Plan Review Details - Permit 02082013
Plan Review Stops For Permit 02082013
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-11-14 Cont ID  
Sent By hpiskura Date 2002-11-14 Time 14:47 Rev Time 0.00
Received By hpiskura Date 2002-11-14 Time 13:34 Sent To  
Notes
2002-11-14 00:00:00REVISION #2 DATED 10/30/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-30 Cont ID  
Sent By hpiskura Date 2002-10-30 Time 08:29 Rev Time 0.00
Received By hpiskura Date 2002-10-30 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-19 Cont ID  
Sent By hpiskura Date 2002-09-19 Time 10:44 Rev Time 0.00
Received By hpiskura Date 2002-09-18 Time 15:52 Sent To  
Notes
2002-09-19 00:00:00PAID PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 THIS IS A GROUP E OCCUPANCY SUBJECT TO
 FBC 306.1.4 THAT DEFERS TO THE TRADE,
 VOCATION OR BUSINESS BEING TAUGHT.
  
 FACTORY INDUSTRIAL USES ARE, THE PRINT
 SHOP, LIGHT METALS, JEWELRY STUDIO ARE
 SUBJECT TO FBC 307.
  
 THE PHOTO AND DIGITAL STUDIOS MAY BE
 GROUP B, FBC 305, SUBJECT TO THE
 MATERIALS AND PROCESSES THAT WILL TAKE
 PLACE THEREIN.
  
 INFORMATION ON THE PROCESSES AND
 MATERIALS IS NECESSARY TO DETERMINE
 COMPLIANCE WITH FBC 308, FBC 307.1.4,
 FBC 405 AND FBC 408.PLEASE ADDRESS
 THESE SECTIONS OF THE CODE AS
 COMPLETELY AS POSSIBLE AT TIME OF
 PERMIT APPLICATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-18 Cont ID  
Sent By dpalmer Date 2002-10-18 Time 05:46 Rev Time 0.50
Received By dpalmer Date 2002-10-18 Time 05:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By dpalmer Date 2002-09-17 Time 06:21 Rev Time 0.50
Received By dpalmer Date 2002-09-16 Time 16:48 Sent To  
Notes
2002-09-17 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY/VERIFY FEEDS AND/
 OR LOADS FOR "AC" AND "AA. PLEASE NOTE
 POWER PLANS SHOW BOTH AT 225A AND RISER
 SHOWS W/ 150A DISC`S FEEDING.
 PLEASE SUBMIT THE PANEL SCHEDULEOR
 LOADS THAT ARE EXISTING AND BEING ADDED.
  
  
 2)NOTE: PLEASE NOTE PLANS SHOW ADDING
 NEW "DP" REPLACING OLD ,,? ,,(WHAT SIZE)
 PANEL AC? PLEASE CLARFIY LOAD ON MAIN
 SERVICE AND SIZE OF EXISTING SERVICE
 ENTRANCE CONDUCTORS.?
  
 3)NOTE: PLEASE SEE FIRE AND MECH REVIEW
 COMMENTS THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-30 Cont ID  
Sent By mcarsill Date 2002-10-30 Time 13:45 Rev Time 0.00
Received By mcarsill Date 2002-10-30 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-12 Cont ID  
Sent By mcarsill Date 2002-09-12 Time 11:21 Rev Time 0.50
Received By kstevens Date 2002-11-19 Time 09:02 Sent To  
Notes
2002-09-12 00:00:001) PLEASE EXPLAIN NOTE ON DRAWING
 " EXISTING WINDOW BARS TO BE REMOVED
 TO ALLOW FOR EMERGENCY ESCAPE". PLEASE
 INDICATE ON PLANS IF THE EXISTING
 WINDOWS IN THESE LOCATIONS ARE CODE
 COMPLIANT FOR EMERGENCY EGRESS.
  
 2) IT APPEARS THAT A DOOR SIWNGS TOO
 FAR INTO CORRIDOR 101.
  
 3) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
  
 4) IS THE FACP LOCATED IN CORRIDOR 101
 NEW OR EXISTING.
  
 5) ALL NEW ELECTRICAL, MECHANICAL OR
 SERVICE TYPE ROOMS ARE TO BE AT LEAST
 ONE HOUR RATED IF SPRINKLER HEADS ARE
 NOT PRESENT.
  
 6) IS THE SS VENT HOOD NEW OR EXISTING
 AND WHAT WILL IT BE USED FOR.
  
 7) PLEASE EXPLAIN USE OF PROJECTIONS
 THAT ARE LOCATED IN EXISTING MAIN
 GALLERY IN FRONT OF DOORS.
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN
 AIR HANDLING UNITS AT 2000 CFM CAPACITY
 OR ABOVE.
  
 9) PLEASE INDICATE LOCATIONS OF ANY
 EXISTING EMERGENCY LIGHTS OR EXIT
 SIGNS IN MONTGOMERY HALL.
  
