Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-09-09 Cont ID  
Sent By dpalmer Date 2002-09-09 Time 07:23 Rev Time 0.50
Received By dpalmer Date 2002-09-09 Time 07:23 Sent To B
Notes
2002-09-09 00:00:00************ NOTES REDLINED *******
  
 PLEASE NOTE THAT ANY OPTIONS SHOWN ON
 PLANS AND THAT ARE INSTALLED NEED TO
 BE REVISED BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 PLEASE ALSO NOTE THERE ARE ITEMS RED-
 -LINED ON PLANS.
  
 1)NOTE : PLEASE NOTE MISSING OUTLETS PER
 210-52 IN MANY LOCATIONS.
  
 2)NOTE: PLEASE NOTE MISSING OUTLETS
 KITCHEN COUNTERSPACEPER 210-52-C-1
  
 3)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-07 Cont ID  
Sent By jleech Date 2002-09-07 Time 10:32 Rev Time 0.50
Received By jleech Date 2002-09-07 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-29 Cont ID  
Sent By jleech Date 2002-08-29 Time 19:19 Rev Time 0.33
Received By jleech Date 2002-08-29 Time 19:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-09-10 Cont ID  
Sent By lhatten Date 2002-09-10 Time 18:38 Rev Time 3.00
Received By lhatten Date 2002-09-09 Time 18:37 Sent To  
Notes
2002-09-10 00:00:00REVIEW & STAMPED PLANS & TRUSS ENG.
 09/09/2002
 CALC. FEES & PRINT CARD 09/10/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By sgraham Date 2002-08-27 Time 11:06 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved