Plan Review Details - Permit 02080563
Plan Review Stops For Permit 02080563
Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2005-08-13 Cont ID  
Sent By shill Date 2005-08-13 Time 19:00 Rev Time 0.00
Received By SHILL Date 2005-08-13 Time 13:59 Sent To  
Notes
2005-08-13 00:00:00SPEC BOOK PREPARED BY ARCHITECT, DATED
 7/29/02
 PROVISO - AS PER FBC AND APPROVED PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2004-12-03 Cont ID  
Sent By shill Date 2004-12-03 Time 15:45 Rev Time 0.50
Received By shill Date 2004-12-03 Time 15:45 Sent To PC
Notes
2004-12-03 00:00:00REVISION, A119, A120 W/WIND DESIGN
 PRESSURES FROM WIND TUNNEL REPORT, DATED
 10/08/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2004-11-16 Cont ID  
Sent By shill Date 2004-11-15 Time 15:18 Rev Time 1.00
Received By shill Date 2004-11-15 Time 15:18 Sent To PC
Notes
2004-11-16 00:00:00REVISION #18, SHEETS A02, A33,A09, A65,
 A90 DATED 10/8/4
  
 PROVISO - 12" MANEUVERING CLEARANCE FBC
 CH 11 FIG 25 AT DOOR 17, SHEET 33
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2004-11-15 Cont ID  
Sent By shill Date 2004-11-15 Time 10:58 Rev Time 0.50
Received By shill Date 2004-11-15 Time 10:58 Sent To FIRE
Notes
2004-11-15 00:00:00OH PARKING CONTROL GATES SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-29 Time 15:26 Rev Time 0.50
Received By shill Date 2004-10-13 Time 09:40 Sent To PC
Notes
2004-10-13 00:00:00POOL DECK DRAIN SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2004-09-23 Cont ID  
Sent By csiegber Date 2004-09-23 Time 16:33 Rev Time 0.50
Received By shill Date 2004-09-23 Time 11:56 Sent To PC
Notes
2004-09-23 00:00:00REVISED A118 DATED 8/21/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2004-09-14 Cont ID  
Sent By shill Date 2004-09-14 Time 12:54 Rev Time 0.50
Received By shill Date 2004-09-14 Time 12:54 Sent To  
Notes
2004-09-23 00:00:00SUBMITTAL, STUCCO DETAIL AT PARAPET
 PREPARED BY THOMAS KELAHER, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status F Date 2004-08-30 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:38 Rev Time 3.00
Received By shill Date 2004-08-30 Time 10:01 Sent To  
Notes
2004-08-30 00:00:00REVISIONS 13-16, SHEETS A02, A09, A33,
 A65, A90 DATED 8/13/04
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SOME REVISIONS WERE ISSUED WITH
 PROVISOS.PLEASE ADDRESS AT THIS
 TIME: REVISE A101 (ELEVATIONS); PROVIDE
 DESIGN PRESSURES ON ARCHITECTURAL
 SHEETS; PROVIDE AN ORIGINAL SEALED WIND
 TUNNEL REPORT.
  
 2.)A33 AND A90; DOORS 9 AND 17 APPEAR
 TO BE REVERSED.
  
 3.)THE DOOR FOR RENTAL OFFICE NO. 2
 LACKS THE MANEUVERING CLEARANCE;
 FBC11 FIGURE 25. (A33, GRILDLINE I)
 SHOW COMPLIANCE FOR THE DOORS AT RENTAL
 OFFICE NO. 1 (GRIDLINE I) AND MANAGER
 (K), PARKING GARAGE TO VALET LOBBY,
 STAIR #5.
  
 4.)IT IS NOT CLEAR WHAT CHANGED FOR
 REVISION #14 AS THE ENTIRE BUILDING IS
 CLOUDED.PLEASE PROVIDE MORE
 INFORMATION IN THE FORM OF A TRANSMITTAL
 LETTER OR A TELEPHONE CALL. SHEETS A02,
 A09.
  
 5.)I WAS UNABLE TO LOCATE REVISION
 #13 ON SHEET A02.PLEASE PROVIDE
 LOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2004-08-10 Cont ID  
Sent By shill Date 2004-08-10 Time 13:35 Rev Time 1.00
Received By shill Date 2004-08-10 Time 13:35 Sent To  
Notes
2004-08-10 00:00:00ROOF CALCS & NOA SUBMITTALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status F Date 2004-08-04 Cont ID  
Sent By shill Date 2004-08-04 Time 12:51 Rev Time 1.00
Received By shill Date 2004-08-04 Time 12:51 Sent To  
Notes
2004-08-04 00:00:00****CORRECTIONS****
 ROOF SUBMITTALS/NOAS
  
 1.)THE CALCULATIONS FROM ATLANTIC &
 CARIBBEAN ROOF CONSULTING, LLC ARE
 TO BE SIGNED, SEALED ORIGINALS.THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 PERSON SEALING THE DOCUMENT IS TO BE ON
 EACH SHEET.
  
 2.)SUBMIT PRODUCT APPROVALS FOR THE
 POLYFOAM.
  
 3.)THE RAINPROOF 40 APPEARS CODE
 COMPLIANT.HAVE REVIEWED BY DOR AND
 RESUBMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-08-04 Time 11:51 Rev Time 1.00
Received By shill Date 2004-07-28 Time 12:13 Sent To  
Notes
2004-07-28 00:00:00GARAGE DOOR NOAS W/COPY OF WIND TUNNEL
  
 1.)PROVISO - SUBMIT ORIGINAL SEALED COPY
 OF WIND TUNNEL REPORT; SUBMIT REVISION
 FROM ARCHITECT SHOWING PRESSURES ON PLAN
 BEFORE C.O.
  
 2.) ROOF SUBMITTALS WERE DENIED PENDING
 RECEIPT OF THE WIND TUNNEL REPORT.
 PLEASE RESUBMIT AT THIS TIME.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 CC: DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status F Date 2004-07-16 Cont ID  
Sent By csiegber Date 2004-07-27 Time 10:56 Rev Time 0.50
Received By shill Date 2004-07-16 Time 18:11 Sent To  
Notes
2004-07-16 00:00:00****CORRECTIONS****
 ROOF SUBMITTAL, GARAGE DOOR SUBMITTAL
 W/NOAS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 PLEASE PROVIDE AN ORIGINAL SEALED
 WIND TUNNEL TEST REPORT.I AM UNABLE
 TO LOCATE OUR COPY.MY APOLOGIES FOR
 ANY INCONVENIENCE.AN UNSEALED COPY
 MAY BE SUBMITTED FOR REVIEW OF THE
 ABOVE REFERENCED SUBMITTALS; AN
 ORIGINAL WILL BE REQUIRED PRIOR TO CO.
  
 PLEASE ALSO HAVE THE DESIGNER OF
 RECORD SUPPLY DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2004-07-16 Cont ID  
Sent By shill Date 2004-07-16 Time 17:58 Rev Time 0.50
Received By shill Date 2004-07-16 Time 17:58 Sent To  
Notes
2004-07-16 00:00:00INSULATION SPECS

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status F Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:38 Rev Time 0.50
Received By shill Date 2004-06-15 Time 09:42 Sent To  
Notes
2004-06-15 00:00:00****CORRECTIONS****
 SHORING/RESHORE LETTERS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE CONTRACTOR CERTIFICATION
 LETTERS ARE TO BE NOTARIZED.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2004-06-08 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:25 Rev Time 0.50
Received By shill Date 2004-06-07 Time 16:51 Sent To  
Notes
2004-06-08 00:00:00DOORS & HARDWARE, INTERIOR ONLY
 **PROVISO**IN ACCORDANCE W/FBC AND
 APPROVED PLAN
 2. INTERIOR DOORS ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2004-06-04 Cont ID  
Sent By shill Date 2004-06-04 Time 17:11 Rev Time 2.00
Received By shill Date 2004-06-04 Time 17:11 Sent To  
Notes
2004-06-04 00:00:00REVISION, SHEETS A93 THROUGH A112A
 #5 & 6
 PROVISO - REVISE A101 (INCORRECT ELEV)

