Plan Review Details - Permit 02080793
Plan Review Stops For Permit 02080793
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-14 Cont ID  
Sent By dpalmer Date 2003-02-14 Time 13:16 Rev Time 0.25
Received By dpalmer Date 2003-02-14 Time 13:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 11:48 Rev Time 0.50
Received By dpalmer Date 2002-08-27 Time 06:07 Sent To M
Notes
2002-08-27 00:00:00************* PROVISO/REVISION *********
  
 PLEASE NOTE ITEMS REDLINED ON PLANS FOR
 CORRECTIONS TO BE MADE.
  
 1)NOTE: PLEASE NOTE WRONG CODE ARTS
 REFERENCED FROM "96" NEC. SHOULD BE
 110-26,250-66,250-140.
  
 2)NOTE: PLEASE NOTE AIC RATING SHOWN AS
 22.00, SHOULD BE 22,000.
  
 3)NOTE: PLEASE NOTE THAT THERE IS NO
 REFERENCE TO THE ARC FAULT PROTECTION
 REQUIRED BY 210-12. RECEPTS ARE SHOWN
 BEING DIFFERENT , BUT NOT DETAILED ON
 SCHEDULE.
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION AS
 A REVSION BEFORE ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-27 Time 14:50 Rev Time 0.00
Received By sthyng Date 2003-03-27 Time 14:50 Sent To M
Notes
2003-03-27 00:00:00TO MECH IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:31 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 15:31 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-10 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 11:48 Sent To E
Notes
2003-02-10 00:00:00TO DVP'S DESK.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-03-28 Cont ID  
Sent By rregueir Date 2003-03-28 Time 07:43 Rev Time 0.33
Received By rregueir Date 2003-03-28 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-03-27 Time 14:50 Rev Time 0.50
Received By rregueir Date 2003-03-26 Time 17:36 Sent To  
Notes
2003-03-26 00:00:00MECHANICAL PLAN REVIEW: FAILED
 EQUIPMENT MODEL NUMBERS LISTED ON
 ARCHITECT'S LETTER SHOW 10 SEER.
 THE LETTER AND ENERGY CALCS CALL FOR
 12 SEER.PLEASE CORRECT THE DISCREPANCY
 AND RESUBMIT.ANY QUESTIONS PLEASE CALL
 RONALD J REGUEIRO 659-8096 X8512

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-28 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 06:11 Rev Time 0.30
Received By pkrauss Date 2002-08-28 Time 10:38 Sent To R
Notes
2002-08-28 00:00:00MECHANICAL PERMIT 02080837

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By kstevens Date 2003-03-13 Time 14:11 Rev Time 0.33
Received By kstevens Date 2003-03-13 Time 14:11 Sent To  
Notes
2003-03-13 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-26 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:31 Rev Time 0.00
Received By kstevens Date 2002-08-26 Time 18:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-08-30 Cont ID  
Sent By pkrauss Date 2002-08-28 Time 10:48 Rev Time 2.50
Received By lhatten Date 2002-08-29 Time 08:58 Sent To  
Notes
2002-08-30 00:00:00REVIEW & STAMPED PLANS 08/29/2002
 CALC. FEES & PRINT CARD 08/30/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-27 Cont ID  
Sent By sgraham Date 2002-08-27 Time 11:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***