Plan Review Details - Permit 02081147
Plan Review Stops For Permit 02081147
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By lmartine Date 2004-03-22 Time 17:27 Rev Time 1.50
Received By lmartine Date   Time   Sent To  
Notes
2004-03-22 00:00:00REVSIONS OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By rbrown Date 2002-09-12 Time 15:35 Rev Time 0.00
Received By rbrown Date 2002-09-12 Time 15:35 Sent To  
Notes
2002-09-12 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS.
  
 --PROVISO--
 SUBMIT SHOP DRAWINGS FOR THE GUARDRAILS,
 PER THE NOTE ON SHEET A9.4, INCLUDING
 METHOD OF ATTACHMENT TO THE SUPPORTING
 STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-27 Cont ID  
Sent By rbrown Date 2002-08-27 Time 16:20 Rev Time 0.00
Received By rbrown Date 2002-08-27 Time 16:20 Sent To  
Notes
2002-08-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 11-4.9.3STAIR NOSING.THE
 STAIR NOSING SHOWN ON SHEET A9.4,
 DETAILS 5 & 6, PROJECT FURTHER THAN THE
 ALLOWABLE MAXIMUM OF 1-1/2" (REF FIG 18)
 AMEND THE DETAIL TO DEMONSTRATE
 COMPLIANCE.
  
 PROVISOS:
  
 SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS.
  
 SUBMIT SHOP DRAWINGS FOR THE GUARDRAILS,
 PER THE NOTE ON SHEET A9.4, SHOWING THE
 METHOD OF ATTACHMENT TO THE SUPPORTING
 STRUCTURE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-13 Cont ID  
Sent By dpalmer Date 2004-04-13 Time 17:53 Rev Time 0.50
Received By dpalmer Date 2004-04-13 Time 17:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-02-24 Cont ID  
Sent By dpalmer Date 2004-02-24 Time 14:04 Rev Time 3.00
Received By dpalmer Date 2004-02-24 Time 14:04 Sent To  
Notes
2004-02-24 00:00:00************* UNSAT ********************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 61G15-23.002
 PLEASE INCLUDE ALL LICENSE #'S AND NAMES
 AS REQ'D.
 PLEASE HAVE PLANS "SIGNED" BY ENGINEERS
 AND ARCH'S OF RECORD.
 WE HAVE BEEN INFORMED BY THE FBPE'S
 INITIALS ARE NOT PERMITTED. SIGNATURE
 AS REQ'D UNDER FS 471.025, 481.221
 SHOULD BE A MIN OF FIRST AND LAST NAME
 AND HOW NAME APPEARS ON LICENSE.
 PLEASE ALSO SEE ALL LICENSE # INFORMAT-
 -ION AS REQ'D UNDER FS 471.023 AND
 481.219.
 THIS IS REQ'D ON ALL SHEETS AND FOR ALL
 TRADES WEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
 PLEASE ALSO SEE PLANS HAVE AN ADDRESS
 OF 800 S. ROSEMARY, PERMIT IS ISSUED
 FOR 700 S. ROSEMARY. PLEASE CORRECT
 TITLE BLOCK.
  
 2)NOTE: PLEASE SEE SERVICE RISER IS NOW
 SHOWINGDIFFERENT MAINS THAN ORIG PLANS
 PLEASE PROVIDE NOTE FOR GROUPING OF MAIN
 -S AS REDLINED ON ORIG PLANS. PLEASE SEE
 230.72.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By dpalmer Date 2003-09-24 Time 14:11 Rev Time 3.00
Received By dpalmer Date 2003-09-24 Time 14:11 Sent To  
Notes
2003-09-24 00:00:00PLAN REVIEW ONLY ON 12/10/02
 ALL ELECTRICAL WORK TO BE DONE UNDER
 2002 NEC>

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-28 Time 09:10 Rev Time 0.25
Received By dpalmer Date 2002-08-28 Time 09:10 Sent To  
Notes
2002-08-28 00:00:00********* NOTE **************
  
