Plan Review Details - Permit 02090118
Plan Review Stops For Permit 02090118
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-12-20 Cont ID  
Sent By btrobaug Date 2003-01-06 Time 14:33 Rev Time 0.00
Received By hpiskura Date 2002-12-20 Time 09:00 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 14:02 Rev Time 0.00
Received By hpiskura Date 2002-09-30 Time 10:22 Sent To  
Notes
2002-09-30 00:00:00REVISION 1 DATED 9/6/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-16 Cont ID  
Sent By hpiskura Date 2002-09-16 Time 10:29 Rev Time 0.00
Received By hpiskura Date 2002-09-16 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 12:29 Rev Time 0.50
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-01-15 Cont ID  
Sent By btrobaug Date 2003-01-15 Time 10:38 Rev Time 1.00
Received By btrobaug Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-01-06 Cont ID  
Sent By btrobaug Date 2003-01-06 Time 14:43 Rev Time 0.75
Received By btrobaug Date   Time   Sent To  
Notes
2003-01-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 18:11 Rev Time 0.50
Received By dpalmer Date 2002-12-30 Time 18:11 Sent To  
Notes
2002-12-30 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% AND PLEASE RE-CONFIGURE LOAD
 SUMMARY SHOWN AND PLEASE SHOW WHERE
 THIS LOAD CALC IS SHOWN/FIGURED PER NEC
 220.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-07 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2002-11-07 Time 05:50 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-20 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:48 Rev Time 0.50
Received By dpalmer Date 2002-09-20 Time 06:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-11 Cont ID  
Sent By dpalmer Date 2002-09-11 Time 10:12 Rev Time 0.25
Received By dpalmer Date 2002-09-11 Time 11:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-01-06 Cont ID  
Sent By nmccray Date 2003-01-06 Time 11:20 Rev Time 0.00
Received By nmccray Date 2003-01-06 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-11-12 Cont ID  
Sent By mcarsill Date 2002-11-12 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2002-11-12 Time 11:21 Sent To  
Notes
2002-11-12 00:00:001) FIRE ALARM NOTES (LINE #19) INDICATE
 CLASS "B", STYLE "C". ONLY CLASS "A",
 STYLE "D" CIRCUITS BY AHJ.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-10-28 Cont ID  
Sent By dpalmer Date 2002-11-07 Time 05:52 Rev Time 0.00
Received By mcarsill Date 2002-10-28 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-23 Cont ID  
Sent By mcarsill Date 2002-10-23 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2002-10-23 Time 16:14 Sent To  
Notes
2002-10-23 00:00:001) FIRE ALARM CIRCUITS AND DEVICES SHALL
 BE CLASS "A", STYLE "D".

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-09-06 Cont ID  
Sent By mcarsill Date 2002-09-06 Time 14:46 Rev Time 0.00
Received By mcarsill Date 2002-09-06 Time 14:46 Sent To  
Notes
2002-09-06 00:00:001) FIRE ALARM NOTES INDICATE CLASS B,
 STYLE C. ONLY CLASS A, STYLE D
 CIRCUITS.
  
 2) INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS SHALL MEET APPLICABLE
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2002-12-17 Time 18:17 Sent To  
Notes
2002-12-30 00:00:00TO COMM BOARD #58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 14:02 Rev Time 0.00
Received By btrobaug Date 2002-12-19 Time 14:01 Sent To B
Notes
2002-12-19 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:47 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 16:47 Sent To E
Notes
2002-11-06 00:00:00HAND ROUTED TO DVP,NEEDS FIRE ALSO./WRT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-26 Cont ID  
Sent By pkrauss Date 2002-12-26 Time 14:25 Rev Time 0.45
Received By pkrauss Date 2002-12-26 Time 13:52 Sent To E
Notes
2002-12-26 00:00:00MECH REV PERMIT 02121106

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-21 Cont ID  
Sent By hpiskura Date 2002-12-20 Time 09:05 Rev Time 0.75
Received By hmoser Date 2002-10-21 Time 18:01 Sent To  
Notes
2002-10-21 00:00:00PASS PRIVISO
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By pkrauss Date 2002-09-30 Time 13:08 Rev Time 0.35
Received By pkrauss Date 2002-09-30 Time 12:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By hmoser Date 2002-09-14 Time 13:14 Rev Time 1.00
Received By hmoser Date 2002-09-14 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-10-03 Cont ID  
Sent By jleech Date 2002-10-03 Time 19:39 Rev Time 0.50
Received By jleech Date 2002-10-03 Time 19:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-09-16 Cont ID  
Sent By hpiskura Date 2002-09-16 Time 10:10 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***