Plan Review Details - Permit 02080795
Plan Review Stops For Permit 02080795
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2002-08-27 Time 08:45 Sent To M
Notes
2002-08-27 00:00:00****************PROVISO/NOTE ***********
  
 1)NOTE: PLEASE NOTE MISSING ARC FAULT
 PROTECTION FOR BEDRROMS PER 210-12.
  
 2)NOTE: PLEASE NOTE, SD NEEDS TO BE
 MOVED IN MASTER HALLWAY TO MASTER
 BEDROOM. NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE NOTE SERVICE CONDUCTOR
 SIZE NEEDS TO BE SIZED PER 310-15/310-16
 SHOWN AS #2?
  
 4)NOTE: PLEASE NOTE ELECTRICAL IN
 MASTER BATH TO MOVE OVER.
  
 5)NOTE: PLEASE NOTE OUTLETS FOR KITCHEN
 ISLAND NEED TO BE CLARIFIED. PER 210-52-
 -C-3. GFI PROTECTION REQ`D PER 210-8-A-6
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-04-21 Time 11:25 Rev Time 0.00
Received By shernand Date 2003-04-21 Time 11:25 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By rregueir Date 2003-04-24 Time 17:52 Rev Time 0.50
Received By rregueir Date 2003-04-24 Time 17:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-28 Cont ID  
Sent By shernand Date 2003-04-21 Time 11:25 Rev Time 0.35
Received By pkrauss Date 2002-08-28 Time 09:57 Sent To R
Notes
2002-08-28 00:00:00PROVISO:MECHANICAL PERMIT 02080848
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-26 Cont ID  
Sent By kstevens Date 2002-08-26 Time 18:53 Rev Time 0.00
Received By kstevens Date 2002-08-26 Time 18:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-08-30 Cont ID  
Sent By pkrauss Date 2002-08-28 Time 10:04 Rev Time 2.50
Received By lhatten Date 2002-08-29 Time 08:43 Sent To  
Notes
2002-08-30 00:00:00REVIEW & STAMPED PLANS 08/29/2002
 CALC. FEES & PRINT CARD 08/30/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-20 Cont ID  
Sent By sgraham Date 2002-08-20 Time 10:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***