Plan Review Details - Permit 02081566
| Plan Review Stops For Permit 02081566 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-29 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-29 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-10-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-10-15 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2002-10-15 00:00:00 | AS NOTED IN THE 9/9/02 REVIEW COMMENTS, | | | THE NOTE #50 ON SHEET ID-01, RE: 120 MPH | | | WIND SPEED IS NOT ACCEPTABLE FOR DESIGN | | | IN THE CITY OF WEST PALM BEACH WHICH IS | | | IN THE 140 MPH WIND ZONE. | | | | | | THE PLAN SHEETS PROVIDED FOR REVIEW | | | ARE IRREGULARLY NUMBERED, SHEETS 1,2,6, | | | AND 7 OF 13 AND SHEET ID 0-1, 1 OF 1, | | | WERE REVIEWED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-09 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-09 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2002-09-09 00:00:00 | SHEET ID 01 HARDSCAPE NOTE #50 DECLARES | | | 120 MPH WIND SPEED.WEST PALM BEACH IS | | | IN THE 140 MPH ZONE.PLEASE REVISE AS | | | NECESSARY. | | | | | | SHEET ID 01 NOTE 17 CALLS OUT 1500 PSI | | | F'M.SH12 CALLS OUT 2000 PSI F'M. | | | PLEASE CLARIFY DESIGN INTENT. | | | | | | THE POOL SHOWER SHOWN IN SECTION 2/HS09 | | | IS REQUIRED TO HAVE ACCESSIBLE CONTROLS. | | | SEE FBC 11-4.27. | | | | | | THE HANDRAIL HEIGHT SHOWN IN SECTION | | | 3/HS10 SHOULD BE MEASURED PERPENDICULAR | | | FROM THE LEADING EDGE OF THE TREAD | | | NOSING,SEE FBC 1007.5.1. | | | | | | SECTION 3/HS10 REQUIRES HANDRAILS ON | | | EACH SIDE.SEE FBC 1007.5.2 AND FBC | | | 11-4.9.4. | | | | | | SH 11 AND SH 12.HOW ARE THE ROOF BEAMS | | | CONNECTED TO THE CONCRETE AND MASONRY | | | COLUMNS? |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-25 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-25 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-09-04 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-04 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2002-09-04 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY SECURITY GATES. WHAT PROVISIONS | | | HAVE BEEN MADE FOR FIRE AND PARAMEDICAL | | | ACCESS. IF GATES ARE ELECTRIC, WHAT | | | PROVISIONS HAVE BEEN MADE IN THE | | | EVENT OF LOSS OF POWER. ALL OPENINGS | | | THAT FIRE RESCUE ARE EXPECTED TO PASS | | | THRU MUST BE AT LEAST 20 FEET IN CLEAR | | | WIDTH. DO THE GATES OPEN TOGETHER OR | | | INDEPENDENTLY OF ONE ANOTHER. | | | | | | 2) CLEARANCES OF AT LEAST 7'- 6" ARE | | | REQUIRED TO THE FIRE HYDRANTS OR ANY | | | FIRE PROTECTION DEVICES. | | | | | | 3) HANDRAILS ARE REQUIRED ON ALL STAIRS | | | AND RAMPS. | | | | | | 4) STREET NUMBERS TO BE AT LEAST SIX | | | INCHES HIGH. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-10-28 |
Time |
12:48 |
Sent To |
B |
|
| Notes |
| 2002-10-28 00:00:00 | TO HAROLD PISKURA./WRT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-10-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-10-22 |
Time |
11:58 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2002-08-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-08-28 |
Time |
10:52 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-28 00:00:00 | DENIED BY ZONING | | | 1. WALL MUST BE MAX HEIGHT OF 6' | | | 2. SIGN MUST BE MAX HEIGHT OF 6' |
|
|
|