Plan Review Details - Permit 02080601
Plan Review Stops For Permit 02080601
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-31 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 16:33 Rev Time 0.50
Received By dpalmer Date 2002-10-31 Time 16:33 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-09-16 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 06:45 Rev Time 1.00
Received By dpalmer Date 2002-09-16 Time 12:13 Sent To B
Notes
2002-09-16 00:00:00************UNSAT ******************
  
 1)NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE OUTLETS TO MEET 210-52-C-1 FOR
 WALL SPACE AND 210-52-C-3 FOR PENINSULAR
  
 2)NOTE: PLEASE CLARIFY GROUNDING ELEC-
 -TRODE NOTE AS ( 2-#6 OR 1-#2) ??
 PLEASE SEE 250-66 FOR SIZING OF GROUND-
 -ING ELECTRODE CONDUCTOR.
  
 3)NOTE: PLEASE ALSO NOTE GROUDING ELEC-
 -TRODE TO COLD WATER PIPE ALSO PER 250-
 50.
  
 4)NOTE: PLEASE LIST THE REQ`D BATH CIR-
 -CUITS PER 210-52D/210-11-C-3 ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE LIST THE REQ`DARC-
 -FAULT PROTECTED CIRCUITS PER 210-12 ON
 PANEL SCHEDULE.
  
 6)NOTE: PLEASE NOTE CLEARENCE REQ`MENTS
 FOR WATER HEATER PER 422.17
  
 7)NOTE: PLEASE NOTE OVERCURRENT PROTECT-
 -ION FOR AHU IS NOT SIZED LARGE ENOUGH
 PER 424-3. MIN 125%.
  
 8)NOTE: PLEASE KW RATINGS FOR FRIG AND
 DRYER DO NOT CORRELATE WITH LOAD
 CALCULATIONS.
  
 9)NOTE: PLEASE CLARIFY/NOTE CONDUIT SIZE
 SHOWN ON RISER DIAGRAM GOING TO AHU IS
 SHOWN AT 1 1/2"? PLEASE NOTE IF SHOWN ON
 PLAN, THEN THATS WHAT SIZE WILL BE REQ`D
 TO BE INSTALLED. PLEASE CLARIFY THAT
 THIS 1 1/2" CONDUIT NOTE SHOULD HAVE
 BEEN FOR CONDUIT FROM METER TO PANEL??
  
 10)NOTE: PLEASE NOTE MISSING OUTLET IN
 MASTER BEDROOM PER 210-52.
  
 11)NOTE: PLEASE NOTE SD`S ARE TO BE A
 MIN OF 3' FROM BATHROOM DOORS PER NFPA-
 72 2-5.2.1.6.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 CHNAGES FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 09:16 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 09:16 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 16:34 Sent To B
Notes
2002-11-15 00:00:00TO ROB MCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-29 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 06:45 Rev Time 0.00
Received By dpalmer Date 2002-10-28 Time 06:45 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-06 Cont ID  
Sent By pkrauss Date 2003-05-06 Time 16:46 Rev Time 0.25
Received By pkrauss Date 2003-05-06 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-12 Cont ID  
Sent By shernand Date 2003-04-30 Time 09:16 Rev Time 0.30
Received By pkrauss Date 2002-11-12 Time 11:03 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By kstevens Date 2002-11-09 Time 06:07 Rev Time 0.50
Received By jleech Date 2002-09-14 Time 08:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-09 Cont ID  
Sent By kstevens Date 2002-11-09 Time 06:06 Rev Time 0.50
Received By kstevens Date 2002-11-09 Time 06:06 Sent To M
Notes
2002-11-09 00:00:00WASH MACHINE SHALL NOT DRAIN THROUGH
 WET VENTED BATHROOM GROUP. SEC 909.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-09-14 Cont ID  
Sent By dpalmer Date 2002-10-31 Time 16:34 Rev Time 0.33
Received By jleech Date 2002-09-14 Time 08:00 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-11-18 Cont ID  
Sent By rmcdouga Date 2002-11-18 Time 16:08 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-11-18 Cont ID  
Sent By rmcdouga Date 2002-11-12 Time 16:34 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-11-12 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE IMPORTANCE FACTOR (1.00)
 AND THE INTERNAL PRESSURE COEFFICIENT
 WHICH IS + OR - .18 ON THE PLANS.
  
