Plan Review Details - Permit 02081855
Plan Review Stops For Permit 02081855
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By jwitmer Date 2002-08-27 Time 10:15 Rev Time 3.00
Received By jwitmer Date 2002-08-27 Time 10:15 Sent To  
Notes
2002-08-27 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02081855
 ADD:7919 S DIXIE HWY
 SUITE 7643/ 7645
 CONT: E.L.C.I. CONSTRUCTION GROUP
 TEL: (305)868-3333
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ****BUILDING PROVISO****
  
 1) PER THE BUILDING OFFICIAL THE OCCU-
 PANCY SHALL BE SET @ NO MORE THAN 200
 PEOPLE FOR THE TEMPORARY USE OF UNIT FOR
 EDUCATIONAL OCCUPANCY.
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 3)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
 4)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
 5) 1021.3.1 PANIC AND FIRE EXIT HARDWARE
 REQUIRED FOR MEANS OF EGRESS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 11:19 Rev Time 0.00
Received By dpalmer Date 2002-08-27 Time 11:19 Sent To  
Notes
2002-08-27 00:00:00*********** NOTE **************
  
 NO ELECTRICAL WORK TO BE DONE AT THIS
 TIME. ALL LIGHTING/EXIT LTS EM LTS
 EXISTING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By mcarsill Date 2002-08-27 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2002-08-27 Time 12:36 Sent To  
Notes
2002-08-27 00:00:001) ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FIXTURES IF EXISTING ARE TO BE
 BROUGHT TO FULL WORKING ORDER.
  
 2) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A, AND OTHER AREAS SHALL BE CLASS
 A OR B.
  
 3) DRAWINGS DO NOT INDICATE FIRE ALARM
 EQUIPMENT. SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE INSTALLATION OF FIRE
 ALARM EQUIPMENT.
  
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
  
 5) PLANS DO NOT INDICATE OCCUPANCY LOAD.
 ACCORDING TO PAPERWORK FROM CONSTRUCTION
 SERVICES, THE DIRECTOR OF THAT
 DEPARTMENT HAS SET THE OCCUPANT LOAD
 AT 200 STUDENTS.
  
 6) NO COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS ARE ALLOWED UNLESS
 AN APPROVED HOOD,DUCT,AND EXTINGUISHING
 SYSTEM IS INSTALLED. SEPARATE PLANS
 AND PERMITS REQUIRED PRIOR TO
 INSTALLATION.
  
 7) PLANS DO NOT INDICATE THE FIRE RATING
 OF ONE OF THE TENANT DEMISING WALLS.
  
 8) FIRE DRILLS ARE REQUIRED TO BE
 PERFORMED.
  
 9) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-08-27 Cont ID  
Sent By pkrauss Date 2002-08-27 Time 11:51 Rev Time 0.35
Received By pkrauss Date 2002-08-27 Time 11:51 Sent To  
Notes
2002-08-27 00:00:00PLEASE PROVIDE 2 COPIES OF ENGINEER
 LETTER SIGNED, SEALED, AND DATED
 INDICATING THE OUTSIDE AIR CALCULATIONS
 IN ACCORDANCE WITH ASHRAE 62-89 & 2001
 FBC(M) TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-08-27 Cont ID  
Sent By kstevens Date 2002-08-27 Time 13:36 Rev Time 0.00
Received By kstevens Date 2002-08-27 Time 13:36 Sent To  
Notes
2002-08-27 00:00:00NO PLUMBING BEING DONE - CERTIFIED
 LETTER REQUIRED EXPLAINING HOW CLASSROOM
 SHALL BE CLEANED WITH OUT A SERVICE SINK
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377