Plan Review Details - Permit 02080606
Plan Review Stops For Permit 02080606
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-10 Cont ID  
Sent By jwitmer Date 2002-09-10 Time 09:51 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-08-28 Cont ID  
Sent By jwitmer Date 2002-08-28 Time 08:06 Rev Time 1.50
Received By jwitmer Date 2002-08-28 Time 08:05 Sent To  
Notes
2002-08-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02080606
 ADD: 10250 HERONWOOD LANE
 CONT: CODE, INC
 TEL: (561)840-6590
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SINGLE HUNG WINDOW- ONLY 1 COPY
 B) FIXED GLASS
 C) BUTT GLASS DISCREPANCY 3/8"VS3/4"
 D) SLIDING GLASS DOOR
 E) STORM SHUTTERS
 F) ROOF ASSEMBLIES
  
 SINGLE HUNG WINDOW- PROVIDE 2 COPIES OF
 REPORT.
  
 FIXED GLASS ARCH SHEET DISCBIBING THE
 USE OF 3/8" THICK GLASS VS ENGINEERED
 SHEET USING 3/4" THICK GLASS. ALSO
 ARCH DETAILS DEPICT FIXED GLASS VS
 BUTT GLASS?
  
 SLIDING GLASS DOORS- EITHER SUBMIT PRO-
 DUCT TESTING REPORT, (2 COPIES) OR SUB-
 MIT A RECORD RESEARCH REQUEST FOR THE
 PLANS OF EXISTING STRUCTURE, THERE IS
 A FEE INVOLVED FOR RECORD RESEARCH RE-
 QUEST.
  
 STORM SHUTTERS ARE REQUIRED SINCE THE
 BUTT GLAZING DOES NOT HAVE LARGE MISSLE
 IMPACT REPORT!!! THE SAME HOLDS TRUE FOR
 ALL GLAZED UNITS BEING ADDED TO THE ADDI
 TION.STORM SHUTTERS REQUIRE:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 ROOFING REPORT REQUIRED AS PER 1705.
  
 PROVIDE ENERGY CALCS PER 600.2.A.3.
 ADDITIONS: TO USE FORM 600C-01, SEE
 ATTACHMENT.
  
 THIRD REVIEWAS PER CITY CODE, 10% OF
 PERMIT FEE OR MINIMUM OF $50.00 WHICH-
 EVER IS GREATER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-16 Cont ID  
Sent By jwitmer Date 2002-08-16 Time 12:51 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02080606
 ADD: 10250 HERONWOD LA
 CONT: CODE, INC
 TEL: (561)840-6590
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A)SINGLE HUNG WINDOW
 B) FIXED GLASS
 C) BUTT GLASS
 D) SLIDING GLASS DOORS
 E) STORM SHUTTERS
 F) ROOF ASSEMBLIES
  
 2)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD. THIS MAY BE A AVENUE THAT
 YOU MAY TRAVEL FOR THE REUSE OF GLASSED
 OPENINGS.3401.7.2.4 REQUIRES THE REPLACE
 MENT EXTERIOR OPENINGS BE DOORS OR WIN-
 DOWS FIXED OR OPERATIVE SHALL BE DESIGN-
 ED AND CONSTRUCTED IN ACCORDANCE WITH
 THIS CODE.
  
 3) BUTT GLASS: 2406.2 WHERE OTHER THAN
 FIRM SUPPORT OF ALL SIDES IS PROVIDED,
 (THREE SIDES, TWO SIDES, CANTILIVER, OR
 HIGHLY FLEXIBLE, FOR EXAMPLE) DETAILED
 SHOP DRAWINGS, SPECIFICATIONS, AND OR
 OTHER TEST DATA ASSURRING SAFE PERFORMAN
 CE FOR THE SPECIFIC INSTALLATION SHALL
 BE PREPARED BY ENGINEERS EXPERIENCED IN
 THIS WORK AND SHALL BE SUBMITTED FOR
 AND RECEIVED, IF WARRENTED FORMAL APPROV
 AL BY THE BUILDING OFFICIAL.
 ( TEMPERED GLASS SHALL ALSO REQUIRE
 LARGE MISSLE IMPACT RESISTANCE).
  
 4) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 5)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 7)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-12 Cont ID  
Sent By sgraham Date 2002-08-12 Time 12:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***