Plan Review Details - Permit 02090179
Plan Review Stops For Permit 02090179
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-11-27 Cont ID  
Sent By lmartine Date 2002-11-27 Time 14:52 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-15 Cont ID  
Sent By hpiskura Date 2002-10-15 Time 11:22 Rev Time 0.00
Received By hpiskura Date 2002-10-15 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-16 Cont ID  
Sent By hpiskura Date 2002-09-16 Time 08:35 Rev Time 0.00
Received By hpiskura Date 2002-09-13 Time 16:34 Sent To  
Notes
2002-09-16 00:00:00COUNTY REVIEW FOR IMPACT FEES REQUIRED.
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHE
 TO THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 18:58 Rev Time 0.25
Received By dpalmer Date 2002-12-30 Time 18:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-21 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 14:52 Rev Time 0.25
Received By dpalmer Date 2002-11-21 Time 05:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-10 Cont ID  
Sent By dpalmer Date 2002-10-10 Time 06:16 Rev Time 0.25
Received By dpalmer Date 2002-10-10 Time 06:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-11 Cont ID  
Sent By dpalmer Date 2002-09-11 Time 07:12 Rev Time 1.00
Received By dpalmer Date 2002-09-11 Time 07:11 Sent To  
Notes
2002-09-11 00:00:00***************** UNSAT *************
  
 PLEASE NOTE PLANS ARE SUBMITTED FOR
 PLAN REVIEW. PLEASE SEE COMMENTS FROM
 ALL REVIEWERS DUE TO CHANGE IN USE OF
 OCCUPANCY. RES APT/ TO OFFICE/STUDIO.
 IMPACT FEES MAY BE DUE. PLEASE SEE BLDG
 COMMENTS.
  
  
 1)NOTE: PLEASE NOTE ALL LOAD CALCULATION
 -S NEED TO BE SHOWN FOR COMMERCIAL USE
 AS PER 220-3,220-100,220-11,220-13,
 PLEASE ALSO NOTE ALL CONTINOUS LOADS
 125% 215-3/230-42
 PLEASE NOTE ALL TRACK LIGHTING PER
 220-12?
  
 2)NOTE: PLEASE NOTE, SOME ITEMS SHOWN ON
 PLANS AS N (NEW) AND E (EXISTING) AND
 OTHER ITEMS WITH NO INDICAITON? PLEASE
 CLARIFY.
 PLEASE SHOW WORK/EXISTING ELEC TO BE
 REMOVED/DEMO.
  
 3)NOTE: PLEASE NOTE MISSING EXIT/EM LTS?
 PLEASE ALSO SEE FIRE REVIEW
 COMMENTS FOR ANY THAT ARE/MAY BE REQ`D.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-11-01 Cont ID  
Sent By hpiskura Date 2002-09-16 Time 08:37 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-11-27 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 18:58 Rev Time 0.00
Received By nmccray Date 2002-11-27 Time 11:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By mcarsill Date 2002-10-28 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2002-10-28 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-13 Cont ID  
Sent By mcarsill Date 2002-09-13 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 10:36 Sent To  
Notes
2002-09-13 00:00:001) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHT FIXTURES NOTED. THE
 EXISTING SPACE WAS DESIGNED AS
 RESIDENTIAL NOT BUSINESS. BUSINESS
 OCCUPANCIES REQUIRE EXIT SIGNS AND
 EMERGENCY LIGHTING.
  
 2) THE FIRE SPRINKLER SYSTEM WILL
 BE REQUIRED TO BE REMODELED SINCE
 NEW INTERIOR WALLS ARE BEING INSTALLED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2002-12-18 Time 19:01 Rev Time 0.00
Received By dpalmer Date 2002-12-18 Time 19:01 Sent To  
Notes
2002-12-30 00:00:00TO COMM BOARD #51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 18:28 Rev Time 0.00
Received By btrobaug Date 2002-11-20 Time 18:28 Sent To  
Notes
2002-11-20 00:00:00TO COMM BOARD# 51./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 14:38 Rev Time 0.30
Received By pkrauss Date 2002-12-26 Time 14:28 Sent To E
Notes
2002-12-26 00:00:00MECHANICAL PERMIT 02121294
  
 PLEASE NOTE AS PER COMMENTS FROM 1ST
 PLAN REVIEW:RETURN AIR REQUIRED,
 PROVIDE INFORMATION AS TO THE SIZE OF
 GRILLE & DUCTWORK.SHOULD THIS BE A
 PLENUM, NO COMBUSTIBLES AS PER 2001
 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By pkrauss Date 2002-10-22 Time 11:47 Rev Time 0.35
Received By pkrauss Date 2002-10-22 Time 11:09 Sent To  
Notes
2002-10-22 00:00:00PROVISO:
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-30 Time 13:26 Rev Time 0.30
Received By pkrauss Date 2002-09-30 Time 13:21 Sent To  
Notes
2002-09-30 00:00:00SPOKE WITH PETE RUSSO 9-30-02 - NO
 CHANGE OCCUPANCY FROM ORIGINAL PERMIT -
 ADDED LOW PARTITION WALLS & EXENDED DUCT
 WORK.LIVE/WORK OCCUPANCY.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-09-18 Cont ID  
Sent By lsmith Date 2002-09-18 Time 11:51 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2002-10-31 Cont ID  
Sent By sgraham Date 2002-10-31 Time 16:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-31 00:00:00PROVISO : BEFORE C/O THE MINOR AMENDMENT
 MUST BE APPROVED

Review Stop Z ZONING
Rev No 2 Status F Date 2002-10-31 Cont ID  
Sent By sgraham Date 2002-10-31 Time 13:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-10-31 00:00:00DENIED, NEED MINOR AMENDMENT

Review Stop Z ZONING
Rev No 1 Status N Date 2002-09-18 Cont ID  
Sent By lsmith Date 2002-09-18 Time 11:51 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***