.
 PLEASE ADJUST LOAD CALCS.
  
 3)NOTE: PLEASE SEE PANEL AND RISER
 DIAGRAM. PLEASE NOTE PANELS SHOWN W/MCB
 AND RISER SHOWN AS MLO? PLEASE CORRELATE
  
 4)NOTE: PLEASE CLARIFY NOTE ON LOWER
 RIGHT HAND CORNER, NOTING GAS WATER
 HEATER? SHOWN AS ELEC ON PANEL SCHEDULE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By jleech Date 2002-09-14 Time 12:02 Rev Time 0.50
Received By jleech Date 2002-09-14 Time 12:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By jleech Date 2002-09-14 Time 12:02 Rev Time 0.33
Received By jleech Date 2002-09-14 Time 12:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By dpalmer Date 2002-10-17 Time 12:51 Rev Time 0.50
Received By lhatten Date   Time   Sent To  
Notes
2002-10-17 00:00:00PRODUCT APPROVALS OK FOR ALL DOORS
 10/17/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-10-08 Cont ID  
Sent By lhatten Date 2002-10-08 Time 15:10 Rev Time 6.00
Received By lhatten Date 2002-10-05 Time 15:09 Sent To  
Notes
2002-10-08 00:00:00REVIEW & STAMPED PLANS 10/05/2002
 NEED PRODUCT APPROV. FOR FRONT DOORS &
 SIDELIGHTS

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-12 Cont ID  
Sent By sgraham Date 2002-09-12 Time 11:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***