 3) PLEASE SPECIFY THE CONNECTORS FOR ALL
 OF THE TRUSSES. WHAT CONNECTORS ARE TO
 BE USED FOR THE TRUSSES THAT ARE NOT
 TAGGED?
  
 4) THE ENERGY CALCS. MUST BE SIGNED AND
 SEALED BY THE OWNER/AGENT.
  
 5)STORM PANELS;CITY AMEND.& FBC SECTIONS
 103.6, 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. PROVIDE (2) COPIES OF KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS OR A SEPARATE PERMIT WITH
 ADDITIONAL FEES WILL BE REQUIRED.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS
 - STEEL ENTRY DOOR (THE ONE SUBMITTED
 HAS EXPIRED)
  
 7) GENERAL NOTE #1 ON SHEET 4 IS NOT
 CORRECT. SEE CITY OF WPB AMENDMENTS TO
 THE 2001 FBC REVISED TABLE 2306.1.
  
 8)WALLS SHALL BE FIREBLOCKED AT CEILINGS
 PER FBC 705.3.1. PLEASE INDICATE ON THE
 WALL SECTION ON SHEET 2.
  
 9) PLEASE REMOVE THE PLOT PLAN FROM
 SHEET 1, THAT WAS NOT APPROVED BY ZONING
 DUE TO TOO MUCH PAVED AREA IN THE FRONT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-23 Cont ID  
Sent By pkrauss Date 2002-11-12 Time 11:04 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-09-23 00:00:00DENIED BY BUILDING
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES IN PSF FOR ALL
 EXTERIOR WINDOW AND DOOR OPENINGS.
  
 5) SPECIFY THE TYPE OF WINDOWS THAT ARE
 BEING USED ON THE PLAN. (SINGLE HUNG,
 AWNING, ETC.). THE PRODUCT APPROVAL THAT
 WAS SUBMITTED IS FOR SINGLE HUNG.
  
 6) FBC 2405.2.1(2) REQUIRES SAFETY
 GLAZING IN WIDOWS AT BATHTUBS. PLEASE
 INDICATE TEMPERED GLASS ON PLANS AT
 THESE LOCATIONS.
  
 7)1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE.
  
 8) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 2001 FBC 1005.4
  
 9) PLEASE SPECIFY THE CONNECTORS FOR ALL
 OF THE TRUSSES.
  
 10) THE UPLIFT VALUES LISTED IN THE
 CONNECTOR SCHEDULE ARE NOT CORRECT.
 PLEASE REFER TO THE 2002 SIMPSON
 CATALOG FOR VALUES. PROVIDE CALCULATIONS
 (SIGNED & SEALED) FOR UPLIFT VALUES
 WHEN USING LESS THAN THE NUMBER OF
 FASTENERS SPECIFIED IN THE CATALOG.
  
 11) THE MINIMUM CENTER TO CENTER SPACING
 OF HETA CONNECTORS IS GIVEN AS 8" IN THE
 CATALOG. IF INSTALLED CLOSER THAN 8" A
 REDUCTION IN VALUE IS REQUIRED.
  
 12) THE AREA UNDER ATTIC ON THE ENERGY
 CALCULATIONS IS 1526 SQFT AND THE A/C
 AREA GIVEN ON PLANS IS 1378 SQFT. NO
 VAULTED OR TRAY CEILINGS ARE INDICATED
 ON THE PLANS. PLEASE CORRECT.
  
 13) THE ENERGY CALCS. MUST BE SIGNED AND
 DATED BY THE OWNER/AGENT.
  
 14)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) INDICATE THE CEILING MATERIAL FOR
 THE COVERED ENTRY. (IF USING WIRE LATH &
 STUCCO, INSTALLATION MUST COMPLY WITH
 ASTM C 926 AND ASTM C 1063. SPECIFY LATH
 TYPE AND FASTENERS. HIGH RIB METAL LATH
 REQUIRES FASTENERS TO PENETRATE 1-3/4"
 INTO HORIZONTAL WOOD FRAMING.)
  
 16) INDICATE THE MEAN ROOF HEIGHT ON THE
 PLANS.
  
 17) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS
 - STEEL ENTRY DOOR (THE ONE SUBMITTED
 HAS EXPIRED)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2002-09-06 Cont ID  
Sent By sgraham Date 2002-09-06 Time 16:22 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-08 Cont ID  
Sent By sgraham Date 2002-08-08 Time 14:19 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-08 00:00:00TOO MUCH CONCRETE IN FRONT YARD