| Plan Review Stops For Permit 02081324 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:07 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-10-30 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2002-10-30 00:00:00 | | | | *** ISSUED MASTER*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 02081324 | | | ADDRESS: LIBERTY BAY | | | MASTER "C" | | | CONT: HOME DYNAMICS | | | TELL # (954) 275-8569 | | | VICTOR GONZALEZ | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-09-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
11:22 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-09-08 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2002-09-08 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02081324 | | | ADD: *****LIBERTY ISLES***** | | | ****MODEL "C"**** | | | CONT: HOME DYNAMICS | | | TEL: (954)275-8569 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) SHEET A-2 NOTE: MONOLITHIC CONCRETE | | | FOUNDATION WITHOUT HOOKBARS DESIGN BY | | | RATIONAL ANAYLIS, WHAT IS THE MINIMUM | | | DOWEL EMBEDDMENT DEPTH WITH NO HOOKS? | | | GARGE SECTION STEMWALL CONT DO THE | | | DOWEL BARS REQUIRE EXTRA EMBEDDMENT TO | | | REACH THE FOUNDATION PORTION OF THE | | | STEMWALL DESIGN? | | | | | | 2) DESIGN NOTES SHEET A-3 INDICATE 130 | | | MPH, WE ARE LOCATED IN A 140 MPH WIND | | | ZONE. ALSO WIND LOADS AS PER CHAPTER 16, | | | AND ASCE 7-98. | | | | | | 3) TABLE 2306.1 PALM BEACH COUNTY | | | AMENDMENTS | | | ROOF SHEATHING NAILING REQUIREMENTS | | | | | | ZONE 1 & 28D COMMON | | | 6" EDGES & 6" INTERMEDIATES | | | | | | ZONE 38DCOMMON | | | 4" EDGES & 6" INTERMEDIATES | | | | | | 4) PROVIDE KEY PLAN FOR THE INSTALLATION | | | | | | SCHEDULE/ STORM SHUTTERS. | | | JIM WITMER | | | PLAN REVIEW | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-10-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-28 |
Time |
11:22 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-10-28 |
Time |
11:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-28 |
Time |
14:46 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-08-28 |
Time |
13:15 |
Sent To |
R |
|
| Notes |
| 2002-08-28 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE NOTE THERE MUST BE A GFI | | | INSTALLED IN THE FRONT OF THE RESIDENCE | | | PER 210-52(E). | | | | | | 2} PLEASE CLARIFY THE #6 GROUND SHOWN | | | BEING RAN WITH THE FPL SERVICE. | | | | | | 3} THE SMOKE DETECTOR IN THE HALLWAY | | | UPSTAIRS IS TO BE LOCATED 5" FROM | | | RETURN AIR(ALSO 3' FROM BATHS, KITCHENS | | | AND AIR DUCTS PER NFPA-72,CHAPTER | | | 8,1999 EDT. | | | | | | PLEASE REVISE PLANS AND RESUBMIT FOR | | | REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-27 |
Time |
15:07 |
Sent To |
B |
|
| Notes |
| 2003-10-27 00:00:00 | TO JW DESK/REV/MASTERED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-29 |
Time |
12:53 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-01-29 |
Time |
12:27 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2003-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-24 |
Time |
12:43 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-01-24 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2003-01-24 00:00:00 | REVISION TO MASTER DENIED.PLEASE | | | ADDRESS THE FOLLOWING INFORMATION. | | | | | | 1.PLANS SUBMITTED WITH THE ORIGINAL | | | APPROVED SET WERE SIGNED & SEALED BY | | | ARCHITECT.REVISIONS NEED TO BE SIGNED, | | | SEALED, AND DATED BY ARCHITECT (PER | | | CHAPTER 481 OF THE FLORIDA STATUTES). | | | | | | 2.PLANS ARE NOT SPECIFIC.NOTES ON | | | PLAN DUCTWORK TRUNK LINE & DROP LOCATION | | | MAY VARY FROM PLAN, GRILLE SIZE OR FLEX | | | MAY VARY TO EQUAL OR LARGER SIZES, | | | TRIANGLE OR SQUARE BOX.AS PER 2001 | | | FBC CHAPTER 1 AMENDMENTS SECTION 104.2.1 | | | DRAWINGS SHALL BE SPECIFIC, & THE | | | TECHNICAL CODES SHALL NOT BE CITED AS A | | | WHOLE OR IN PART NOR SHALL THE TERM | | | "LEGAL" OR ITS EQUIVALENT BE USED AS | | | SUBSITITUTE FOR SPECIFIC INFORMATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-10-26 |
Time |
06:25 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-10-26 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-08-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-08-24 |
Time |
07:11 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-08-24 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2002-08-24 00:00:00 | PLAN DENIED | | | 1) CAN NOT GO THROUGH WALL ON "O" LOT | | | LINE SIDE OF HOUSE WITH DRYER WALL | | | CAP. | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-10-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-10-26 |
Time |
06:26 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2002-10-26 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2002-10-26 00:00:00 | RE-STAMP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-08-20 |
Time |
17:02 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-08-20 |
Time |
17:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-10-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-10-30 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|