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status F Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-04 Time 14:01 Rev Time 0.50
Received By shill Date 2004-06-02 Time 16:38 Sent To  
Notes
2004-06-02 00:00:00****CORRECTIONS****
 OVERHEAD DOOR SHOPS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TEST REPORTS/PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR THE WINDOWS OR
 DOORS.PLEASE SUBMIT AT THIS TIME FOR
 REVIEW.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status F Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 15:36 Rev Time 0.50
Received By shill Date 2004-06-02 Time 15:36 Sent To  
Notes
2004-06-02 00:00:00****CORRECTIONS****
 DECORATIVE ALUMINUM GRILLE SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)REVISE AS PER ARCHITECT'S NOTE.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 15:26 Rev Time 0.50
Received By shill Date 2004-06-02 Time 15:26 Sent To  
Notes
2004-06-02 00:00:00SUBMITTALS
  
 MACHINE ROOM STAIR SHOPS
 LOUVERS AT TRANSVAULT SHOPS
 ROOF TOP ANCHOR SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-13 Time 09:31 Rev Time 0.50
Received By shill Date 2004-05-04 Time 16:15 Sent To  
Notes
2004-05-04 00:00:00CABLE & SHORING LETTERS FOR LEVEL 7
 POUR 1, LEVEL 8 POURS 1,4,5,6,7
  
 M.A. SUAREZ, PE
 CAPRI ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2004-05-04 Cont ID  
Sent By shill Date 2004-05-04 Time 14:40 Rev Time 1.00
Received By shill Date 2004-05-04 Time 14:40 Sent To  
Notes
2004-05-04 00:00:00REVISIONS DATED 3/25/04
 A30,A31, A82, S29A

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-05-04 Time 14:30 Rev Time 0.50
Received By shill Date 2004-04-23 Time 10:54 Sent To  
Notes
2004-04-23 00:00:00REVISION TO DRY IN PLAN, PROVISO -
 SUBJECT TO ARCHITECT'S APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2004-04-19 Cont ID  
Sent By alange Date 2004-04-22 Time 12:58 Rev Time 1.00
Received By shill Date 2004-04-19 Time 13:36 Sent To  
Notes
2004-04-19 00:00:00POOL DECK REVISION, SHEETS S18,S19,S21A
 DATED 12/31/03, A06, A62 DATED 3/31/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2004-04-19 Cont ID  
Sent By shill Date 2004-04-19 Time 13:14 Rev Time 0.50
Received By shill Date 2004-04-19 Time 13:14 Sent To  
Notes
2004-04-19 00:00:00SHORING/POST TENSION LETTERS FOR
 LEVEL 7, POURS 6 & 7, LEVEL 8,
 POURS 2 & 3
 PREPARED BY MA SUAREZ, PE
 AUBREY DUNHAM, PE
 CAPRI ENGINEERING
  
 LW CONCRETE SHOPS & PRODUCT DATA

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2004-04-15 Cont ID  
Sent By shill Date 2004-04-15 Time 11:24 Rev Time 2.50
Received By shill Date 2004-04-15 Time 11:24 Sent To  
Notes
2004-04-15 00:00:00STEEL TRUSS DRAWINGS PREPARED BY
 TS CHEHAL PE, 3/30/04
 PROVISO - ENGINEER IS TO SUBMIT A COPY
 COMPLIANT W/FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-06 Time 13:53 Rev Time 1.00
Received By shill Date 2004-04-05 Time 14:32 Sent To  
Notes
2004-04-05 00:00:00SUBMITTALS
 CONCRETE MIX 3000 PSI SIDEWINDER PUMP
 METAL SPECS DECKING
 RESHORE PLAN PREPARED BY AUBREY DURHAM
 PE DATED 2/23/04, 8TH FLOOR
 TRELLIS REV B
 SPA PERGOLA

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2004-04-05 Cont ID  
Sent By shill Date 2004-04-05 Time 11:58 Rev Time 0.50
Received By shill Date 2004-04-05 Time 11:58 Sent To  
Notes
2004-04-05 00:00:00SHORING PLAN PREPARED BY AUBREY DUNHAM
 PE DATED 3/22/04 ROOF LEVEL

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2004-04-05 Cont ID  
Sent By shill Date 2004-04-05 Time 10:34 Rev Time 2.00
Received By shill Date 2004-04-05 Time 10:34 Sent To  
Notes
2004-04-05 00:00:00****CORRECTIONS****
 REV LD1, GP1, L1-4
 SAMANTHA HILL, BUILDING PLANS EXAMINER
  
 1.)THE SEAL BEARS THE NAME OF WARREN
 MCCORMICK, BUT A STUART GREENBURG
 HAS SIGNED SOME OF THE DRAWINGS.
  
 2.)THE COMPANY OF WARREN E.
 MCCORMICK AND ASSOCIATES IS NULL AND
 VOID, SEE ATTACHED.
  
 3.)THE SEAL IS TO INCLUDE A DATE.
  
 4.)PLEASE REVIEW YOUR BOARD RULES AND
 FLORIDA STATUTES IN REGARDS TO ANY OTHER
 REQUIREMENTS FOR SEALS/TITLE BLOCKS.
  
 FS481, FAC61G10-12.009
  
 CC:DON NEELY
 COMPANY NAME REMOVED FROM PLAN -
 QUALIFIER APPLYING FOR COMPANY AUTH #
 W/DBPR
 APPROVED EXCEPT FOR GP1 - RESUBMIT
 WITH WARREN MCCORMICK'S SIGNATURE
 NEW PLAN BROUGHT IN FOR GP1

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-04-01 Time 13:00 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2004-03-17 00:00:00PROVISO:
  
 RE: THE DRY IN PLAN PHASES I AND II.
 WITH REGARDS TO WATERPROOFING BEING
 APPLIED TO THE INTERIOR FACE OF THE
 EXTERIOR WALL, HOW WILL MOISTURE THAT
 HAS PERMEATED THE EXTERIOR PORTION OF
 THE HOLLOW CMU'S AND IN THE CELLS, BE
 STOPPED AT THE FLOOR SLAB?PROVIDE A
 METHOD AT THE SITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status F Date 2004-03-16 Cont ID  
Sent By shill Date 2004-03-16 Time 09:19 Rev Time 2.00
Received By shill Date 2004-03-16 Time 09:19 Sent To  
Notes
2004-03-16 00:00:00****CORRECTIONS****
 REVISION (A30, A31, A82, S29A)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A82 DOES NOT INDICATE THE REVISION
 #4.CLOUD AND NUMBER ALL CHANGES.
 A30 DOES NOT SHOW CHANGES TO THE SHEET.
  
 2.)A30 AND A31 ROOFING NOTES REFER TO
 SOUTH FLORIDA BUILDING CODE.PLEASE
 REVISE TO REFLECT GOVERNING CODE.
  
 3.)THERE ARE FOURSTAIR #5S ON SHEET
 A31 (S43-D, S3-D, N5-K, N17-K).

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2004-03-15 Cont ID  
Sent By shill Date 2004-03-15 Time 13:12 Rev Time 0.50
Received By shill Date 2004-03-15 Time 13:12 Sent To E
Notes
2004-03-15 00:00:00REVISED SHEETS A.02, A11, A.33G DATED
 3/6/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2004-03-11 Cont ID  
Sent By shill Date 2004-03-11 Time 14:50 Rev Time 1.00
Received By shill Date 2004-03-11 Time 14:50 Sent To  
Notes
2004-03-11 00:00:00**ONLY ONE COPY SUBMITTED** CALLED
 CONTRACTOR
  
 SHORING/RESHORE INSPECTION LETTER
 PREPARED BY CAPRI ENGINEERING 2/11/04
 4TH ELEVATED DECK, POUR #1
  
 POST TENSION CABLES INSPECTION LETTER
 PREPARED BY MA SUAREZ PE 2/11/04
 4TH ELEVATED DECK, SECTION 1
  
 LETTER FROM CURRENT BUILDERS
  
 SAME LETTERS FOR THE FOLLOWING:
 5TH EL DECK, POUR #13/1/04
 6TH EL DECK, POUR #62/13/4
 6TH EL DECK, POUR #72/19/04
 4TH EL DECK, POUR #12/11/04
 7TH EL DECK, POUR #22/24/04
 7TH EL DECK, POUR #32/26/04
 W/INSPECTION BY AUBREY DUNHAM, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-10 Time 08:57 Rev Time 0.00
Received By shill Date 2004-03-08 Time 08:40 Sent To  
Notes
2004-03-08 00:00:00DRYIN PLAN GIVEN TO DON NEELY FOR REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 08:16 Rev Time 0.50
Received By shill Date 2004-03-05 Time 08:16 Sent To  
Notes
2004-03-05 00:00:00REVISION DATED 2/12/04 SHEET S42

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2004-03-04 Cont ID  
Sent By shill Date 2004-03-04 Time 14:11 Rev Time 0.50
Received By shill Date 2004-03-04 Time 14:11 Sent To  
Notes
2004-03-04 00:00:00****CORRECTIONS****
  
 STEEL TRUSS SUBMITTALS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ADDRESS FOR KEYMARK ENGINEERING
 IS NOT CONSISTENT WITH THE FBPE WEBSITE.
 IS THIS A SECOND OFFICE?
  
