Plan Review Details - Permit 02081866
Plan Review Stops For Permit 02081866
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-10-15 Cont ID  
Sent By hpiskura Date 2002-10-15 Time 11:16 Rev Time 0.00
Received By hpiskura Date 2002-10-15 Time 10:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By jwitmer Date 2002-09-17 Time 17:47 Rev Time 1.00
Received By hpiskura Date 2002-09-17 Time 17:30 Sent To  
Notes
2002-09-17 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02081866
 ADD: 515 N FLAGLER SUITE 401
 CONT: M J SIMPSON CORP
 TEL: (954)733-9980
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) TABLE 705.1.2 EXIT ACCESS CORRIDORS
 RATING OF ENTRY DOORS.
  
 3)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-08 Cont ID  
Sent By dpalmer Date 2002-10-08 Time 18:06 Rev Time 0.50
Received By dpalmer Date 2002-10-08 Time 16:54 Sent To  
Notes
2002-10-08 00:00:00PLANS NEED TO HAVE OLD SHEETS REMOVED
 AND INSERT NEW SHEETS TO HAVE TWO
 COMPLETE SETS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-09 Cont ID  
Sent By dpalmer Date 2002-09-09 Time 06:14 Rev Time 0.30
Received By dpalmer Date 2002-09-09 Time 06:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-10-04 Cont ID  
Sent By mcarsill Date 2002-10-04 Time 13:44 Rev Time 0.00
Received By mcarsill Date 2002-10-04 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-13 Cont ID  
Sent By mcarsill Date 2002-09-13 Time 11:06 Rev Time 0.00
Received By mcarsill Date 2002-09-13 Time 11:06 Sent To  
Notes
2002-09-13 00:00:001) DOUBLE DOORS INTERSECT WITH THE
 SINGLE DOOR FROM THE ADJACENT AREA.
  
 2) PLEASE INDICATE FIRE RATING OF NEW
 DOUBLE DOORS. THESE DOORS WILL EXIST
 IN A ONE HOUR WALL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By pkrauss Date 2002-10-22 Time 10:53 Rev Time 0.35
Received By pkrauss Date 2002-10-22 Time 09:15 Sent To  
Notes
2002-10-22 00:00:00PROVISO:MECHANICAL PERMIT 02081869
  
 PLEASE CORRELATE PLANS FOR FINAL
 SUBMITTAL.MECHANICAL SHEET M-1 SHOULD
 BE REPLACED WITH REVISED SHEET DATED
 10-1-02 & THE ORIGINAL M-1 SHEET DATED
 7-19-02 SHOULD BE REMOVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-23 Cont ID  
Sent By pkrauss Date 2002-09-23 Time 09:27 Rev Time 0.40
Received By pkrauss Date 2002-09-23 Time 09:19 Sent To  
Notes
2002-09-23 00:00:00SPOKE WITH BERNARDO CARDENAL (ENG),
 O.A. IS SUPPLIED FROM RETURN AIR PLENUM
 FROM ADJOINING SPACE.(THIS IS AN EXIST
 ING SYSTEM - CHANGING OUT HEATPUMP.)

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-11-05 Cont ID  
Sent By kstevens Date 2002-11-05 Time 12:58 Rev Time 1.25
Received By kstevens Date 2002-11-05 Time 12:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-17 Cont ID  
Sent By kstevens Date 2002-10-17 Time 17:44 Rev Time 0.50
Received By kstevens Date 2002-10-17 Time 17:44 Sent To  
Notes
2002-10-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1.0 DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY HDCP FIX-
 TURE. SECTION 11-4.17.5, 11-4.22.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-09-18 Cont ID  
Sent By kstevens Date 2002-09-18 Time 08:53 Rev Time 0.00
Received By kstevens Date 2002-09-18 Time 08:53 Sent To  
Notes
2002-09-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-1.0 PLEASE SHOW CLEAR FLOOR
 SPACE FOR BREAK AREA SINK ROOM #403. IF
 PARALLEL APPROACH THE SINK SHALL BE REQ-
 UIRED TO BE CENTERED IN THE 48" LENGTH
 AT 2'. IF FRONTAL APPROACH SHOW DETAIL
 FOR 11-4.24.3 KNEE CLEARANCE, 11-4.24.5,
 CLEAR FLOOR SPACE, 11-4.24.6 EXPOSED
 PIPES AND SURFACES ECT.
 2) SHT P-1 WATER ISOMETRIC, WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP AS SHOWN PER PDI WH-201 AND MAN-
 UFACTURE INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377