Plan Review Details - Permit 02080565
Plan Review Stops For Permit 02080565
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-12 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 18:00 Rev Time 0.50
Received By btrobaug Date 2002-09-12 Time 17:29 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-13 Cont ID  
Sent By btrobaug Date 2002-08-13 Time 15:23 Rev Time 0.00
Received By btrobaug Date 2002-08-13 Time 09:51 Sent To M
Notes
2002-08-13 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLAN,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.INDICATE AS
 GFI'S PER 210-8(A)(1).
  
 3} PLEASE NOTE REAR RECEPTACLE PER
 210-52(E).
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE SHOW THE LOCATION OF THE NEW
 SERVICE ON THE DRAWING IF IT IS TO BE
 MOVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT,8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By btrobaug Date 2002-08-13 Time 15:24 Rev Time 0.35
Received By pkrauss Date 2002-08-19 Time 08:41 Sent To P
Notes
2002-08-19 00:00:00PROVISO ON PLAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-19 Time 09:11 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2002-08-22 00:00:00APPR,PES

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-09-19 Cont ID  
Sent By rmcdouga Date 2002-09-17 Time 14:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-08-28 Cont ID  
Sent By btrobaug Date 2002-09-12 Time 18:01 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE SURVEY SUBMITTED DOES NOT SHOW
 THE ONE STORY ADDITION "B" OR THE
 EXISTING COVERED PORCH THAT IS BEING
 ENCLOSED.
  
 4) INDICATE THE THICKNESS OF THE NEW
 SLAB (POUR OVER) SHOWN IN SECTION C ON
 SHEET 3.
  
 5) THE ENGINEER IS REQUIRED TO INITIAL
 AND DATE THE POSITIVE AND NEGATIVE WIND
 PRESSURES THAT WERE ADDED TO THE PLANS.
  
 6) THE PERCENT OF WALL AREA ALLOWED AS
 OPENINGS BY TABLE 600 IS EXCEEDED AT THE
 FIRST FLOOR WEST ELEVATION. BASED ON A
 DISTANCE TO THE PROPERTY LINE OF BETWEEN
 10 TO 20 FEET(40%) AND A 19'X 8'WALL
 AREA, THE AREA ALLOWED AS OPENINGS IS
 60.8 SQ.FT. PLEASE CORRECT.
  
 7) PROVIDE DETAILS OF THE (2) 2"X 12"
 HEADER AT THE OPENING TO THE NEW SECOND
 FLOOR BATH. INDICATE FASTENERS, SPACING,
 CONNECTIONS TO JACKS, NUMBER OF JACKS,
 CONTINOUS LOAD PATH, ETC.
  
 8) INDICATE HOW ATTIC ACCESS WILL BE
 PROVIDED AT ADDITION AS REQUIRED BY FBC
 SEC.2309.6.
  
 9) INDICATE HOW THE ADDITION WALLS,
 FOOTINGS, WILL BE ATTACHED TO THE
 EXISTING STRUCTURE.
  
 10) PROVIDE DETAILS INDICATING THE
 CONNECTION (STRAPPING,ETC.) OF THE NEW
 ROOF TO THE EXISTING AT ADDITION "A".
  
 11) PROVIDE A NAILING SCHEDULE FOR THE
 FLOOR, WALL AND ROOF SHEATHING. SEE FBC
 TABLE 2306.1 AND REVISED TABLE 2306.1 OF
 THE CITY OF W.P.B. AMENDMENTS TO THE
 2001 FBC.
  
 12) INDICATE THE CEILING MATERIAL FOR
 THE PORCH AT REAR AND SPECIFY THE
 FASTENER TYPE AND SPACING.
  
 13) INDICATE THE MEAN ROOF HEIGHT, FLOOR
 AND WALL HEIGHTS ON THE ELEVATIONS.
  
 14)INDICATE THE ROOF PITCH ON THE PLANS.
  
 15) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALC. FORM.
  
 16) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOF TILE (ONES SUBMITTED ARE EXPIRED)
 - STRUCTURAL MULLIONS
 - EXTERIOR WOOD ENTRY DOOR
  
 17) GUARDRAILS ARE REQUIRED AT REAR
 PORCH IF MORE THAN 30" ABOVE FINISHED
 GROUND LEVEL. PROVIDE DETAILS FOR
 GUARDRAILS AND STAIRS IF REQUIRED.
 SEE FBC SEC.1015 AND 1007.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2002-09-18 Cont ID  
Sent By sgraham Date 2002-09-18 Time 12:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-09-18 00:00:00APPROVED FOR ADDITIONS A & C ONLY
 ADDITION (B) DENIED, DOES NOT MEET
 FRONT SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-12 Cont ID  
Sent By sgraham Date 2002-08-12 Time 12:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***