 2.)THE FOLLOWING INFORMATION IS
 REQUIRED TO BE ON EACH SHEET FAC61G15-
 23.002:
 AUTHORIZATION # FOR KEYSTONE
 PRINTED NAME & LIC # OF THE PERSON
 SEALING THE PLAN
  
 3.)A FULL SIGNATURE IS REQUIRED PER
 BUILDING OFFICIAL AND FBPE.ORIGINAL
 SIGNATURE REQUIRED, NOT PHOTOCOPY.
  
 4.)SHEETS SG LACK A TITLE BLOCK.
 ADDRESS.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-02-26 Cont ID  
Sent By shill Date 2004-02-26 Time 11:49 Rev Time 1.50
Received By shill Date 2004-02-26 Time 11:49 Sent To  
Notes
2004-02-26 00:00:00APPROVED SUBMITTALS
  
 STEEL SHOPS PREPARED BY ASA; PIT LADDER,
 CORNER GUARD ANGLES, LOUVERS, SEPARATOR
 BEAM, ELEVATOR SUMP, FPL SUMP COVER
  
 BALCONY HANDRAIL/GUARDRAIL SHOPS AND
 CALCS PREPARED BY THOMAS M. KELAHER, PE
 DATED 1/22/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-02-26 Time 10:34 Rev Time 1.50
Received By shill Date 2004-02-24 Time 14:58 Sent To E
Notes
2004-02-24 00:00:00****CORRECTIONS****
  
 REVISION DATED 1/20/4, A11, A33F,A02
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PRINTED NAME AND LICENSE NUMBER
 OF THE PERSON SEALING THE DOCUMENT IS
 TO BE ON EACH SHEET, FAC61G1-16.
  
 2.)A NOTE INDICATION A 4 HOUR WALL
 AROUND THE TRANS. VAULT (A.11) WAS
 REMOVED FROM THE PLAN.PLEASE
 ADDRESS.
  
 3.)THERE ARE NOTATIONS FOR SEVERAL
 REVISIONS (7, 8) WHICH APPARENTLY
 HAVE NOT BEEN SUBMITTED.PLEASE
 CLARIFY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-02-24 Cont ID  
Sent By shill Date 2004-02-24 Time 08:44 Rev Time 0.50
Received By shill Date 2004-02-24 Time 08:44 Sent To  
Notes
2004-02-24 00:00:00ALT SHORING PLAN PREPARED BY AUBREY
 DUNHAM, PE DATED 12/3/3(3RD FLOOR)

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-02-21 Cont ID  
Sent By shill Date 2004-02-21 Time 16:28 Rev Time 0.50
Received By shill Date 2004-02-21 Time 16:28 Sent To  
Notes
2004-02-21 00:00:00SUBMITTAL - CONCRETE MIX (RINKER)
 4500 AND 5000 PSI PUMP MIX

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2004-02-20 Cont ID  
Sent By shill Date 2004-02-20 Time 10:01 Rev Time 0.50
Received By shill Date 2004-02-20 Time 10:01 Sent To  
Notes
2004-02-20 00:00:00****CORRECTIONS****
  
 ALTERNATE SHORING PLAN PREPARED BY
 AUBREY DUNHAM, PE DATED 12/3/3
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A COMPLETE TITLE BLOCK IS REQUIRED
 ON EACH SHEET, FAC61G15-23.002.PLEASE
 READ AND INCLUDE ALL INFORMATION
 REQUIRED.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 16:41 Rev Time 0.50
Received By shill Date 2004-02-19 Time 12:50 Sent To  
Notes
2004-02-19 00:00:00PAINT SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2004-02-18 Cont ID  
Sent By shill Date 2004-02-18 Time 11:14 Rev Time 0.50
Received By shill Date 2004-02-18 Time 11:14 Sent To  
Notes
2004-02-18 00:00:00****CORRECTIONS****
  
 FOAM TRIM SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE EXTERIOR FOAM TRIM WILL NOT
 BE CONSIDERED UNDER ALTERNATE MATERIALS
 AND METHODS AS PER THE BUILDING
 OFFICIAL.FOR THIS PRODUCT TO BE USED
 IN BUILDINGS OVER THREE STORIES, OVER
 40' IN HEIGHT, OR IN THE FIRE DISTRICT
 AN APPLICATION MUST BE MADE TO THE
 CONSTRUCTION BOARD OF ADJUSTMENT AND
 APPEALS.THE BOARD CAN DENY THE REQUEST
 AND THE APPEAL IS TO OVERTURN THE
 BUILDING OFFICIAL AND FBC1404.1.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:05 Rev Time 1.00
Received By alange Date 2004-01-23 Time 12:53 Sent To  
Notes
2004-01-23 00:00:00FITNESS CENTER REVISION OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 14:30 Rev Time 0.50
Received By shill Date 2004-01-12 Time 14:30 Sent To  
Notes
2004-01-12 00:00:00*****CORRECTIONS*****
 BALCONY ALUMINUM HANDRAIL SHOP DRAWINGS
 AND CALUCLATIONS
 PREPARED BY T.KELAHER, PE 11/4/03
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HANDRAIL DESIGN (A.1, A.2, A.3)
 NOT IN ACCORDANCE WITH FBC1608.2.2,
 GUARDRAIL SYSTEM DESIGN AND
 CONSTRUCTION.
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-01-12 Cont ID  
Sent By shill Date 2004-01-12 Time 13:27 Rev Time 1.00
Received By shill Date 2004-01-12 Time 13:27 Sent To  
Notes
2004-01-12 00:00:00RESHORE PLAN DATED 10/20/03 (SEAL DATE
 12/16/03) BY AUBREY L. DUNHAM, PE
 2ND THROUGH 7TH RESHORE PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-12-30 Time 09:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-11-20 00:00:00CECO CONCRETE SHORING LETTERS DATED
 10/30/03, 11/3/03, 11/10/03 AND
 11/12/03, SIGNED AND SEALED BY AUBREY L
 DUNHAM, PE.
  
 THE WORDING IN THE LETTERS IMPLIES THAT
 THE SHORING INSPECTIONS WERE PERFORMED
 BY SOMEONE OTHER THAN MR. DUNHAM.FBC
 105.12 REQUIRES THAT SHORING INSPECTIONS
 BE PERFORMED BY FLORIDA LICENSED
 PROFESSIONAL ENGINEER.PLEASE PROVIDE
 DOCUMENTATION ATTESTING THAT THE
 INSPECTIONS WERE PERFORMED BY AN
 ENGINEER AS PROVIDED FOR IN THE FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2003-11-05 Cont ID  
Sent By hpiskura Date 2003-11-05 Time 12:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-11-05 00:00:00CECO CONCRETE SHORING PLANS 5TH THROUGH
 8TH FLOORS DATED 10/15/03.
  
 ENGINEERING DOCUMENTS SUBMITTED FOR
 PUBLIC RECORD REQUIRE AN EMBOSSED SEAL
 AND ORIGINAL SIGNATURE AND DATE.
 SEE FBC 104.2.2.
  
 PLEASE USE THE CURRENT CITY SUBMITTAL
 FORM.A COPY IS ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2003-09-09 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-09-09 00:00:00ASA ALUMINUM RAILING SHOP DRAWINGS.
 THE DRAWINGS DO NOT SHOW THE DESIGN
 LOADS USED.SEE FBC 1608.2.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2003-08-15 Cont ID  
Sent By csiegber Date 2003-09-03 Time 12:31 Rev Time 0.00
Received By hpiskura Date 2003-08-15 Time 08:47 Sent To FIRE
Notes
2003-08-15 00:00:00REVISIONS DATED 7/21/03, SHEETS A46-A50,
 A52, A53, AND A55-A61.
  
 ARCHITECT'S LETTER DATED 7/19/03 SIGNED
 BY G.J. ENCINOSA.
  
