| 2002-09-17 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE ENGINEERING ANALYSIS/CALCS |
| | SHOWING HOW THE MAIN WIND FORCE RESIS- |
| | TING SYSTEM (MWFRS) WAS DESIGNED TO |
| | TRANSFER LOADS THRU FLOOR AND CEILING |
| | DIAPHRAGMS CONSIDERING THE DOUBLE |
| | CEILING AREA AND THE PARTIAL FLOOR |
| | DIAPHRAGM SUPPORTED ON WOOD COLUMNS |
| | WITH CONNECTORS (TOP AND BOTTOM) THAT |
| | DON'T PROVIDE SUPPORT FOR LATERAL |
| | FORCES. SEE SEC. 1606.2.4 FBC 2001 AND |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 3-PROVIDE ENGINEERING ANALYSIS/CALCS |
| | SHOW'G MASONRY WALLS LATERAL STABILITY |
| | (SEE SEC. 2105 FBC 2001) AND LATERAL |
| | SUPPORT (SEE SEC. 2107 FBC 2001) |
| | CONSIDERING THE HIGH VOLUME AREA & THE |
| | SINGLE BOND BEAM ONLY. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE FIREBLOCKING AT STAIRS. SEE |
| | SEC. 2305.1.4 FBC 2001. |
| | 5-A)SPECIFY FIREBLOCKING AT ALL WALL |
| | SECTIONS. SEC. 2305.1.4 FBC 2001. |
| | B)PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| | AT ALL CONCEALED SPACES REQ'D BY SEC. |
| | 2305.1.4 FBC 2001. |
| | 6-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS. |
| | 7-PROVIDE DETAIL/SPECS FOR ONE HR FIRE |
| | RATED WALL ASSEMBLY @ FRAMED WALL AREA |
| | ABOVE BOND BEAM AT ZERO LOT LINE WALL. |
| | TABLE 600 FBC 2001. |
| | 8-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | ARCHED WINDOWS AT FRAMED AREAS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 9-PROVIDE COMPLETE STRUCTURAL DETAILS & |
| | SPECS FOR RECESSED WINDOW TO ALLOW FOR |
| | INSTALLATION OF STORM SHUTTERS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 10-SEE PRODUCT APPROVAL FOR GARAGE DOORS |
| | STRUCTURAL BUCK REQUIREMENTS. REVISE |
| | DETAIL AS REQUIRED AND SPECIFY BOLT |
| | SIZE AND WASHER. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 11-SPECIFY FIRECUT REQUIREMENTS ON THE |
| | STRUCTURAL WALL SECTIONS. SEC. 2305.4 |
| | 12-STAIR FLOOR PLAN, SHEET A-5: CLARIFY |
| | NOTE #13. THERE IS NOT POST AT THIS |
| | LOCATION. |
| | 13-REVISE STAIR FRAMING PLANS WHEN WOOD |
| | COLUMNS ARE CHANGED FOR STEEL COLUMNS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 14-SPECIFY SPACING FOR WWM IN CONCRETE |
| | SLAB. SEC. 1909.3 FBC 2001. |
| | 15-SHEET S-1: A)SOME INFORMATION IS OVER |
| | LAPPING. B)COLUMN F6 DOESN'T MATCH THE |
| | SCHEDULE. |
| | 16-IDENTIFY ROOF ZONES IN PLANS. SEE |
| | TABLE 2306.1 CITY AMENDMENTS TO FBC. |
| | 17-REVISE TRUSS CONNECTOR SCHEDULE TO |
| | MATCH USP PUBLISHED VALUES. PROVIDE |
| | ENGINEERING CALCS FOR DIFFERENT VALUES |
| | SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 18-A)ATTIC ACCESS TO BE 36" MIN. SEC. |
| | 2309.6 FBC 2001. |
| | B)PROVIDE ATTIC ACCESS ABOVE GARAGE AREA |
| | AND ABOVE MORNING ROOM AREA IF CLEAR |
| | HEIGHT IS MORE THAN 24". SEC. 2309.6 |
| | 19-24SH & 34SH WINDOWS DON'T PROVIDE THE |
| | MIN. CLEAR HEIGHT AND MIN. CLEAR OP'G |
| | REQUIRED BY SEC. 1005.4.4 FBC 2001. |
| | 20-UPDATE SHEET C-1. FOUNDATION NOTE TO |
| | CALL FOR 0.006 MIL VISQUEEN, NOT 0.004 |
| | SEC. 1909.2 FBC 2001. |
| | 21-WHERE IS SEC/5 SHOWN ON SOME PLANS |
| | BY GARAGE AREA. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 22-SHEET A-2: UPDATE GENERAL NOTE FOR |
| | PLUMBING. REFER TO FPC 2001. |
| | 23-SHEET A-3: A)SOME INFORMATION IS OVER |
| | LAPPING. SEE FRONT ELEVATION. B)REVISE |
| | NOTE #4 FOR FRAMING AT ARCHED OPENINGS |
| | AND AT ONE HR FIRE RATED ASSEMBLIES AS |
| | REQUIRED BY TABLE 600 FBC 2001. |
| | 24-SHEET A-5: A)STAIR CALCS AREN'T CLEAR |
| | B)UPDATE SEMCO STRAP. C)HANDRAIL |
| | DIMENSION IS OVERLAPPING. D)KEY NOTE # |
| | 14: DRAFSTOPPING IS NOT THE SAME AS |
| | FIREBLOCKING. REVISE AS REQUIRED. |
| | E)FIREBLOCKING SHOWN ON STAIR SECTION |
| | IS INCORRECT. REVISE AS REQUIRED. SEE |
| | SEC. 2305.1.4 FBC 2001. |
| | 25-SHEET S-1: A)UPDATE SEMCO CONNECTORS. |
| | B)WHERE IS COLUMN P3 SPECIFIED ON 2ND |
| | FLOOR FRAMING PLAN?. |
| | 26-SHEET S-2: A)REVISE SEMCO CONNECTORS. |
| | B)SPECIFY DRAFSTOPPING LOCATION AND |
| | MATERIAL NOT TO EXCEED 500 S.F. SEE |
| | SEC. 2305.2.2 FBC 2001. C)CLARIFY SEC. |
| | #2: USING 1#7 OR 1#5?. FLOOR PLAN TO |
| | BE CALLED 2ND FL. FRAMING PLAN, NOT |
| | GROUND FLOOR PLAN. |
| | 27-PROVIDE SECTION/DETAIL SHOWING HOW IS |
| | BEAM 2B-1 ANCHORED AT THE ENDS. SAME |
| | APPLIES TO BEAM ABOVE MORNING ROOM |
| | AREA. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 28-UPDATE SEMCO CONNECTOR SPECIFIED ON |
| | SECTION 5 OF SHEET S-2 AND ON NOTE #2 |
| | ON SHEET S-2. |