| 2002-09-20 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECCESARY CHANGES |
| | ON THE PLANS,AND RESUBMIT FOR REVIEW. |
| | |
| | 1} INDICATE HOW PANEL "B" IS BEING FED. |
| | PANEL "A" DOES NOT HAVE A BREAKER |
| | LISTED FOR IT AND IS NOT LISTED AS A |
| | FEED THROUGH. |
| | |
| | 2} INDICATE THE CONDUIT & WIRE SIZE |
| | FEEDING PANEL "B". |
| | |
| | 4} INDICATE THE OCP OF THE MAIN |
| | (3/0=225AMPS). |
| | |
| | 5} PLEASE INDICATE THE MAIN DISCONNECT |
| | LOCATION ON THE PLANS.NOTE |
| | 230-70(A)C.W.P.B.. |
| | |
| | 6} THE PLANS SHOW A SERVICE- |
| | LATERAL,PLEASE NOTE 680-10 REGARDING |
| | THE POOL. |
| | |
| | 7} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3,ON THE PANEL |
| | SCHEDULE. |
| | |
| | 8} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 9} PLEASE NOTE THE BATH GFI'S REQUIRED |
| | BY 210-11(C)(3) MUST ALSO COMPLY WITH |
| | 210-52(D).THESE RECEPTACLE LOCATIONS |
| | NEED TO BE SHOWN ON THE PLANS. |
| | |
| | 10} THE DETACHED GARAGE MUST COMPLY WITH |
| | 225-31.ALSO SEE 250-32(A) EXEPTION. |
| | |
| | 11} ALL EQUIPMENT MUST COMPLY WITH |
| | 110-26 EG: DISCONNECTS FOR CONDENSERS. |
| | |
| | 12} KITCHEN ISLAND TO COMPLY WITH |
| | 210-52(C)(2). |
| | |
| | IF THERRE ARE ANY QUESTIONS PLEASE CALL; |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/659-8096 EXT. 8392 |