Plan Review Details - Permit 02081382
Plan Review Stops For Permit 02081382
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-16 Cont ID  
Sent By jwitmer Date 2003-06-16 Time 14:16 Rev Time 0.45
Received By jwitmer Date 2003-06-16 Time 14:16 Sent To  
Notes
2003-06-16 00:00:00MASTER UPDATE TRUSS ANCHOR SCHEDULE TO
 REFLECT 1609.4.3 LOAD REDUCTIONSJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-09-23 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:27 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2002-09-23 00:00:00APPROVED BY JIM WITMER 9-19-02 PERMIT
 02081383

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-04 Cont ID  
Sent By dpalmer Date 2002-09-04 Time 17:00 Rev Time 1.00
Received By dpalmer Date 2002-09-04 Time 16:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-29 Cont ID  
Sent By mcarsill Date 2002-08-29 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2002-08-29 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-30 Cont ID  
Sent By shernand Date 2003-05-30 Time 15:23 Rev Time 0.00
Received By shernand Date 2003-05-30 Time 15:23 Sent To B
Notes
2003-05-30 00:00:00JW DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-23 Cont ID  
Sent By pkrauss Date 2002-09-23 Time 11:39 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2002-09-23 00:00:00LETTER SUBMITTED IN RESPONSE TO H. MOSER
 PROVISO NOTES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-07 Cont ID  
Sent By hmoser Date 2002-09-07 Time 11:17 Rev Time 1.00
Received By hmoser Date 2002-09-07 Time 11:17 Sent To  
Notes
2002-09-07 00:00:00PASS/PROVISO
 1) REFER TO SECTION 402.3.1 BATHROOM
 EXHAUST FBC 2001
 2) NEED FRESH AIR CALCULATIONS FOR ROUGH
 INSPECTION
 3) CONDENSATE DRAIN MUST TERMINATE A MIN
 12IN.FROM BUILDING 1503.4.4 FBC.2001
 4) NEED PRESSURE TEST ON REF.LINES
 150 LB. 1108.1 FBC 2001
 THIS PROVISO IS FOR UNITS C,CR,B,BR,CM,
 AND CMR
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-31 Cont ID  
Sent By kstevens Date 2002-08-31 Time 08:18 Rev Time 0.00
Received By kstevens Date 2002-08-31 Time 08:18 Sent To  
Notes
***NONE***