| Plan Review Stops For Permit 02081554 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
08:26 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-25 |
Time |
07:01 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-03-25 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2003-03-25 00:00:00 | REVISION OK - 2 LB SYSTEM -REGULATORS - | | | CHANGE RISER DIAGRAM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-03-07 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
08:26 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-03-06 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2003-03-07 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) LINE TO RANGE (180,000 BTU) IS TOO | | | SMALL @ 178' DEVELOPED LENGTH. EITHER | | | 1-1/4" PIPE IS REQUIRED OR A 2 LB. | | | SYSTEM IS REQUIRED WITH A REGULATOR AT | | | THE UNION PRIOR TO ENTERING THE BLDG. | | | AND AT EACH BBQ AND THE POOL HEATER. | | | IF 2 LB SYSTEM USED, PLEASE PROVIDE CUT | | | SHEETS FOR REGULATORS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-08-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-08-21 |
Time |
13:47 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-21 00:00:00 | PROVISO: APPR PER JIM MUNDY. PES |
|
|
|