 THE ARCHITECT PROPOSES THE USE OF A
 COMBUSTIBLE ARCHITECTURAL TRIM
 PROHIBITTED BY FBC 1404.1.1 AND FBC
 F102.2.7 AS AMENDED BY THE CITY, BE
 APPROVED AS AN ALTERNATE MATERIAL IN
 ACCORDANCE WITH FBC103.7.
  
 AS JUSTIFICATION THE ARCHITECT CITES A
 2/02 LETTER FROM HUGHES ASSOC. INC
 SIGNED BY HAMID BAHADORI, PE.
  
 THE ARGUMENTS SET OUT IN THE HUGHES
 LETTER ARE DEEMED INVALID BY THIS PLANS
 EXAMINER FOR THE FOLLOWING REASONS:
  
 THE FIRST BULLETTED ITEM IN THE LETTER
 NOTES EPS HAVING A DENSITY OF 1.25 LB
 PER CUBIC FOOT.THE 1997 SBC CODE IN
 EFFECT THEN AS WELL AS THE CURRENT FBC
 IN SECTION 803.4 REQUIRES 20 LB MINIMUM.
  
 MR. BAHADORI CITES 803 WHICH IS
 INTERIOR FINISH AND MAKES NO RELATION
 TOEXTERIOR EXPOSURES, AND HE TOTALLY
 IGNORED THAT PART OF 803 THAT LIMITS
 INTERIOR FOAM TRIM TO WIDTHS OF 4" AND
 THICKNESS OF 1/2" IN DECLARING 6"
 THICKNESS OF FLAMMABLE MATERIAL
 ACCEPTABLE.
  
 THE OTHER BULLETED ITEMS IN THE BAHADORI
 LETTER REGARDING TESTS OF THE FUTURA
 COATINGS AND PAREX FINISH WOULD BE
 ACCEPTABLE IF USED IN ACCORDANCE WITH
 THEIR PROPRIETARY LISTINGS AND AS
 REGULATED BY THE FBC.
  
 AT THIS POINT WITH THOSE COATINGS IN
 MIND, LOOK AT THE DEFINITION OF
 NON-COMBUSTIBLE IN FBC 202.IT IS THIS
 COATING THAT GETS TESTED TO E84 AS
 DESCRIBED IN THE SECOND PART OF THE
 DEFINITION AND APPLIED TO A STRUCTURAL
 BASE, (THE FOAM), WHICH IS TESTED TO
 E136 TO QUALIFY AS NON-COMBUSTIBLE.
 NO TESTING IS PROVIDED FOR THE FOAM BASE
 THAT DEMONSTRATESNON COMBUSTIBLE.
  
 THE 1997 CODES, THE CURRENT FBC, AND THE
 2003 INTERNATIONAL CODE CONTAIN SIMILAR
 RESTRICTIONS AND PROHIBITIONS ON
 COMBUSTIBLE EXTERIOR ARCHITECTURAL
 TRIMS.
  
 CC: DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2003-08-07 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 10:54 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-08-07 00:00:00THE NOA'S AND PLANS FOR THE EXTERIOR
 WINDOWS AND DOORS REQUIRE A SEPARATE
 PERMIT APPLICATION AND FEES SINCE THEY
 WERE NOT INCLUDED WITH THE ORIGINAL
 PERMIT APPLICATION.
  
 THE INFORMATION HAS NOT BEEN REVIEWED FO
 R CODE COMPLIANCE AT THIS TIME.
  
 CC DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2003-07-31 Cont ID  
Sent By alange Date 2003-08-06 Time 15:12 Rev Time 0.00
Received By hpiskura Date 2003-07-31 Time 12:46 Sent To  
Notes
2003-07-31 00:00:00STEEL CONSTRUCTION SYSTEMS PRELIMINARY
 TRUSS ENGINEERING PACKAGE DATED 6/24/03
  
 THE DESIGN LOADINGS DECLARE FBC 1606.2
 AND 60'.SOME SHEETS DECLARE 130 MPH
 AND 30' ASCE 7-98.
  
 THIS BUILDING IS >60' TALL AND IS
 LOCATED IN AN 140 MPH ZONE THUS THE
 ABOVE IS INCORRECT.
  
 THE EOR SHOULD RE-ASSERT THE DESIGN
 CRITERIA FOR DELEGATED ENGINEERING
 RESPONSIBILITIES IN ACCORDANCE WITH
 RULE 61G15-30.005 OF THE FAC TO THE
 TRUSS DESIGNERS.
  
 CC: DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-30 Time 13:40 Rev Time 0.00
Received By hpiskura Date 2003-07-28 Time 11:52 Sent To  
Notes
2003-07-18 00:00:00TRANS #00257 MASONRY BLOCK
 RE: THE WINGERTER LABORATORIES, INC.
  
 WERE THE LOT OF MASONRY UNITS TO BE USED
 ON THIS SITE PRODUCED IN MIAMI IN 1998
 AS NOTED IN THE REPORT?
  
 THE FIRE RATING CITES COMPLIANCE WITH
 THE SFBC.THE 2001 FBC IS CURRENTLY IN
 EFFECT.IF ANY OF THE FIRE DESIGNS IN
 THE BUILDING INCORPORATE A UL DESIGN #
 THEN THE MANUFACTURER MUST BE LISTED BY
 UL.
  
 THE PAGES HAVING DONALD FLOOD, PE, WHEN
 SUBMITTED FOR PUBLIC RECORD MUST HAVE AN
 EMBOSSED SEAL AND AN ORIGINAL SIGNATURE
 AND DATE.
  
 CC DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-07-11 Time 09:05 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-06-27 00:00:00REVISIONS DATED 6/16/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-06-25 Time 13:37 Rev Time 0.00
Received By hpiskura Date 2003-05-09 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:52 Rev Time 0.00
Received By hpiskura Date 2003-04-09 Time 17:16 Sent To  
Notes
2003-04-10 00:00:00SHEET A46A.THE CALCULATIONS FOR FBC
 TABLE 600 FOR AREA OF PERMITTED WALL
 OPENINGS IS STILL INCORRECT.AS NOTED
 IN THE EARLIER CODE COMMENTS THE AREA
 IS DETERMINED ON A PER FLOOR BASIS.
  
 WALL AREAS IN THE SAME PLANE ON THE
 SAME FLOOR ARE CALCULATED AS A SINGLE
 UNIT.
  
 ON THE FIRST LEVEL AREAS SHOWN AS 40%
 ALLOWABLE EXCEED THAT IN TABLE 600.
 263 ALLOWED 450 SHOWN.
  
 SECOND LEVEL @ 40% ALLOWED 147 < 372
 SHOWN
  
 THIRD LEVEL @ 20% ALLOWED 430 < 850
 SHOWN.
  
 THIRD LEVEL @ 40% ALLOWED 147 < 328
 SHOWN.
  
 FOURTH LEVEL @ 40% ALLOWED 179 < 350
 SHOWN.
  
 FIFTH LEVEL @ 40% ALLOWED 147 < 372
 SHOWN.
  
 SIXTH LEVEL @ 20% ALLOWED 430 < 438
 SHOWN.
  
 SIXTH LEVEL @ 40% ALLOWED 147 < 353
 SHOWN.
  
 SEVENTH LEVEL @ 20% ALLOWED 276 < 386
 SHOWN.
  
 SEVENTH LEVEL @ 40% ALLOWED 147 < 372
 SHOWN.
  
 EIGHTH LEVEL @ 40% ALLOWED 161 < 250
 SHOWN.
  
 PLEASE REVISE AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-02-25 Cont ID  
Sent By hpiskura Date 2003-02-25 Time 13:39 Rev Time 0.00
Received By hpiskura Date 2003-02-25 Time 13:39 Sent To  
Notes
2003-02-25 00:00:00SHEET A46A IMPROPERLY CALCULATES THE
 RATIO OF WALL OPENINGS TO WALL AREA FOR
 DETERMINATION OF COMPLIANCE WITH FBC
 TABLE 600.
  
 THE WALL AREA IS MEASURED ON A PER
 FLOORBASIS.WIDTH IS DETEMINED ALONG
 THE WALL IN A SINGLE PLANE.
  
 THE HEIGHT IS MEASURED ON THE INTERIOR
 FROM THE FINISH FLOOR TO THE CEILING
 ABOVE.
  
 OPENINGS ARE DETERMINED BY THE ROUGH
 OPENING DIMENSIONS.
  
 EACH FLOOR IN TURN, ALONG THE SOUTH
 ELEVATION ON TANGLEWOOD CT. WHICH WALL
 IS SETBACK EIGHTEEN FEET FROM THE
 CENTERLINE DOES NOT COMPLY WITH FBC
 TABLE 600 AS TO THE PERCENTAGE OF
 OPENINGS ALLOWED. (20%)
  
 SHEET A88 SHOWS TWO WINDOWS OF
 DIFFERING SIZE DESIGNATED AS TYPE "M"
  
 THE DOOR SHOWN AS #46 FOR THE CLUB HOUSE
 IS REQUIRED TO BE FIRE RATED SINCE THE
 EXTERIOR WALL IS LESS THAN FIFTEEN FEET
 FROM THE PROPERTY LINE.SHOW THE FIRE
 DESIGN NUMBER FOR THE 3 HOUR RATED WALL
 ALSO.SEE FBC 705.1.1.2.
  
 SHEET S21.B, WHERE IS THE STRUCTURAL
 SHEATHING FOR THE CLUBHOUSE ROOF? HOW
 WILL IT BE ATTACHED?SEE FBC 104.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-01-14 Cont ID  
Sent By hpiskura Date 2003-01-10 Time 10:30 Rev Time 0.00
Received By hpiskura Date 2003-01-08 Time 16:49 Sent To  
Notes
2003-01-10 00:00:00SEE THE FOUNDATION PERMIT COMMENTS FOR
 1. THE THRESHOLD INSPECTION PLAN ISSUES
 NOT YET RESOLVED.
  
 2. THE PREVIOUS COMMENT RE: SITE
 ACCESSIBILITY ISSUES PERTAINS TO
 IMPROVEMENTS EFFECTING THE SIDEWALKS ON
 ALL FOUR SIDES, DROP OFF ZONES, TENANT
 SPACE ENTRANCES AND ANY OTHER PERTINENT
 INFORMATION, NOT JUST THE ARCADE.
  
 3. STAIR #1 DOES NOT COMPLY WITH
 CONDITION #1 OF FBC 1010, PARTICULARLY
 THE SECOND CLAUSE, "SUCH WAY BEING
 READILY VISIBLE AND IDENTIFIABLE FROM
 THE POINT OF EXIT DISCHARGE."
  
 4.
  
  
  
 5. AS PREVIOUSLY STATED, PLYWOOD ROOF
 SHEATHING IS NOT PERMITTED IN TYPE I
 CONSTRUCTION FOR USE AS A STRUCTURAL
 COMPONENT.THE ARCHITECT'S REFERENCE
 TOFBC 707.1 EXCEPTIONS, IS WITHOUT
 STANDING SINCE EXCEPTION 3 WHICH SPEAKS
 TO FRT CITES TABLE 600, WHICH IN TURN
 AT FOOTNOTE "E" APPLIES TO TWO STORY
 BUILDINGS, AND THE REFERENCE TO 609 IS
 APPLICABLE TO PARTITIONS.FURTHER, FRT
 IS NOT EQUIVALENT TO NON-COMBUSTIBLE.
 SEE FBC 202 DEFINITIONS.
  
 8. SEE THE FOUNDATION PERMIT COMMENTS
 REGARDING THE HC RAMP IN THE VALET
 LOBBY AREA.
  
 9.THE PREVIOUSLY NOTED METHOD FOR
 CALCULATING AREA FOR THE APPLICATION OF
 TABEL 600 REMAINS.THE "STATE"
 INTERPRETATION PROVIDED IS
 WITHOUTSTANDING. ALSO, THE REFERENCED
 SHEET A46A WAS NOT FOUND.
  
 10.MY PREVIOUS CHECKLIST REQUESTED
 FIRE RESISTANCE FOR THE EXTERIOR WALLS
 AS BEING IN THE CATEGORY OF BEARING
 WALLS.
 THE ARCHITECTS' RESPONSE IS THAT THEY
 ARE NON BEARING.PLEASE PROVIDE A
 SIGNED AND SEALED STATEMENT FROM THE
 STRUCTURAL ENGINEER OF RECORD THAT THEY
 ACT AS CURTAIN WALLS AND DO NOT SUPPORT
 OR TRANSMIT ANY GRAVITY LOADS.
  
 11. SHEET A62 SHOWS AN HC RAMP FOR THE
 RECREATION AREA BUT THE "HP" DRAWINGS
 REFERENCED IN THE ARCHITECT'S RESPONSE
 ARE NOT FOUND.
  
 12. PREVIOUSLY NOTED WAS THAT FOAM TRIM
 WAS NOT PERMITTED FOR EXTERIOR USE. IT
 WAS RESPONDED THAT THE TRIM IS
 "PRECAST"PRE CAST WHAT?CONCRETE?ARE
 THERE
 ANY DELEGATED DESIGN OR ATTACHMENT
 DETAILS?SEE FBC 104.2.
  
 13.THE REVISED FIRE RATED CEILING
 SECTIONS ON SHEET A64 IS LACKING SOME
 ATTACHMENT DETAILS.
  
 14.THE COMMENT REGARDING FIRE STOP
 SYSTEMS IS A CAVEAT.WHILE ALL OF THE
 SYSTEMS ARE UL LISTED, THERE ARE
 NUANCES INVOLVED WITH THEIR APPLICATION
 THAT MAY RESULT IN ADDITIONAL COST,
 TIME AND REWORK.
  
 15.PLEASE PROVIDE SIGNED, SEALED AND
 DATED SPECIFICATIONS.SEE FBC 104.2.
  
 16. DOOR 46 ON THE EAST SIDE OF THE
 FITNESS CENTER IS REQUIRED TO BE FIRE
 RATED AS IT IS LOCATED LESS THAN
 FIFTEEN FEET FROM A COMMON PROERTY LINE
 AND IS LOCATED IN AN EXTERIOR THREE
 HOUR RATED BEARING WALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-09-27 Cont ID  
Sent By hpiskura Date 2002-09-27 Time 12:44 Rev Time 0.00
Received By hpiskura Date 2002-09-23 Time 14:19 Sent To  
Notes
2002-09-27 00:00:00SECOND PLAN REVIEW, NOT A PERMIT
 APPLICATION.
  
 SEVERAL OF THE COMMENTS ON THE 8/16/02
 REVIEW HAVE NOT BEEN ADDRESSED.
  
 THRESHOLD BUILDING INFORMATION IS
 ABSENT SEE FBC 105.13.
  
 SHEET A.01 CITES A "FLORIDA CODE 2000
 EDITION".THE STATE INVOKES THE
 FLORIDA BUILDING CODE 2001. THERE ARE
 NUMEROUS REFERENCES THROUGHOUT THE
 PLANS TO THE S. FL. BUILDING CODE.THE
 PLANS AND SPECIFICATIONS SHOULD BE
 REVISED TO INCLUDE THE CODE IN EFFECT,
 FBC 2001, AND INSURE COMPLIANCE WITH
 SAME.
  
 SHOW THE SITE ACCESSIBILITY FOR THE
 HANDICAP.SEE FBC 11-4.1.2, CURB CUTS,
 MAIN ENTRANCE, COVERED ARCADE, TACTILE
 WARNING AREAS, ETC.
  
 STAIR #1 AS SHOWN ON SHEET A.01A DOES
 NOT COMPLY WITH FBC 1010, AS WAS NOTED
 ON THE PREVIOUS REVIEW.
  
 WALL SECTION C ON SHEET A56 IMPLIES
 THAT THE HIGHEST OCCUPIABLE FLOOR WILL
 EXCEED 75' ABOVE FIRE DEPARTMENT
 VEHICLE ACCESS AND THEREFORE MUST
 COMPLYWITH FBC 412.1.
  
 SEVERAL OF THE STAIRS ON SHEET A.21,
 (FIFTH LEVEL RECREATION AREA) SHOW
 HANDRAILS ON JUST ONE SIDE OF THE
 STAIRS.FBC 11-4.9.4 REQUIRES HANDRAILS
 ON BOTH SIDES.
  
 THE PLYWOOD ROOF SHEATHING SHOWN IN
 SECTION 1/A.30 AND ELSEWHERE, IS NOT
 ALLOWED IN TYPE I AND II CONSTRUCTION
 AS A STRUCTURAL COMPONENT.SEE FBC 603
  
 THE H.C. ACCESSIBLE RAMP SHOWN NEAR THE
 GALLERY/VALET AREA ON SHEET A.34 DOES
 NOT COMPLY WITH THE LANDING
 REQUIREMENTS OF FBC 11-4.8.4.
  
