| 2002-08-27 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02081855 |
| | ADD:7919 S DIXIE HWY |
| | SUITE 7643/ 7645 |
| | CONT: E.L.C.I. CONSTRUCTION GROUP |
| | TEL: (305)868-3333 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ****BUILDING PROVISO**** |
| | |
| | 1) PER THE BUILDING OFFICIAL THE OCCU- |
| | PANCY SHALL BE SET @ NO MORE THAN 200 |
| | PEOPLE FOR THE TEMPORARY USE OF UNIT FOR |
| | EDUCATIONAL OCCUPANCY. |
| | 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | 3)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | 4)705.1.2 PENETRATIONS SHALL BE PRO- |
| | TECTED BY AN APPROVED PENETRATION FIRE- |
| | STOP SYSTEM AS TESTED IN ACCORDANCE WITH |
| | ASTM E 814, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER COLUMN AND AN F RATING OF NOT LESS |
| | THAN REQUIRED RATING OF THE WALL |
| | PENETRATED. |
| | 5) 1021.3.1 PANIC AND FIRE EXIT HARDWARE |
| | REQUIRED FOR MEANS OF EGRESS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |