| 2002-08-28 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) THE SURVEY SUBMITTED DOES NOT SHOW |
| | THE ONE STORY ADDITION "B" OR THE |
| | EXISTING COVERED PORCH THAT IS BEING |
| | ENCLOSED. |
| | |
| | 4) INDICATE THE THICKNESS OF THE NEW |
| | SLAB (POUR OVER) SHOWN IN SECTION C ON |
| | SHEET 3. |
| | |
| | 5) THE ENGINEER IS REQUIRED TO INITIAL |
| | AND DATE THE POSITIVE AND NEGATIVE WIND |
| | PRESSURES THAT WERE ADDED TO THE PLANS. |
| | |
| | 6) THE PERCENT OF WALL AREA ALLOWED AS |
| | OPENINGS BY TABLE 600 IS EXCEEDED AT THE |
| | FIRST FLOOR WEST ELEVATION. BASED ON A |
| | DISTANCE TO THE PROPERTY LINE OF BETWEEN |
| | 10 TO 20 FEET(40%) AND A 19'X 8'WALL |
| | AREA, THE AREA ALLOWED AS OPENINGS IS |
| | 60.8 SQ.FT. PLEASE CORRECT. |
| | |
| | 7) PROVIDE DETAILS OF THE (2) 2"X 12" |
| | HEADER AT THE OPENING TO THE NEW SECOND |
| | FLOOR BATH. INDICATE FASTENERS, SPACING, |
| | CONNECTIONS TO JACKS, NUMBER OF JACKS, |
| | CONTINOUS LOAD PATH, ETC. |
| | |
| | 8) INDICATE HOW ATTIC ACCESS WILL BE |
| | PROVIDED AT ADDITION AS REQUIRED BY FBC |
| | SEC.2309.6. |
| | |
| | 9) INDICATE HOW THE ADDITION WALLS, |
| | FOOTINGS, WILL BE ATTACHED TO THE |
| | EXISTING STRUCTURE. |
| | |
| | 10) PROVIDE DETAILS INDICATING THE |
| | CONNECTION (STRAPPING,ETC.) OF THE NEW |
| | ROOF TO THE EXISTING AT ADDITION "A". |
| | |
| | 11) PROVIDE A NAILING SCHEDULE FOR THE |
| | FLOOR, WALL AND ROOF SHEATHING. SEE FBC |
| | TABLE 2306.1 AND REVISED TABLE 2306.1 OF |
| | THE CITY OF W.P.B. AMENDMENTS TO THE |
| | 2001 FBC. |
| | |
| | 12) INDICATE THE CEILING MATERIAL FOR |
| | THE PORCH AT REAR AND SPECIFY THE |
| | FASTENER TYPE AND SPACING. |
| | |
| | 13) INDICATE THE MEAN ROOF HEIGHT, FLOOR |
| | AND WALL HEIGHTS ON THE ELEVATIONS. |
| | |
| | 14)INDICATE THE ROOF PITCH ON THE PLANS. |
| | |
| | 15) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | AND DATE THE ENERGY CALC. FORM. |
| | |
| | 16) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ROOF TILE (ONES SUBMITTED ARE EXPIRED) |
| | - STRUCTURAL MULLIONS |
| | - EXTERIOR WOOD ENTRY DOOR |
| | |
| | 17) GUARDRAILS ARE REQUIRED AT REAR |
| | PORCH IF MORE THAN 30" ABOVE FINISHED |
| | GROUND LEVEL. PROVIDE DETAILS FOR |
| | GUARDRAILS AND STAIRS IF REQUIRED. |
| | SEE FBC SEC.1015 AND 1007. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |