| Plan Review Stops For Permit 02081617 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-11 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-11 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-05 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-03 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2002-09-05 00:00:00 | THE "EXECUTIVE OFFICES" COMPRISE | | | SEPARATE TENANTS, THEREFORE COMPLIANCE | | | WITH FBC704.3.1 IS REQUIRED SINCE IT | | | APPEARS THETOTAL SPACE EXCEEDS THE 3000 | | | SQUARE FEET AREA EXCEPTION.PLEASE | | | REVISE AS NECESSARY. | | | | | | IT APPEARS SEVERAL OF THE PROPOSED | | | OFFICES WILL NOT HAVE THE HC | | | MANEUVERING CLEARANCE AT THE DOORS | | | SHOWN AS (1), AND REQUIRED BY FBC | | | 11-4.13.6. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-03 |
Time |
06:08 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-10-03 |
Time |
06:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-29 |
Time |
05:44 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2002-08-28 |
Time |
20:55 |
Sent To |
|
|
| Notes |
| 2002-08-29 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY METHOD OF | | | EQUIPMENT GROUND FOER NEW PANEL. SIZE | | | PER 250-122. | | | | | | 2)NOTE: PLEASE NOTE, NEED LOAD CALCS | | | FOR EXISTING PANEL "2S" AND 2T. | | | PLANS SHOWING NEW LOADS TO EXISTING | | | PANELS. PLEASE CLARIFY | | | | | | 3)NOTE: PLEASE VERIFY MEANS OF DISC | | | FOR NEW AHU`S. 440-11. | | | | | | 4)NOTE: PLEASE CLARIFY FIRE REVIEW | | | COMMENT. IS THIS GOING TO BE ALL ONE | | | TENANT? ACESS FOR PANEL? | | | | | | 5)NOTE: PLEASE CLARIFY SQ FT IN LOAD | | | CALCS. 220-3,220-10,220-11,,,, | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-10-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-10-01 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-10-01 |
Time |
17:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-08-22 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-08-22 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | 1) DOORS # 2 AND # 5 ARE TO BE AT | | | LEAST 20 MINUTE FIRE RATED. THESE | | | DOORS ARE TO BE EQUIPPED WITH | | | SELF-CLOSING DEVICES TO ENSURE | | | THAT THE DOORS LATCH. | | | | | | 2) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | | | | 3) ARE THE OFFICES GOING TO BE USED | | | FOR SEPARATE TENANTS OR WILL THEY | | | BE USED FOR SEPARATE TENANTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-03 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-03 |
Time |
14:22 |
Sent To |
M |
|
| Notes |
| 2003-09-03 00:00:00 | TO PK DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-19 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-19 |
Time |
15:19 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2003-09-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-09-23 |
Time |
11:09 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-09-23 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-09-11 |
Time |
14:10 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-09-11 |
Time |
14:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-07-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-03 |
Time |
14:22 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-07-02 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-01 |
Time |
08:47 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-07-01 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2003-07-01 00:00:00 | DENIED: | | | | | | ORIGANL PLANS SUBMITTED ARE SIGNED & | | | SEALED BY ARCHITECT.ALL REVISIONS | | | ARE TO BE SIGNED AND SEALED ALSO AS PER | | | FLORIDA STATUES 481. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-19 |
Time |
15:19 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-10-09 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2002-10-09 00:00:00 | PASS/PRIVISO | | | 1) NEED FAN SHUTDOWN ON A/C #3 | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-06 |
Time |
14:26 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-09-06 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2002-09-06 00:00:00 | DENIED: | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3. | | | | | | 2.AS PER 2001 FBC(M) 601.4, PRESSURE | | | DIFFERENTIALS ACROSS CLOSED DOORS | | | WHERE RETURNS ARE CENTRALLY LOCATED | | | SHALL BE LIMITED TO .001 WC OR LESS. | | | PLEASE PROVIDE AIR DUCT PATHWAYS OR | | | AIR TRANSFER PATHWAYS FROM THE HIGH | | | PRESSURE ZONE TO THE LOW ZONE. | | | | | | 3.PROVIDE FAN SHUTDOWN BY DUCT SMOKE | | | DETECTORS IN ACCORDANCE WITH 2001 | | | FBC(M) 606.2.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-10-12 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-10-12 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-08-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-31 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-31 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2002-08-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A2 DETAIL #1 HEIGHT OF SINK SHALL | | | COMPLY WITH 11-4.24.2. ALSO SHOW DETAIL | | | FOR 11-4.24.3 KNEE CLEARANCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|