 SHEET A46A USES AN INCORRECT METHOD FOR
 CALCULATING TABLE 600. THE DISTANCE
 FROM FINISH FLOOR TO NEAREST CEILING IS
 THE HEIGHT TO BE USED ON A PER FLOOR
 BASIS.NOT THE ENTIRE BUILDING FACADE.
 PLEASE REVISE AS NECESSARY.
  
 NOTE #23 ON SHEET S-01 IMPLIES THE
 EXTERIOR MASONRY WALLS AS BEING
 BEARING, AND AS SUCH IS SUBJECT TO THE
 FIRE RESISTANCE REQUIREMENTS OF FBC T
 600 FOR BEARING WALLS AS A FUNCTION OF
 DISTANCE SEPARATION.
  
 SHOW THE EXTERIOR WALL FIRE RATINGS,
 INCLUDING THE FIRE DESIGN NUMBER, AND
 THE OPENING PROTECTIVE WHERE REQUIRED.
 INCLUDE THE FITNESS CENTER ON THE FIFTH
 LEVEL.
  
 SHOW THE HANDICAP ACCESSIBLE ROUTE
 THROUGH THE FIFTH LEVEL RECREATION AREA.
  
 SHEET A56 AND OTHERS SHOW THE USE OF
 FOAM TRIM.AS NOTED IN THE PREVIOUS
 COMMENTS, THIS IS PROHIBITTED BY FBC
 F102.2.7 AS AMENDED BY THE CITY, AS
 WELL AS FBC 1404.1.1.
  
 SHOW THE 1.5 HOUR FIRE RESISTANCE RATING
 METHOD FOR THE ROOF TRUSSES OF THE CLUB
 HOUSE IN ACCORDANCE WITH FBC TABLE 600.
  
 SHEET A65 CALLS OUT POWDER ACTUATED
 FASTENER WITH A MAX 1/4" PENETRATION TO
 SUPPORT THE SUSPENDED GYPSUM BOARD
 CEILING AND SIMILAR CONSTRUCTION.
 PROVIDE SPECIFIC PIN DIAMETER, SPACING
 AND ASSUMMED DESIGN LOADING TOGETHER
 WITH REFERENCE TESTING.SEE FBC 104.2.1
  
 SHEET A90 REFERENCES NFPA 5-2.1.5 FOR
 THE FIRE RATES DOORS.THERE IS NO
 5-2.1.5 IN THE 2000 EDITION OF NFPA
 101.FURTHER, FBC 705.1.3 INVOKES NFPA
 80, 1995 EDITION.ALSO, THE DOOR
 SCHEDULE DOES NOT CALL OUT THE REQUIRED
 FIRE RATED DOORS.
  
 SEVERAL OF THE FIRE STOP SYSTEMS CALLED
 ON SHEET LS-9 DO NOT HAVE THE T RATING
 REQUIRED BY FBC 705.5.1 & 705.6.1.2.
  
 THE MECHANICAL PLANS DO NOT SHOW THE
 MAKEUP AIR FOR THE GARAGE VENTILATION
 SYSTEM.WHAT LEVEL OF NOISE WILL THE
 EIGHT FANS PRODUCE?
  
 HOW WILL THE 7' HEIGHT REQUIRED BY FBC
 411.2.2 BE MAINTAINED UNDER THE 30"
 DEEP DUCT?
  
 THE ROOF OVERHANGS THE PROPERTY LINE TO
 THE EAST NEAR GRID LINES N AND N20 ON
 SHEET A 32. (STAIR #3)
  
 PROVIDE CONSTRUCTION DETAILS FOR THE
 "COVERED ARCADE" ALONG HIBISCUS ST.
 INCLUDE THE FIRE PROTECTION INFORMATION.
  
  
 SOME OF THE EXTERIOR STAIR HANDRAILS
 EXTEND INTO THE PUBLIC RIGHT OF WAY ON
 THE TANGLEWOOD CT SIDE (SOUTH)SEE FBC
 3206.1.
  
 THE SPECIFICATIONS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE SPECIALTY
 ENGINEERS WHEN SUBMITTED FOR PUBLIC
 RECORD.SEE FBC 104.2.2.
  
 PROVIDE A COPY OF THE SOIL REPORT
 MENTIONED IN THE SPECIFICATIONS AS
 APPENDIX A AND ON THE STRUCTURAL PLANS
 IN NOTE 10, OF THE GENERAL NOTES.
  
 SHEET S.O2 DEPICTS A TERRACE IN THE
 PUBLIC R.O.W.
  
 THE STRUCTURAL DETAILS FOR THE CLUBHOUSE
 FITNESS CENTER AND SWIMMING POOL ARE
 NOT READILY DISCERNIBLE ON THE
 STRUCTURALPLANS.
  
 SHOW THE DESIGN INFORMATION FOR THE
 VARIOUS RAILINGS TO BE USED THROUGHOUT
 THE BUILDING.SEE FBC 1608.2.
  
 SHOW HOW FBC 1606.1.4 WILL BE COMPLIED
 WITH.
  
 PROVIDE THE INFORMATION REQUIRED BY FBC
 160.1.7 INCLUDING THE COMPONENT AND
 CLADDING PRESSURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-16 Cont ID  
Sent By hpiskura Date 2002-08-16 Time 14:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-08-16 00:00:00PLAN REVIEW ONLY, NOT A PERMIT
 APPLICATION.NO SPECIFICATONS WERE
 PROVIDED
  
 AT TIME OF PERMIT APPLICATION A RECENT
 PROPERTY SURVEY WILL BE REQUIRED.SHOW
 THE BUILDING ELEVAION MEASURED FROM THE
 LOWEST POINT OF FIRE DEPARTMENT VEHICLE
 ACCESS, (STREET), TO HIGHEST OCCUPIABLE
 FLOOR.IF MORE THAN 75' COMPLY WITH FBC
 412.
  
 THE MINIMUM CONSTRUCTION TYPE IS TYPE I
 FIRE SPRINKLERED.R2 OCCUPANCY.THE
 BUILDING WILL BE LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND MUST
 COMPLT WITH APPEDIX OF THE FBC AS
 AMENDED BY THE CITY OFWEST PALM BEACH.
  
 THIS WILL BE A THRESHOLD BUILDING AND
 WILL REQUIRE A THRESHOLD INSPECTION
 PLAN AND A THRESHOLD INSPECTOR.SEE
 FBC 105.13.
  
 SHEETS A65 AND A67 DEPICT SUSPENDED
 GYPSUM BOARD CEILINGS AND SOFFIT
 FRAMING.INCLUDE SPECIFIC CONNECTIONS
 IN THE DESIGN INCLUDING ATTACHMENT TO
 THE STRUCTURE ABOVE.
  
 THE PORTION OF THE BUILDING ON THE SOUTH
 ELEVATION, (TANGLEWOOD CT.) DOES NOT
 COMPLY WITH FBC TABLED 600 MEASURED 18'
 TO THE STREET CENTERLINE AS TO WALL
 FIRE RATING, (2HRS) AND ALLOWABLE
 PERCENTAGE OF EXTERIOR WALL OPENINGS.
 PLANS INDICATE 334 SF OF 300 SF
 ALLOWABLE AT THE FIRST FLOOR.THE UPPER
 FLOORS EXCEED THE ALLOWABLE BY A
 GREATER PERCENTAGE.
  
 THE FITNESS CENTER, FIFTH LEVEL, ON THE
 EAST ELEVATION INDICATES A TWELVE FEET
 SETBACK FROM AN INTERIOR PROPERTY LINE.
 THEREFORE THE EXTERIOR BEARING WALL IS
 REQUIRED TO BE 4 HR FIRE RATED AND IS
 LIMITED TO 20% PROTECTED OPENINGS.SEE
 FBC T-600 AND FBC 705.1.1.2.
  
 THE PARKING GARAGE WILL BE ENCLOSED AS
 PROVIDED FOR IN FBC 411.4.INDICATE
 THE WALLS, WHERE APPLICABLE, WILL
 COMPLY WITH FBC 411.2.3. (VEHICLE
 IMPACT RESISTANCE)
  
 SHEET LS-1 SHOWS INGRESS/EGESS FROM THE
 GARAGE ON THE EAST SIDE TO BE PARTIALLY
 ON THE ADJACENT PROPERTY.HOW IS THIS
 RESOLVED?
  
