Plan Review Details - Permit 02081926
| Plan Review Stops For Permit 02081926 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-10 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-09 |
Time |
16:07 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-05 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-05 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2002-09-05 00:00:00 | THE STAIRS ARE REQUIRED TO BE ENCLOSED | | | WITH FIRE RATED CONSTRUCTION IN | | | ACCORDANCE WITH FBC 1006.1.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-29 |
Time |
06:14 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-08-29 |
Time |
06:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-10 |
Time |
08:32 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-21 00:00:00 | COMMENTS WERE ADDRESSED BY DESIGNER, SEE | | | PLANS FOR PROVISO LM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-05 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-05 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2002-09-05 00:00:00 | 1) PLEASE INDICATE ON THE PLANS THAT | | | THE EXISTING STAIRS ARE EQUIPPED WITH | | | HANDRAILS. | | | | | | 2) PLEASE INDICATE THE RISE AND RUN | | | OF THE STAIRS ADJACENT TO DOOR # 2. | | | | | | 3) PLEASE PROVIDE OCCUPANT LOAD COUNTS | | | FOR THE LIBRARY AREA. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-05 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-05 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-05 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|