Plan Review Details - Permit 02081856
Plan Review Stops For Permit 02081856
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By jwitmer Date 2002-08-27 Time 11:03 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-27 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02081856
 ADD: 7919 S DIXIE
 SUITE: 7631/ 7629
 CONT: E.L.C.I. CONSTRUCTION GROUP
 TEL: (305)868-3333
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 *****BUILDING PROVISO*****
  
 1) PER THE BUILDING OFFICIAL THE OCCU-
 PANCY SHALL BE SET @ NO MORE THAN 200
 PEOPLE FOR THE TEMPORARY USE OF UNIT FOR
 EDUCATIONAL OCCUPANCY.
 2)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; 2 HR OCCUPANCY SEPERATION
 REQUIRED, PROVIDE U. L. LISTING FOR THE
 2 HR RATED WALL.
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 4)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 5)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
 6) 1021.3.1 PANIC AND FIRE EXIT HARDWARE
 REQUIRED FOR MEANS OF EGRESS, EDUCATION-
 AL OCCUPANCY.
 7) 11-5.2 WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34" IN HEIGHT FOR
 CONSUMPTION, A PORT5ION OF THE MAIN
 COUNTER WHICH IS 60" IN LENGTH MINIMUM
 SHALL BE PROVIDED IN COMPLIANCE WITH
 11-4.32 OR SERVICE SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.
  
 8) REMOVAL OF PLATFORM, OTHERWISE COMPLI
 ANCE WITH VERTICAL ACCESSIBILITY SHALL
 BE REQUIRED, ALSO GUARDRAILS AND HAND
 SHALL BE REQUIRED AS PROPOSED IN SECTION
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2002-08-27 Time 11:36 Sent To  
Notes
2002-08-27 00:00:00********** NOTE **********
  
  
 NO ELECTRICAL WORK TO BE DONE AT THIS
 TIME.
 ALL LIGHTING/RECEPTS EXIT AND EM LTS
 AREEXISTING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By mcarsill Date 2002-08-27 Time 17:26 Rev Time 0.00
Received By mcarsill Date 2002-08-27 Time 17:26 Sent To  
Notes
2002-08-27 00:00:001) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING EQUIPMENT IF EXISTING ARE TO
 BE BROUGHT TO FULL WORKING ORDER.
  
 2) INTERIOR FINISH IN EXITS TO BE CLASS
 A, AND A OR B IN OTHER AREAS.
  
 3) PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
  
 4) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS.SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM EQUIPMENT.
  
 5) REMOVE STAGE AND STAIRS OR MEET
 ALL REQUIREMENTS OF THE FLORIDA
 BUILDING AND FIRE CODES.
  
 6) NO COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS WILL BE ALLOWED
 UNLESS AN APPROVED HOOD,DUCT,AND
 EXTINGUISHING SYSTEM IS INSTALLED.
 PROVIDE SEPARATE PLANS AND PERMITS PRIOR
 TO INSTALLATION.
  
 7) NO OCCUPANT LOADS PROVIDED.ACCORDING
 TO INFORMATION PROVIDED, THE DIRECTOR
 OF CONSTRUCTION SERVICES HAS LIMITED
 THE OCCUPANT LOAD AT 200 PERSONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-08-27 Cont ID  
Sent By pkrauss Date 2002-08-27 Time 12:05 Rev Time 0.35
Received By pkrauss Date 2002-08-27 Time 12:05 Sent To  
Notes
2002-08-27 00:00:00PLEASE PROVIDE 2 COPIES OF ENGINEER
 LETTER SIGNED, SEALED, AND DATED
 INIDCATING THE OUTSIDE AIR CALCULATIONS
 IN ACCORDANCE WITH ASHRAE 62-89 & 2001
 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By kstevens Date 2002-08-27 Time 13:15 Rev Time 0.00
Received By kstevens Date 2002-08-27 Time 13:15 Sent To  
Notes
2002-08-27 00:00:00PASSED-PROVISO
  
 SERVICE SINK SHALL BE INSTALLED IN COUN-
 TER WHERE SINK WAS REMOVED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377