 10) PLEASE PROVIDE MORE DETAILS ON
 OXYGEN TANKS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2002-11-19 Cont ID  
Sent By kstevens Date 2002-11-19 Time 09:04 Rev Time 0.25
Received By kstevens Date 2002-11-19 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:23 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 17:23 Sent To  
Notes
2002-11-06 00:00:00TO COMM BOARD #31./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By pkrauss Date 2002-10-22 Time 13:43 Rev Time 0.30
Received By pkrauss Date 2002-10-22 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-26 Cont ID  
Sent By pkrauss Date 2002-09-26 Time 15:24 Rev Time 3.00
Received By pkrauss Date 2002-09-26 Time 14:51 Sent To  
Notes
2002-09-26 00:00:00DENIED:(1ST PLAN CHECK)
  
 1.PLEASE CLARIFY PLAN SHEET A1.3, "NEW
 PARTITIONS TYPE 1 TYP.PLAN SHEET
 A1.1 INDICATES THE AFOREMENTIONED
 PARTITIONS AS A TYPE 2 NON RATED
 STUD WALL. AS PER 2001 FBC(M)607.1.2
 FIRE DAMPERS ARE REQUIRED FOR DUCTS
 PENETRATING WALLS OR PARTITIONS
 HAVING A FIRE RESISTANCE RATING OF
 1 OR MORE HOURS.
  
 2.PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THE ACID, PROVIDE
 MSDS FOR ACID BEING USED.
  
 3.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 2001 FBC(M) 501.4.
  
 4.WHAT IS BEING STORED IN ROOM 110?
  
 5.PROVIDE SUBMITTAL DATA FOR THE
 FLAMMABLE STORAGE CABINET.
  
 6.DUCT SMOKE DETECTORS REQUIRED FOR
 UNIT OR COMBINED UNITS WITH THE
 DESIGN CAPACITY GREATER THAN 2,000
 CFM (2001 FBC(M) 606.2.1 & 606.2.2).
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD/FIRE SUPRESSION/GAS/WALK-IN
 COOLER/FREEZERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-11-19 Cont ID  
Sent By kstevens Date 2002-11-19 Time 09:03 Rev Time 1.00
Received By kstevens Date 2002-11-19 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-18 Cont ID  
Sent By kstevens Date 2002-10-18 Time 19:01 Rev Time 1.50
Received By kstevens Date 2002-10-18 Time 19:01 Sent To  
Notes
2002-10-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW: SHT A1.2 BREAK
 ROOM (108), SINK SHALL COMPLY WITH SECTI
 ON 11-4.24. SHOW HEIGHT 11-4.24.2, KNEE
 CLEARANCE 11-4.24.3, AND CLEAR FLOOR
 SPACE 11-4.24.5 ECT. ALSO DOOR SHALL NOT
 SWING OPEN INTO CLEAR FLOOR SPACE OF ANY
 FIXTURE.
 2) PLEASE SUBMIT GAS CHART USED. FBC-
 2001 FUEL GAS CHARTS ONLY GO UP TO 200'
 AND TOTAL DEVELOPED LENGTH IS APPROX
 400 FEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-20 Cont ID  
Sent By kstevens Date 2002-09-20 Time 18:09 Rev Time 0.00
Received By kstevens Date 2002-09-20 Time 18:09 Sent To  
Notes
2002-09-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT A1.2 BREAK ROOM (108), SINK SHALL
 COMPLY WITH SECTION 11-4.24. SHOW HEIGHT
 11-4.24.2, KNEE CLEARANCE 11-4.24.3,
 CLEAR FLOOR SPACE, 11-4.24.5 ECT.
 2) SHT A1.2 DEVELOPING SINK, IS THERE A
 DILLUTION TANK FOR THE CHEMICALS USED?
 3) SHT P2.1 KEY NOTES #2 & #3, ALL DEMO.
 WORK SHALL BE INSPECTED PRIOR TO COVER-
 ING.
 4) SHT P2.1 KEY NOTES #6, GAS SHALL BE
 ON SEPARATE PERMIT. (SEE F0LLOWING FOR
 GAS PERMIT APPLICATION INFORMATION RE-
 QUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SEC. 401.8 THRU
 402.5.2 & TABLES 402(1)THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A-USE OF
 CAPACITY TABLES(A)(3).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2 IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7-A) PLEASE INDICATE TOTAL APPLIANCES
 WITH BTU'S ON EXISTING PORTION OF GAS
 SYSTEM. PROVIDE COMPLETE GAS RISER DIA-G
 RAM WITH ALL GAS OUTLETS WITH BTU'S FOR
 EACH OUTLET.
 5) PLEASE SUBMIT MORE INFORMATION ON THE
 OXYGEN SYSTEM. PLEASE INDICATE THE WORK-
 ING PRESSURE OF THE OXYGEN SYSTEM.
 6) SEPARATE PERMITS REQUIRED FOR IRRIGA-
 TION AND BACKFLOW. PLUMBING CONTRACTOR
 SHALL INSTALL BACKFLOW FOR IRRIGATION
 CONTRACTOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***