 SHOW THE VENTILATION REQUIRED BY FBC
 411.4.2.
  
 DETAIL K/A87, AND OTHERS, SHOW THE USE
 OF PLYWOOD FOR A STRUCTURAL COMPONENT
 WHICH IS PROHIBITTED IN TYPE I
 CONSTRUCTION
 SEE FBC 603.
  
 SECTION G A.86, AND OTHERS SHOW A 3/4"
 DEEP RECESS FOR THE EXTERIOR MASONRY
 WALLS.FBC 2111.1.9 AS AMENDED BY THE
 CITY REQUIRES 1 1/2".
  
 PARTITION TYPE 21 ON SHEET A92 DOES NOT
 AGREE WITH UL465 ASSEMBLY.
  
 THE SHAFT DETAIL ON LS-8 IS NOT
 PRACTICAL FOR UL505 DESIGN.
  
 PARTITION TYPE 7, UL907 REQUIRES
 ADDITIONAL DETAILS SINCE THE BLOCK IS A
 PROPRIETARY ONE.SAME FOR PARTITION
 TYPES 4, 4A & 4B.
  
 THE NOTE "FIRE SAFING AS REQUIRED" ON
 SHEET A92 AND ELSEWHERE, IS NOT A
 SUBSTITUTE FOR SPECIFIC DESIGN MATERIAL
 INFORMATION SEE FBC 104.2.1.
  
 THE EXTERIOR WALLS DO NOT INDICATE THEIR
 RESPECTIVE FIRE RATINGS IN ACCORDANCE
 WITH FBC T 600 FOR TYPE I CONSTRUCTION.
 INCLUDE THE FIRE DESIGN NUMBERS.
  
 WHERE IN THE BUILDING DO THE CORRIDOR
 SUPPLY RISERS DEPICTED ON SHEET A/C 200
 OCCUR?CONSTRUCTION DETAIL?
  
 STAIR #1 DOES NOT COMPLY WITH FBC
 1010.3EXCEPTION 1 AS DOES STAIR #3.
 FURTHER, ONLY 50% OF THE EXITS MAY USE
 THE EXCEPTION, NOT 2/3 (66%).
  
 SHOW THE METHODS OF PROTECTION OF
 PENTRATION OF FIRE RATED ASSEMBLIES.
 SEE FBC 705.4.
  
 SHOW HOW FBC 705.6 WILL BE COMPLIED WITH
  
 THE VARIOUS FOAM TRIM ITEMS SHOWN FOR
 USE ON THE EXTERIOR WALL MUST COMPLY
 WITH FBC 1404.1.1 AND (FBC F102.2.7
 AMENDMENT)NON COMBUSTIBLE MATERIAL.
  
 NOTE#21 ON SHEET S-01 SPEAKS TO
 PILINGS BUT THE PLANS DO NOT AGREE.
 PLEASE CLARIFY.
  
 THE NOTES ON S-O1 FOR THE POST TENSION
 #8 AND POST TENSION CONCRETE SLAB #1
 CONFLICT WITH EACH OTHER.PLEASE
 CLARIFY THE DESIGN INTENT.
  
 THE SECTIONS ON SHEET S34 ARE NOT
 NUMBERED PROPERLY.
  
 SHOW THE BUILDING ENVELOPE PRESSURES.
  
 SHOW A DETAIL FOR THE EMERGENCY OVERFLOW
 SCUPPER.SEE FBC 1511.6.1.4.3.
  
 FA SHEETS 9, 9.1, 9.2, AND 10, CALLED
 OUT THE TITLE SHEET AO ARE MISSING.
  
 FP SHEETS 120, 119, 118, 116, 8.0 ARE
 MISSING.SEE NFPA 13-99 CHAPTER 8 FOR
 THE REQUIRED FIRE SPRINKLER INFORMATION.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.
  
 PLEASE SEPARATE THE PLANS INTO SMALLER
 SECTIONS, IE BIND THE MEP SEPARATELY.
 THEY ARE OVERLY HEAVY AND UNWIELDLY IN
 THEIR PRESENT STATE.

Review Stop E ELECTRICAL
Rev No 20 Status F Date 2005-10-03 Cont ID  
Sent By jleahy Date 2005-10-03 Time 07:24 Rev Time 2.30
Received By jleahy Date 2005-10-03 Time 07:23 Sent To  
Notes
2005-10-03 00:00:00PAGES E.13.0, E.13.1, E.13.2 NEW
 TRANSFORMERS ON ROOF NOT SHOWN.
  
 PANEL SCHEDULES ON PAGES E.208.1,
 E.209.9, E.209.1, E.209.2 STILL SHOW
 CONDUIT SIZES.
  
 PANEL SCHEDULES ON PAGE E.209 SHOW
 CIRCUITS 14A, AND 14B AS A TWO (2) POLE
 BREAKER SHOULD BE 12A, 12B.
  
 QUESTIONS
  
 JAKE 644-7291

Review Stop E ELECTRICAL
Rev No 19 Status P Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 20:26 Rev Time 0.30
Received By dpalmer Date 2005-08-15 Time 20:26 Sent To  
Notes
2005-08-15 00:00:00REV FOR SPEC/CONTROL BOOKS.
 REDLINED 215.2, 277/480V "B"
 PHASE,"PURPLE".

Review Stop E ELECTRICAL
Rev No 18 Status F Date 2005-07-29 Cont ID  
Sent By jleahy Date 2005-07-29 Time 07:15 Rev Time 6.30
Received By jleahy Date 2005-07-29 Time 07:15 Sent To FIRE
Notes
2005-07-29 00:00:00NEED TO CORRELATE DRAWINGS AND PANEL
 SCHEDULES CIRCUITS SHOWN ON LAYOUTS OF
 ROOMS NOT SHOWN ON PANEL SCHEDULES.
  
 PAGES 13.0,13.1,13.2 DO NOT SHOW ADDED
 TRANSFORMERS ON A/C UP ON ROOF.
  
 PAGE 109 UNITS B1,B1.1,B1.2,B1.3,B1.4,
 B1.5 ADDED OUTLETS ON KITCHEN COUNTER
 MISSING FROM DRAWINGS.
  
 PAGE 208NOTE 20 AND ALL PANEL
 SCHEDULES SHOW RACEWAYS NOT MC CABLES
 PLEASE CHANGE NOTE AND PANEL SCHEDULES
 TO SHOW WHAT IS INSTALLED.
  
 PAGE 207 NEED TO SHOW WIRE SIZES TO THE
 FIRE PUMP FROM CONTROLER. NOT SHOWN.
  
 I DO NOT HAVE THE TIME TO LIST ALL
 PROBLEMS THAT WE HAVE PLEASE LOOK AT THE
 UNIT DRAWINGS AND THE PANEL SCHEDULES
 THAT IS WHERE MOST OF THE PROBLEMS ARE!!

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2005-06-28 Cont ID  
Sent By jleahy Date 2005-06-28 Time 09:56 Rev Time 0.30
Received By jleahy Date 2005-06-28 Time 09:56 Sent To  
Notes
2005-06-28 00:00:00THIS REVISION WAS FOR ONLY THE STEAM
 GENERATORJL
  
 PAGE SE-209.2 & E-207JL

Review Stop E ELECTRICAL
Rev No 16 Status F Date 2005-06-28 Cont ID  
Sent By jleahy Date 2005-06-28 Time 09:56 Rev Time 1.00
Received By jleahy Date 2005-06-28 Time 09:55 Sent To  
Notes
2005-06-28 00:00:00PLANS SUBMITTED HAVE NO ELECTRIC SHOWN
 PAGE AC-120JL

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2005-03-16 Cont ID  
Sent By dpalmer Date 2005-03-16 Time 16:52 Rev Time 4.00
Received By dpalmer Date 2005-03-16 Time 16:52 Sent To  
Notes
2005-03-16 00:00:00LTR FROM POWER DESIGN FOR MANUAL
 TRANSFER OF GENERATOR TO POWER ONE ELEV.
  
 OK, PER FIRE DEPT.
 REDLINED CLEARENCES PER 110.26

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 08:40 Rev Time 2.00
Received By dpalmer Date 2004-12-29 Time 08:40 Sent To  
Notes
2004-12-29 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED DATED
 7/14/04
 SOME OF THESE NOTES STILL NEED TO BE
 ADDRESSED.
 PLEASE SUBMIT OTHER REVISED SHEETS FROM
 THE MOST CURRENT AND LATEST PLANS WHICH
 HAD COMMENTS FROM 7/14/04
 A REVIEW FOR CODE COMPLIANCE CAN NOT BE
 DONE UNTIL WE ARE ABLE TO VERIFY
 FEEDS/OCP/PANELS ETC.
 PLEASE PROVIDE REVISED PANEL SCHEDULES
 TO CORRELATE WITH RISER DIAGRAM.
  
