Plan Review Details - Permit 02080675
Plan Review Stops For Permit 02080675
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By hpiskura Date 2002-08-22 Time 07:31 Rev Time 0.00
Received By hpiskura Date 2002-08-21 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-16 Cont ID  
Sent By dpalmer Date 2002-08-16 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2002-08-16 Time 07:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-09 Cont ID  
Sent By mcarsill Date 2002-08-09 Time 14:20 Rev Time 0.00
Received By mcarsill Date 2002-08-09 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-03 Cont ID  
Sent By pkrauss Date 2002-09-03 Time 14:37 Rev Time 0.25
Received By hmoser Date 2002-09-03 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-23 Cont ID  
Sent By pkrauss Date 2002-08-23 Time 09:06 Rev Time 0.45
Received By pkrauss Date 2002-08-23 Time 08:34 Sent To  
Notes
2002-08-23 00:00:00PLEASE CLARIFY EXHAUST FAN 1, WILL FAN
 HAVE THE CHANCE OF BEING ACTIVATED?
  
 PROVIDE AIR BALANCE SCHEDULE FOR THE
 "FUTURE" CONFIGURATION OF THIS AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-03 Cont ID  
Sent By kstevens Date 2002-09-03 Time 14:07 Rev Time 0.00
Received By kstevens Date 2002-09-03 Time 14:07 Sent To  
Notes
2002-09-03 00:00:00PASSED/PROVISO
  
 WATER COOLER IN BREAKROOM TO BE ARI-1010
 COMPLIANT.
 BREAK ROOM SINK TO BE DEEP SERVICE SINK

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By kstevens Date 2002-08-15 Time 14:39 Rev Time 0.00
Received By kstevens Date 2002-08-15 Time 14:39 Sent To  
Notes
2002-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT P-1 WATER ISOMETRIC, WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN EFFECTIVE RANGE NOT AT THE
 TOP OF THE DROP AS SHOWN. PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS.
 2) SERVICE SINK AND DRINKING FOUNTAIN
 REQUIRED PER TABLE 403.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377