| Plan Review Stops For Permit 02090179 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-11-27 |
Time |
14:52 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-15 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-15 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-09-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-16 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-13 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2002-09-16 00:00:00 | COUNTY REVIEW FOR IMPACT FEES REQUIRED. | | | PLANS MUST BE STAMPED BY THAT OFFICE | | | AND A COPY OF THE PAID RECEIPT ATTACHE | | | TO THE PERMIT APPLICATION.CALL | | | 561-233-5025 FOR MORE INFORMATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-30 |
Time |
18:58 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-12-30 |
Time |
18:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-26 |
Time |
14:52 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-11-21 |
Time |
05:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-10 |
Time |
06:16 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-10-10 |
Time |
06:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-09-11 |
Time |
07:12 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-09-11 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2002-09-11 00:00:00 | ***************** UNSAT ************* | | | | | | PLEASE NOTE PLANS ARE SUBMITTED FOR | | | PLAN REVIEW. PLEASE SEE COMMENTS FROM | | | ALL REVIEWERS DUE TO CHANGE IN USE OF | | | OCCUPANCY. RES APT/ TO OFFICE/STUDIO. | | | IMPACT FEES MAY BE DUE. PLEASE SEE BLDG | | | COMMENTS. | | | | | | | | | 1)NOTE: PLEASE NOTE ALL LOAD CALCULATION | | | -S NEED TO BE SHOWN FOR COMMERCIAL USE | | | AS PER 220-3,220-100,220-11,220-13, | | | PLEASE ALSO NOTE ALL CONTINOUS LOADS | | | 125% 215-3/230-42 | | | PLEASE NOTE ALL TRACK LIGHTING PER | | | 220-12? | | | | | | 2)NOTE: PLEASE NOTE, SOME ITEMS SHOWN ON | | | PLANS AS N (NEW) AND E (EXISTING) AND | | | OTHER ITEMS WITH NO INDICAITON? PLEASE | | | CLARIFY. | | | PLEASE SHOW WORK/EXISTING ELEC TO BE | | | REMOVED/DEMO. | | | | | | 3)NOTE: PLEASE NOTE MISSING EXIT/EM LTS? | | | PLEASE ALSO SEE FIRE REVIEW | | | COMMENTS FOR ANY THAT ARE/MAY BE REQ`D. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-11-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-16 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-30 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2002-11-27 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-28 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-28 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-09-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-13 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-13 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2002-09-13 00:00:00 | 1) NO ILLUMINATED EXIT SIGNS OR | | | EMERGENCY LIGHT FIXTURES NOTED. THE | | | EXISTING SPACE WAS DESIGNED AS | | | RESIDENTIAL NOT BUSINESS. BUSINESS | | | OCCUPANCIES REQUIRE EXIT SIGNS AND | | | EMERGENCY LIGHTING. | | | | | | 2) THE FIRE SPRINKLER SYSTEM WILL | | | BE REQUIRED TO BE REMODELED SINCE | | | NEW INTERIOR WALLS ARE BEING INSTALLED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-18 |
Time |
19:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-18 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2002-12-30 00:00:00 | TO COMM BOARD #51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-20 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-20 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2002-11-20 00:00:00 | TO COMM BOARD# 51./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-26 |
Time |
14:38 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-12-26 |
Time |
14:28 |
Sent To |
E |
|
| Notes |
| 2002-12-26 00:00:00 | MECHANICAL PERMIT 02121294 | | | | | | PLEASE NOTE AS PER COMMENTS FROM 1ST | | | PLAN REVIEW:RETURN AIR REQUIRED, | | | PROVIDE INFORMATION AS TO THE SIZE OF | | | GRILLE & DUCTWORK.SHOULD THIS BE A | | | PLENUM, NO COMBUSTIBLES AS PER 2001 | | | FBC(M) 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-22 |
Time |
11:47 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-10-22 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2002-10-22 00:00:00 | PROVISO: | | | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | | RETURN AIR SHALL BE EQUAL TO SUPPLY | | | AIR BY MEANS OF AIR TRANSFER OR A RETURN | | | AIR (JUMPER). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-30 |
Time |
13:26 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-09-30 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2002-09-30 00:00:00 | SPOKE WITH PETE RUSSO 9-30-02 - NO | | | CHANGE OCCUPANCY FROM ORIGINAL PERMIT - | | | ADDED LOW PARTITION WALLS & EXENDED DUCT | | | WORK.LIVE/WORK OCCUPANCY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-09-18 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-09-18 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-10-31 |
Time |
16:21 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | PROVISO : BEFORE C/O THE MINOR AMENDMENT | | | MUST BE APPROVED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2002-10-31 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-10-31 |
Time |
13:46 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-31 00:00:00 | DENIED, NEED MINOR AMENDMENT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-09-18 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-09-18 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|