Plan Review Details - Permit 02080980
Plan Review Stops For Permit 02080980
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-10-18 Cont ID  
Sent By dpalmer Date 2002-10-18 Time 13:11 Rev Time 0.50
Received By dpalmer Date 2002-10-18 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-09-30 Cont ID  
Sent By dpalmer Date 2002-09-30 Time 07:14 Rev Time 0.50
Received By dpalmer Date 2002-09-30 Time 07:14 Sent To B
Notes
2002-09-30 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE NOTE ONE FROM FIRST
 REVIEW. PLEASE SUBMIT AIC RATING FOR
 ALL NEW SERVICE EQUIPMENT. 110-9/215-5
  
 2)NOTE: PLEASE NOTE RISER DIAGRAM
 NOW SHOWS EQUIPMENT GROUNDING CONDUCTORS
 BETWEEN METER AND MAINS AND MAINS AND
 PANELS.? PLEASE NOTE THERE ARE NO
 EQUIPMENT GROUNDING CONDUCTORS BETWEEN
 METER AND MAIN. THIS IS PARALLELING THE
 NEUTRAL. PER 250-24.
  
 3)NOTE: PLEASE INITIAL AND DATE ALL
 HANDWRITTEN CHANGES ON PLANS BY AN
 ARCH. FS/FAC 481.221.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-04 Cont ID  
Sent By dpalmer Date 2002-09-04 Time 20:34 Rev Time 0.50
Received By dpalmer Date 2002-09-04 Time 20:34 Sent To B
Notes
2002-09-04 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 SERVICE EQUIPMENT BEING INSTALLED.
 ALL DISC`S/PANEL/BRKRS MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9/
 215-5
  
 2)NOTE: PLEASE NOTE MISSING SD OUTSIDE
 BEDROOMS #`S 3&4
  
 3)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52H/ OUTSIDE 3&4.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED BRANCH CIRCUITS PER 210-12
  
 5)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. PLEASE SIZE PER 250-122
  
 6)NOTE: PLEASESHOW REQ`D GFI
 PROTECTION FOR WHIRLPOOL/SPA TUB. 680-70
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-04 Cont ID  
Sent By hmoser Date 2002-09-04 Time 17:41 Rev Time 0.50
Received By hmoser Date 2002-09-04 Time 17:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By jleech Date 2002-08-27 Time 16:58 Rev Time 0.33
Received By jleech Date 2002-08-27 Time 16:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-10-18 Cont ID  
Sent By rmcdouga Date 2002-10-18 Time 15:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-18 00:00:00*****************PROVISO****************
  
 1) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBBCI OR METO-DADE PRODUCT
 APPROVALS FOR THE OVAL FIXED GLASS
 WINDOWS.
  
 2) IF OPTIONAL BBQ IS TO BE INSTALLED
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION WILL BE REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-10-03 Cont ID  
Sent By rmcdouga Date 2002-10-03 Time 17:33 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON THE PLANS PER 2001 FBC
 1606.1.7. FOR AN ENCLOSED STRUCTURE IT
 IS +/- .18.
  
 2) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ ON
 THE COVERED PORCH AT REAR.
  
 3) THE PRODUCT APPROVAL FOR THE SERIES
 PW-701 FIXED WINDOWS IS MISSING PAGE 8
 OF 8 FROM THE APPROVED DRAWINGS #4231.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE OVAL FIXED GLASS
 WINDOWS. THESE WERE NOT SHOWN ON THE
 PW-701 PRODUCT APPROVAL.
  
 5) THE DESIGNER OF RECORD (ARCHITECT) IS
 REQUIRED TO INITIAL AND DATE EACH OF THE
 REVISIONS THAT WERE RED LINED ON THE
 ORIGINAL PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-11 Cont ID  
Sent By rmcdouga Date 2002-09-11 Time 15:22 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-09-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) ACTIVE LEAF OF FRONT EGRESS DOOR IS
 REQUIRED TO PROVIDE A CLEAR OPENING OF
 NOT LESS THAN 32"WIDE. FBC1012.1.1,
 1012.1.7 & 1012.1.8
  
 5) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR BBQ.
  
 6) SPECIFY THE SIZE OF THE ATTIC ACCESS
 OPENING ON THE PLANS.
  
 7) THE 14" FOOTING DEPTH INDICATED IN
 THE FOUNDATION SCHEDULE ON A2 IS NOT
 ADEQUATE. THE 2001 FBC REQUIRES THE
 BOTTOM OF FOOTINGS TO BE A MINIMUM A 12"
 BELOW GRADE AND THE CITY AMENDMENTS TO
 THE FBC REQUIRE FINISH FLOOR TO BE A
 MINIMUM OF 4" ABOVE GRADE AT HABITABLE
 AREAS. FBC 1804.1.3 AND CITY AMENDMENTS
 1804.1.7. PLEASE REVISE.
  
 8) THE FOUNDATION TYPE IS NOT SPECIFIED
 AT THE INTERIOR GARAGE WALL AND THE
 SHOWER FOR BATH #5.
  
 9) SPECIFY THE LENGTH/EMBEDMENT OF THE
 1/2" ANCHOR BOLTS FOR THE STEEL COLUMNS
 ON A6.
  
 10) PROVIDE A SECTION DETAIL OF THE
 FRONT ENTRY AREA.
  
 11) SPECIFY THE LENGTH/EMBEDMENT OF THE
 3/8" BOLTS, ATTACHING THE BUCKS FOR THE
 GARAGE DOOR ON DETAIL C ON A2.
  
 12) INDICATE THE CONNECTORS FOR THE TOP
 AND BOTTOM OF THE 4X4 WOOD POST.
  
 13) THE ROOF FRAMING PLAN LISTS AN A2
 ANCHOR FOR THE TRUSSES BETWEEN GARAGE
 AND FRONT ENTRY. THE UPLIFTS ON THE PLAN
 EXCEEDS THE VALUES FROM THE TRUSS ANCHOR
 SCHEDULE ON A3. PLEASE CORRECT.
  
 14) THE UPLIFT CAPACITIES OF THE ANCHORS
 LISTED FOR TRUSS ANCHORS D AND E ON A3
 CONTAIN ERRORS. THE RT24T WITH (18) 16D
 NAILS HAS UPLIFT VALUE OF 1565# AND THE
 TAPR216 WITH (11) 16D NAILS HAS AN
 UPLIFT VALUE OF 1485#. THERE IS ALSO A
 REDUCED VALUE WHEN USING MULTIPLE STRAPS
 INSTALLED CLOSER THAN 8" CENTER TO
 CENTER. SEE 2001 USP CATALOG. PLEASE
 REVISE.
  
 15) THE CONDITIONED SPACE SQUARE FOOTAGE
 ON THE ENERGY CALCS. IS DIFFERENT FROM
 THE LIVING AREA LISTED ON THE PLANS.
 PLEASE CORRECT.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS (THE ONE SUBMITTED
 IS FOR AN OXXO CONFIGURATION AND AN OXO
 CONFIG. IS INDICATED ON PLANS)
 - HORIZONTAL SLIDING WINDOWS (EXPIRED ON
 5-20-02 THE CONFIGURATION IS XO AND PLAN
 IS DIFFERENT, WIDTH OF WINDOW ON PLAN
 EXCEEDS PROD. APP.)
 - SERIES PW 701 FIXED WINDOW (EXPIRED ON
 5-20-02 AND SEVERAL FIXED GLASS WINDOWS
 ON PLAN EXCEED THE SIZE LIMITS OF PROD.
 APP.)
 - OVAL FIXED GLASS WINDOWS
 - ARCHED TOP FIXED GLASS WINDOWS
 - DOUBLE FRENCH DOOR WITH SIDELITES
 - GLASS BLOCK [ GLASS BLOCK AT MASTER
 BATH IS IN A HAZARDOUS LOCATION AND A
 MINIMUM UNIFORM FACE THICKNESS OF 0.25
 INCH IS REQUIRED PER FBC 2405.2.2(5)]
  
 17) SAFETY GLAZING IS REQUIRED IN FIXED
 AND OPERABLE PANELS WITH INDIVIDUAL
 PANES GREATER THAN 9 SQ FT, BOTTOM EDGE
 LESS THAN 18" ABOVE THE FLOOR, TOP EDGE
 GREATER THAN 36" ABOVE THE FLOOR AND
 WITHIN 36" OF A WALKING SURFACE PER
 FBC 2405.2.1(4). PLEASE INDICATE ON THE
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By sgraham Date 2002-08-19 Time 09:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***