| Plan Review Stops For Permit 02081147 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-03-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2004-03-22 |
Time |
17:27 |
Rev Time |
1.50 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-03-22 00:00:00 | REVSIONS OK LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-09-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-09-12 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-09-12 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2002-09-12 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | --PROVISO-- | | | SUBMIT PRODUCT APPROVALS FOR THE | | | EXTERIOR DOORS AND WINDOWS. | | | | | | --PROVISO-- | | | SUBMIT SHOP DRAWINGS FOR THE GUARDRAILS, | | | PER THE NOTE ON SHEET A9.4, INCLUDING | | | METHOD OF ATTACHMENT TO THE SUPPORTING | | | STRUCTURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-08-27 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-08-27 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-08-27 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2002-08-27 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC 11-4.9.3STAIR NOSING.THE | | | STAIR NOSING SHOWN ON SHEET A9.4, | | | DETAILS 5 & 6, PROJECT FURTHER THAN THE | | | ALLOWABLE MAXIMUM OF 1-1/2" (REF FIG 18) | | | AMEND THE DETAIL TO DEMONSTRATE | | | COMPLIANCE. | | | | | | PROVISOS: | | | | | | SUBMIT PRODUCT APPROVALS FOR THE | | | EXTERIOR DOORS AND WINDOWS. | | | | | | SUBMIT SHOP DRAWINGS FOR THE GUARDRAILS, | | | PER THE NOTE ON SHEET A9.4, SHOWING THE | | | METHOD OF ATTACHMENT TO THE SUPPORTING | | | STRUCTURE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-04-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-13 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-04-13 |
Time |
17:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-02-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-24 |
Time |
14:04 |
Rev Time |
3.00 |
| Received By |
dpalmer |
Date |
2004-02-24 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2004-02-24 00:00:00 | ************* UNSAT ******************** | | | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND | | | 61G15-23.002 | | | PLEASE INCLUDE ALL LICENSE #'S AND NAMES | | | AS REQ'D. | | | PLEASE HAVE PLANS "SIGNED" BY ENGINEERS | | | AND ARCH'S OF RECORD. | | | WE HAVE BEEN INFORMED BY THE FBPE'S | | | INITIALS ARE NOT PERMITTED. SIGNATURE | | | AS REQ'D UNDER FS 471.025, 481.221 | | | SHOULD BE A MIN OF FIRST AND LAST NAME | | | AND HOW NAME APPEARS ON LICENSE. | | | PLEASE ALSO SEE ALL LICENSE # INFORMAT- | | | -ION AS REQ'D UNDER FS 471.023 AND | | | 481.219. | | | THIS IS REQ'D ON ALL SHEETS AND FOR ALL | | | TRADES WEATHER OR NOT COMMENT IS MADE | | | BY OTHER REVIEWERS. | | | PLEASE ALSO SEE PLANS HAVE AN ADDRESS | | | OF 800 S. ROSEMARY, PERMIT IS ISSUED | | | FOR 700 S. ROSEMARY. PLEASE CORRECT | | | TITLE BLOCK. | | | | | | 2)NOTE: PLEASE SEE SERVICE RISER IS NOW | | | SHOWINGDIFFERENT MAINS THAN ORIG PLANS | | | PLEASE PROVIDE NOTE FOR GROUPING OF MAIN | | | -S AS REDLINED ON ORIG PLANS. PLEASE SEE | | | 230.72. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-24 |
Time |
14:11 |
Rev Time |
3.00 |
| Received By |
dpalmer |
Date |
2003-09-24 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2003-09-24 00:00:00 | PLAN REVIEW ONLY ON 12/10/02 | | | ALL ELECTRICAL WORK TO BE DONE UNDER | | | 2002 NEC> |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2002-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-28 |
Time |
09:10 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-08-28 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2002-08-28 00:00:00 | ********* NOTE ************** | | | | | | PLEASE NOTE THAT NO ELECTRICAL PLANS | | | WERE SUBMITTED FOR REVIEW. | | | PLEASE NOTE THAT PLANS WILL BE REQ`D | | | UPON APPLICATION OF ELECTRICAL PERMIT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-09-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-09-12 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-04-22 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-04-22 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2004-04-22 00:00:00 | REVISION DATED 3-25-04 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-02-24 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-02-24 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-02-24 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2004-02-24 00:00:00 | REVISION DATED 01-12-04 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-08-22 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-08-22 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ 2000 EDITION NOT THE 1994 | | | EDITION. | | | | | | 2) WHEN THE CEILING IS PAINTED BLACK, | | | CARE IS TO BE TAKEN TO NOT PAINT THE | | | FIRE SPRINKLER HEADS. ANY FIRE | | | SPRINKLER HEADS THAT ARE PAINTED MUST | | | BE REPLACED. | | | | | | 3) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | FIRE LITE MATERIAL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-03-31 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-03-31 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2004-03-31 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2004-03-31 00:00:00 | TO COMMERCIAL BOARD #53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-18 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-18 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2004-02-18 00:00:00 | TO COMM BD#51 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-06 |
Time |
13:56 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-04-06 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-03-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-03-02 |
Time |
14:28 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-03-02 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2004-03-02 00:00:00 | DENIED: | | | SEE COMMENTS FROM ELECTRICAL & PLUMBING | | | PLAN REVIEW.PLANS ARE TO BE SIGNED, | | | SEALED, AND DATED BY THE ENGINEER PER | | | FS 471.025.PLANS ARE OTHERWISE CODE | | | COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-09-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-09-12 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2004-04-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-01 |
Time |
18:07 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-04-01 |
Time |
18:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-02-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-28 |
Time |
08:10 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2004-02-28 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2004-02-28 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A PROFESSIONAL ENGINEER SHALL SIGN HIS | | | NAME AND AFFIX HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, REPORTS AND FINAL BID | | | DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE, OR OTHER DOCU- | | | MENTS PREPARED OR ISSUED BY SAID REGIS- | | | TRANT AND BEING FILED FOR PUBLIC RECORD. | | | THE DATE THAT THE SIGNATURE AND SEAL IS | | | AFFIXED AS PROVIDED HEREIN SHALL BE EN- | | | TERED ON SAID PLANS, SPECIFICATIONS, RE- | | | PORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL | | | ENGINEER, FAC 61G15-23.002(1) | | | | | | EACH SHEET OF PLANS AND PRINTS WHICH | | | MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 471 SHALL BE SEALED, SIGNED AND | | | DATED BY THE PROFESSIONAL ENGINEER IN | | | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) | | | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2)-FS 471.025 | | | | | | PER FBPE'S RULING INITIALS ARE NOT | | | ACCEPTABLE. SIGNATURE REQUIRED WITH A | | | MINIMUM OF FIRST & LAST NAME AS SHOWN ON | | | LICENSE. | | | | | | ADDRESS ON PLANS SHOWS 800 S ROSEMARY, | | | CORRECT ADDRESS IS 700 S ROSEMARY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-24 |
Time |
14:24 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-09-24 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2003-09-24 00:00:00 | SEE REVIEW PERMIT #01071119 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-09-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-09-12 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-09-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-09-12 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-09-12 00:00:00 | AS PER CITY PLACE APPROVAL STAMP DATED | | | 8/13/02. |
|
|