Plan Review Details - Permit 02082011
Plan Review Stops For Permit 02082011
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-21 Cont ID  
Sent By rmcdouga Date 2003-01-21 Time 16:00 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-21 00:00:00SEPARATE PERMIT IS REQUIRED FOR WINDOWS,
 DOORS AND ROOFING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-10-18 Cont ID  
Sent By kstevens Date 2003-01-16 Time 13:17 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-18 00:00:00DENIED BY BUILDING
  
 1)THE WIND LOAD DESIGN CRITERIA CONTAINS
 INCORRECT INFORMATION. PLEASE REVISE.
 - THE BUILDING IMPORTANCE FACTOR IS .77
 - THE BUILDING CATEGORY IS I
 - THE INTERNAL PRESSURE IS + OR - .18
 FOR AN ENCLOSED STRUCTURE
  
 2) SPECIFY THE ROOF SHEATHING ATTACHMENT
 REQUIRED BY THE CITY OF WPB AMENDMENTS
 TO FBC TABLE 2306.1. INDICATE THE
 FASTENER AND THE SPACING THAT IS
 REQUIRED.
  
 3) INDICATE THE POSITIVE AND NEGATIVE
 WIND LOAD PRESSURES FOR ALL EXTERIOR
 OPENINGS ON THE PLANS. ONLY THE NEGATIVE
 PRESSURES HAVE BEEN INDICATED.
  
 4) INDICATE ON THE PLANS THE MIN. SOIL
 BEARING CAPACITY REQUIRED TO SUPPORT THE
 STRUCTURE.
  
 5) THE PLANS MUST BE APPROVED BY THE
 CITY HISTORIC PRESERVATION DEPT. AND BE
 STAMPED AND SIGNED BY THEM.
  
 6) PLEASE REVISE THE REFERENCE TO THE
 FBC IN THE NOTES BELOW THE ROOF FRAMING
 PLAN FROM 2002 TO 2001.
  
 7) ADDITIONAL PERMITS (WITH ADDITIONAL
 FEES) WILL BE REQUIRED FOR THE WINDOWS,
 DOORS, STORM PANELS, PLUMBING AND
 ELECTRICAL AS YOU HAVE INDICATED ON THE
 PLANS.
  
 8) PLEASE RETURN OLD PLANS WHEN
 RESUBMITTING NEW PLANS, IN ORDER TO
 EXPEDIATE REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-24 Cont ID  
Sent By rmcdouga Date 2002-09-24 Time 13:36 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-09-24 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) PROVIDE BUCK ATTACHMENT DETAILS FOR
 EXTERIOR WINDOWS, DOORS AND OVERHEAD
 GARAGE DOOR.
  
 4) THE ROOF SHEATHING NAIL SPACING IS
 INCORRECT. THE CITY OF WPB AMENDMENTS TO
 THE FBC TABLE 2306.1 REQUIRES 8D COMMON
 NAILS SPACED 6"O.C. AT EDGES AND 6" O.C.
 INTERMEDIATE IN ZONES 1&2. PLEASE
 CORRECT.
  
 5) INDICATE THE LOCATION AND SPACING OF
 ALL VERTICLE REINFORCEMENT. (REQUIRED AT
 CORNERS AND EACH SIDE OF OPENINGS)
  
 6) THE USP JRSX CONNECTORS PROVIDE 1180#
 OF UPLIFT RESISTANCE. THE 1735# IS FOR
 FLOOR LOAD. PLEASE REVISE PLANS.
  
 7) THE PLANS SPECIFY 10J COMMON NAILS. I
 AM NOT FAMILIAR WITH THE "J" DESIGNATION
 PLEASE CLARIFY.
  
 8) PROVIDE CONSTRUCTION DETAILS THAT
 INDICATE THE CONSTRUCTION OF THE PARAPET
 CORNER DETAILS. (MATERIALS,ATTACHMENTS,
 ETC.)
  
 9) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WALL OPENINGS ON THE PLANS.
  
 10) THE PLUMBING, ELECTRIC AND WINDOW &
 DOOR INSTALLATION WILL REQUIRE SEPARATE
 PERMITS(WITH ADDITIONAL FEES) AS YOU
 HAVE INDICATED ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 07:28 Rev Time 0.63
Received By btrobaug Date   Time   Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-10-17 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:39 Rev Time 0.25
Received By dpalmer Date 2002-10-17 Time 06:23 Sent To  
Notes
2002-10-17 00:00:00*************** NOTE **************
  
 PLEASE NOTE THAT PLANS WERE SUBMITTED
 WITH NO ELECTRICAL SHOWN. PLANS REDLINED
 FOR REQ`D ELECTRICAL PER NEC.
 210-70
 210-52G
 225-31
 250-32 ETC
  
 PLEASE SUBMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-10 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:38 Rev Time 0.00
Received By btrobaug Date 2003-01-10 Time 16:38 Sent To E
Notes
2003-01-10 00:00:00IN BOX./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By rmcdouga Date 2002-10-28 Time 15:11 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-16 Cont ID  
Sent By kstevens Date 2003-01-16 Time 13:16 Rev Time 0.25
Received By kstevens Date 2003-01-16 Time 13:16 Sent To B
Notes
2003-01-16 00:00:00SUBMITTED SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 07:42 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-28 00:00:00PLUMBING PERMIT WILL BE REQUIRED PRIOR
 TO POURING CONCRETE SLAB.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-09-05 Cont ID  
Sent By sgraham Date 2002-09-05 Time 12:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***