Plan Review Details - Permit 02080886
Plan Review Stops For Permit 02080886
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 11:49 Rev Time 0.50
Received By dpalmer Date 2002-12-26 Time 11:49 Sent To B
Notes
2002-12-26 00:00:00TO ROBERT BROWN'S DESK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By btrobaug Date 2002-09-24 Time 09:36 Rev Time 1.00
Received By btrobaug Date 2002-09-24 Time 08:33 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-13 Cont ID  
Sent By jleahy Date 2002-08-13 Time 16:27 Rev Time 0.30
Received By jleahy Date 2002-08-13 Time 16:26 Sent To P
Notes
2002-08-13 00:00:00NEED TO SHOW WHAT SIZE MAIN????????????
 NEED TO SHOW AIC RATING OF MAIN AND C.B.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-01 Cont ID  
Sent By pkrauss Date 2002-10-01 Time 13:32 Rev Time 0.35
Received By pkrauss Date 2002-10-01 Time 13:17 Sent To R
Notes
2002-10-01 00:00:00MECHANICAL PERMIT 02080887

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-18 Cont ID  
Sent By rbrown Date 2002-09-18 Time 16:38 Rev Time 0.33
Received By hmoser Date 2002-09-18 Time 17:05 Sent To  
Notes
2002-09-18 00:00:00PLAN DENIED
 1) NO ENERGY CALCULATIONS OR
 MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By pschmitz Date 2002-09-30 Time 10:40 Rev Time 0.66
Received By pschmitz Date   Time   Sent To  
Notes
2002-09-30 00:00:00APPR, PES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-17 Cont ID  
Sent By btrobaug Date 2002-09-24 Time 09:36 Rev Time 0.00
Received By kstevens Date 2002-08-17 Time 16:04 Sent To Z
Notes
2002-08-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM SHALL REFLECT
 FLOOR PLAN.
 2) SHOWER NOT VENTED.
 3) HORIZONTAL DRY VENT PAST TUB NOT
 PER CODE. SEC 905.3
 4) SEE ATTACHED SHEET FOR EXAMPLE OF
 SANITARY RISER
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-12-31 Cont ID  
Sent By rbrown Date 2002-12-31 Time 09:49 Rev Time 0.00
Received By rbrown Date 2002-12-31 Time 09:49 Sent To  
Notes
2002-12-31 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 REVISION SUBMITTED ON 12-13-02 HAS BEEN
 PASSED WITH A PROVISO.SEE PROVISO
 MARKED ON WOOD BUCK DETAIL FOR PROPOSED
 FRENCH DOORS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-03 Cont ID  
Sent By rbrown Date 2002-10-03 Time 09:32 Rev Time 0.00
Received By rbrown Date 2002-10-03 Time 09:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-18 Cont ID  
Sent By pkrauss Date 2002-10-01 Time 13:33 Rev Time 0.00
Received By rbrown Date 2002-09-18 Time 15:58 Sent To M
Notes
2002-09-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC 13-103.0ITEMS 2, 3,AND 8 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORM
 SHALL BE COMPLETED.ALSO, ENTER THE
 PERMIT# (02080886) AND JURISDICTION#
 (604700).
  
 3) FBC 2309.6ATTIC ACCESS.PROVIDE AN
 INTERIOR ACCESS OPENING, NOT LESS THAN
 20"X36", TO THE NEW ATTIC.
  
 4) THE SUBMITTED COPY OF THE NOTICE OF
 ACCEPTANCE (NOA# 00-0105.01) FOR THE
 ASPHALT SHINGLES IS OF POOR QUALITY.
 SUBMIT LEGIBLE COPIES.
  
 5) FBC* 104.1.2NO LINTELS HAVE BEEN
 SPECIFIED FOR THE NEW OPENINGS, IN THE
 EXISTING FAMILY ROOM WALL, FOR THE AHU
 CLOSET AND TV AREA.CLARIFY THE MEANS
 OF SUPPORT AT THESE LOCATIONS.
  
 6) FBC 1707.4.2SUBMIT A PRODUCT
 APPROVAL FOR THE PROPOSED GLASS BLOCK
 WINDOW SYSTEM.
  
 7) FBC 1606.1.4MASTER BEDROOM WINDOW.
 THE SUBMITTED NOTICE OF ACCEPTANCE (NOA#
 01-0516.10) FOR THE SINGLE HUNG WINDOWS
 IS FOR SINGLE UNIT APPLICATIONS ONLY.
 SUBMIT A SEPARATE MULLION PRODUCT
 APPROVAL AS APPROPRIATE FOR THE PROPOSED
 DOUBLE WINDOW ARRANGEMENT.
  
 8) FBC 2405.2 THE MASTER BATHROOM SHOWER
 WINDOW IS IN A 'HAZARDOUS LOCATION' & IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-23 Cont ID  
Sent By kstevens Date 2002-08-17 Time 16:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***