 PLEASE NOTE THAT NO ELECTRICAL PLANS
 WERE SUBMITTED FOR REVIEW.
 PLEASE NOTE THAT PLANS WILL BE REQ`D
 UPON APPLICATION OF ELECTRICAL PERMIT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-09-12 Cont ID  
Sent By rbrown Date 2002-09-12 Time 15:42 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-04-22 Cont ID  
Sent By nmccray Date 2004-04-22 Time 13:51 Rev Time 0.00
Received By nmccray Date 2004-04-22 Time 13:51 Sent To  
Notes
2004-04-22 00:00:00REVISION DATED 3-25-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By nmccray Date 2004-02-24 Time 15:18 Rev Time 0.00
Received By nmccray Date 2004-02-24 Time 15:18 Sent To  
Notes
2004-02-24 00:00:00REVISION DATED 01-12-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By mcarsill Date 2002-08-22 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2002-08-22 Time 13:38 Sent To  
Notes
2002-08-22 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2000 EDITION NOT THE 1994
 EDITION.
  
 2) WHEN THE CEILING IS PAINTED BLACK,
 CARE IS TO BE TAKEN TO NOT PAINT THE
 FIRE SPRINKLER HEADS. ANY FIRE
 SPRINKLER HEADS THAT ARE PAINTED MUST
 BE REPLACED.
  
 3) PLEASE PROVIDE PRODUCT APPROVALS FOR
 FIRE LITE MATERIAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 13:49 Rev Time 0.00
Received By alange Date 2004-03-31 Time 13:49 Sent To  
Notes
2004-03-31 00:00:00TO COMMERCIAL BOARD #53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 12:23 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 12:23 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#51

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-06 Cont ID  
Sent By pkrauss Date 2004-04-06 Time 13:56 Rev Time 0.35
Received By pkrauss Date 2004-04-06 Time 13:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-03-02 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 14:28 Rev Time 0.45
Received By pkrauss Date 2004-03-02 Time 14:09 Sent To  
Notes
2004-03-02 00:00:00DENIED:
 SEE COMMENTS FROM ELECTRICAL & PLUMBING
 PLAN REVIEW.PLANS ARE TO BE SIGNED,
 SEALED, AND DATED BY THE ENGINEER PER
 FS 471.025.PLANS ARE OTHERWISE CODE
 COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-25 Cont ID  
Sent By rbrown Date 2002-09-12 Time 15:42 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-04-01 Cont ID  
Sent By kstevens Date 2004-04-01 Time 18:07 Rev Time 1.00
Received By kstevens Date 2004-04-01 Time 18:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-02-28 Cont ID  
Sent By kstevens Date 2004-02-28 Time 08:10 Rev Time 1.25
Received By kstevens Date 2004-02-28 Time 08:10 Sent To  
Notes
2004-02-28 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)-FS 471.025
  
 PER FBPE'S RULING INITIALS ARE NOT
 ACCEPTABLE. SIGNATURE REQUIRED WITH A
 MINIMUM OF FIRST & LAST NAME AS SHOWN ON
 LICENSE.
  
 ADDRESS ON PLANS SHOWS 800 S ROSEMARY,
 CORRECT ADDRESS IS 700 S ROSEMARY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-24 Cont ID  
Sent By kstevens Date 2003-09-24 Time 14:24 Rev Time 0.25
Received By kstevens Date 2003-09-24 Time 14:24 Sent To  
Notes
2003-09-24 00:00:00SEE REVIEW PERMIT #01071119

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-09-12 Cont ID  
Sent By rbrown Date 2002-09-12 Time 15:42 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2002-09-12 Cont ID  
Sent By rbrown Date 2002-09-12 Time 16:03 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
2002-09-12 00:00:00AS PER CITY PLACE APPROVAL STAMP DATED
 8/13/02.