Plan Review Details - Permit 02081566
Plan Review Stops For Permit 02081566
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-10-29 Cont ID  
Sent By hpiskura Date 2002-10-29 Time 14:31 Rev Time 0.00
Received By hpiskura Date 2002-10-29 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-10-15 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 12:49 Rev Time 0.00
Received By hpiskura Date 2002-10-15 Time 11:31 Sent To  
Notes
2002-10-15 00:00:00AS NOTED IN THE 9/9/02 REVIEW COMMENTS,
 THE NOTE #50 ON SHEET ID-01, RE: 120 MPH
 WIND SPEED IS NOT ACCEPTABLE FOR DESIGN
 IN THE CITY OF WEST PALM BEACH WHICH IS
 IN THE 140 MPH WIND ZONE.
  
 THE PLAN SHEETS PROVIDED FOR REVIEW
 ARE IRREGULARLY NUMBERED, SHEETS 1,2,6,
 AND 7 OF 13 AND SHEET ID 0-1, 1 OF 1,
 WERE REVIEWED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-09-09 Cont ID  
Sent By hpiskura Date 2002-09-09 Time 09:39 Rev Time 0.00
Received By hpiskura Date 2002-09-09 Time 09:39 Sent To  
Notes
2002-09-09 00:00:00SHEET ID 01 HARDSCAPE NOTE #50 DECLARES
 120 MPH WIND SPEED.WEST PALM BEACH IS
 IN THE 140 MPH ZONE.PLEASE REVISE AS
 NECESSARY.
  
 SHEET ID 01 NOTE 17 CALLS OUT 1500 PSI
 F'M.SH12 CALLS OUT 2000 PSI F'M.
 PLEASE CLARIFY DESIGN INTENT.
  
 THE POOL SHOWER SHOWN IN SECTION 2/HS09
 IS REQUIRED TO HAVE ACCESSIBLE CONTROLS.
 SEE FBC 11-4.27.
  
 THE HANDRAIL HEIGHT SHOWN IN SECTION
 3/HS10 SHOULD BE MEASURED PERPENDICULAR
 FROM THE LEADING EDGE OF THE TREAD
 NOSING,SEE FBC 1007.5.1.
  
 SECTION 3/HS10 REQUIRES HANDRAILS ON
 EACH SIDE.SEE FBC 1007.5.2 AND FBC
 11-4.9.4.
  
 SH 11 AND SH 12.HOW ARE THE ROOF BEAMS
 CONNECTED TO THE CONCRETE AND MASONRY
 COLUMNS?

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-25 Cont ID  
Sent By mcarsill Date 2002-09-25 Time 12:54 Rev Time 0.00
Received By mcarsill Date 2002-09-25 Time 12:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-09-04 Cont ID  
Sent By mcarsill Date 2002-09-04 Time 10:20 Rev Time 0.00
Received By mcarsill Date 2002-09-04 Time 10:20 Sent To  
Notes
2002-09-04 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY SECURITY GATES. WHAT PROVISIONS
 HAVE BEEN MADE FOR FIRE AND PARAMEDICAL
 ACCESS. IF GATES ARE ELECTRIC, WHAT
 PROVISIONS HAVE BEEN MADE IN THE
 EVENT OF LOSS OF POWER. ALL OPENINGS
 THAT FIRE RESCUE ARE EXPECTED TO PASS
 THRU MUST BE AT LEAST 20 FEET IN CLEAR
 WIDTH. DO THE GATES OPEN TOGETHER OR
 INDEPENDENTLY OF ONE ANOTHER.
  
 2) CLEARANCES OF AT LEAST 7'- 6" ARE
 REQUIRED TO THE FIRE HYDRANTS OR ANY
 FIRE PROTECTION DEVICES.
  
 3) HANDRAILS ARE REQUIRED ON ALL STAIRS
 AND RAMPS.
  
 4) STREET NUMBERS TO BE AT LEAST SIX
 INCHES HIGH.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 12:49 Rev Time 0.00
Received By btrobaug Date 2002-10-28 Time 12:48 Sent To B
Notes
2002-10-28 00:00:00TO HAROLD PISKURA./WRT

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-22 Cont ID  
Sent By sgraham Date 2002-10-22 Time 11:58 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-28 Cont ID  
Sent By sgraham Date 2002-08-28 Time 10:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-28 00:00:00DENIED BY ZONING
 1. WALL MUST BE MAX HEIGHT OF 6'
 2. SIGN MUST BE MAX HEIGHT OF 6'