Plan Review Details - Permit 02081895
Plan Review Stops For Permit 02081895
Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-17 Cont ID  
Sent By btrobaug Date 2002-10-17 Time 18:06 Rev Time 0.50
Received By btrobaug Date 2002-10-17 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-04 Cont ID  
Sent By btrobaug Date 2002-09-04 Time 07:04 Rev Time 1.00
Received By btrobaug Date 2002-09-03 Time 15:35 Sent To  
Notes
2002-09-04 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE COMPLY WITH THE FOLLOWING ITEMS
 THAT WERE NOT CLARIFIED ON THE PLANS.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER
 110-9,SUBMIT SAME BEFORE CALLING
 INSPECTION.(MAY BE FAXED TO MY
 ATTENTION @ 659-8026).
  
 2} PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.LIST ON SCHED.
  
 3} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,ON THE PANEL
 SCHEDULE (IN THE RESIDENCE)BEFORE
 CALLING INSPECTION.
  
 4} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392