 2)NOTE: PLEASE SEE NOTE#3 FROM 7/14/04.
 PLEASE SEE MAIN #6 ON RISER.
  
 3)NOTE: PLEASE SEE FEEDER NOTES: MANY
 HAVE CHANGED TO ALUM, SOME STILL SHOWN
 AS COPPER ON RISER. IT IS OUR
 UNDERSTANDING, THESE WERE ALL CHANGED TO
 ALUM DUE TO VE.?
  
 4)NOTE: PLEASE VERIFY LOAD SHEDDING
 UNIT. DOES THIS SHED THE LOAD FOR LIFT
 STATION?
  
  
 ** PLEASE ALSO NOTE: IT HAS NEVER BEEN
 SETTLED SINCE OUR LAST MEETING WHAT
 LOADS WILL BE ON EM POWER.
 THIS NEEDS TO BE SETTLED BY ALL PARTIES
 BEFORE IT BECOMES A FINAL/CO ISSUE.
  
  
 PLEASE SEE ANY POSSIBLE FIRE REVIEW
 COMMENTS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 13 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2004-11-15 Time 17:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 17:08 Rev Time 0.50
Received By dpalmer Date 2004-09-21 Time 16:58 Sent To  
Notes
2004-09-21 00:00:00REVISION FOR FIRST FLR LOBBY LIGHTING
 REVISIONS TO HOUSE PANELS/LOADS.
 6.3 AND 209.2 ONLY

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2004-07-21 Cont ID  
Sent By dpalmer Date 2004-07-21 Time 15:16 Rev Time 3.00
Received By dpalmer Date 2004-07-21 Time 13:50 Sent To  
Notes
2004-07-21 00:00:00REV'S TO UNITS
 REV'S FOR SERV/CONDUCTORS/PANEL SCHEDULE
 -S ETC.,
  
 REDLINED 206, ALUM GRND SHOWN.
 STAMPED E-SHEETS.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2004-06-08 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 12:20 Rev Time 6.00
Received By dpalmer Date 2004-06-08 Time 16:35 Sent To  
Notes
2004-06-08 00:00:00************* UNSAT ******************
  
 REVISION FOR HOUSE PANELS/ RISER/
 GENERATOR/ LOAD CALCS ETC.
  
 1)NOTE: PLEASE CORRELATE ALL PANELS ON
 PANEL SCHEDULES AND HOW THEY ARE
 LABELED
 ON OTHER PANEL SCHEDULES AND PLANS.
 PLEASE SEE ONE SET HAS SOME OF THESE
 ITEMS REDLINED.
  
 2)NOTE: PLEASE SEE SOME PANEL
 SCHEDULES/
 RISER/FEEDERS ETC HAS HAD CONDUCTOR
 SIZES CHANGE DUE TO VE ISSUES. PLEASE
 SEE SOME CONDUCTOR SIZES WERE INCREASED
 FOR ALUM/ 310.16 YET SOME
 CONDUCTOR/FEED
 -ERS SIZES WERE NOT CHANGED. IF THESE
 ARE TO REMAIN COPPER AS ORIG THEN THIS
 WOULD BE OK, BUT SEEMS MOST ALL FEEDERS
 HAVE BEEN CHANGED TO ALUM?
 PLEASE CLARIFY IF THIS IS INDEED THE
 CASE. IF SO, PLEASE ADJUST SOME
 FEEDERS.
  
 3)NOTE: PLEASE CORRELATE E-206 AND 207
 FOR DIST SECTION AND MCB'S SHOWN FOR
 OCP.
  
 4)NOTE: PLEASE CLARIFY FEED FOR SECTION
 SE-1, SHOWS 400A ON RM LAYOUT PLANS AND
 RISER, HOWEVER SE-1/2? SHOWS 800A. IS
 THIS THE SAME?
  
 5)NOTE: PLEASE SEE RISER SHOWS FEEDERS
 TO PKA AS #1 ALUM YET OCP ON PANEL
 SCHEDULE IS SHOWN AT 125A'S. PLEASE
 VERIFY. PLEASE SEE PREVIOUS NOTES FOR
 THIS ALSO ON THIS REVIEW.
  
 PLEASE SEE ONE SET OF THESE PLANS HAVE
 SOME OF THESE ITEMS REDLINED
  
 PLEASE CLARIFY GENERATOR SITUATION, AT
 LAST MEETING IT WAS MENTIONED THE FIRE
 PUMP AND ONE ELEVATOR WAS GOING TO
 REMAIN ON EM POWER? THIS REVISION DOES
 NOT SUPPORT THIS.
 PLEASE SUBMIT UPDATED PLANS DUE TO
 CHANGE IN OCCUPANCY AND IF EM POWER
 WILL
 BE PROVIDED FOR MORE THAN LIFT STATION.
 PLEASE ALSO SEE FIRE PLAN REVIEW FOR
 ANY
 POSSIBLE COMMENTS FOR THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2004-06-08 Cont ID  
Sent By dpalmer Date 2004-06-08 Time 15:10 Rev Time 2.00
Received By dpalmer Date 2004-06-08 Time 15:10 Sent To  
Notes
2004-06-08 00:00:00********** UNSAT ****************
  
 REVIEW FOR APT LAYOUTS ONLY.
  
 1)NOTE: PLEASE SEE NOTES FOR SD'S ON
 EACH SHEET HAS NOT BEEN UPDATED.
  
 SD'S ARE REQUIRED TO A MIN OF 3' FROM
 SUPPLY AIR GRILLES AND 5' FROM RETURNS.
 PLEASE ALSO SEE NFPA-72 8-1.4.2.1
 WHICH REQUIRES SD'S TO BE 3' FROM BATH(S
 DOORS/ KITCHEN DOORS AND 20' FROM
 COOKING APPLIANCES W/ EXCEPTIONS. ETC
 PLEASE SEE NFPA AND NOTE NFPA ART. ON
 PLANS FOR INSTALLATION.
  
 2)NOTE: PLEASE SEE UNIT/ LAYOUTS,
 SOME SHOW SMALL APPLIANCE CIRCUITS
 IN DEN AREA. THESE CAN BE IN DINING RM
 AREA BUT NOT DEN.
 210.52-2-B
  
 3)NOTE: PLEASE SEE SOME UNITS ARE
 CIRCUITING FOR SD'S.
 ALSO MISSING SOME CIRCUITING FOR SOME
 NEW ITEMS.
 PLEASE GOING OVER CIRCUITING FOR ALL
 UNITS.
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OF WALL SPACE IN SOME
 UNITS.
 PLEASE SEE ONE SET HAS SOME REDLINED/
 CIRCILED FOR THIS. E-117/118 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:48 Rev Time 0.33
Received By btrobaug Date 2004-03-22 Time 11:58 Sent To B
Notes
2004-03-22 00:00:00 
 THIS REV FOR 4HR VAULT WALL,SH A.33G.
 WRT.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2004-03-04 Cont ID  
Sent By shill Date 2004-03-15 Time 13:12 Rev Time 1.50
Received By dpalmer Date 2004-03-04 Time 06:15 Sent To  
Notes
2004-03-04 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 ABOUT EM POWER ETC.
 PLEASE SEE PLANS/RISER STILL INDICATE
 EM GENERATOR.
  
 2)NOTE: NO ALUM EQUIPMENT GRNDS/ BONDING
 IS PERMITTED UNDER LOCAL AMENDMENTS.
 310.2(B)2
  
 3)NOTE: PLEASE CORRELATE RISER.
 FIRE PUMP CONT SHOWN WITH ATS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-02-24 Cont ID  
Sent By dpalmer Date 2004-02-24 Time 15:11 Rev Time 0.50
Received By dpalmer Date 2004-02-24 Time 15:11 Sent To  
Notes
2004-02-24 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE BLDG REV FOR VAULT
 / ELECTRICAL ROOMS. PLEASE SEE 450.42
 FOR A MIN OF 3HR REATED WALLS.
 NO PIPING OF ANYKIND PERMITTED WITHIN
 3HR RATED WALLS.
 PLEASE PROVIDE INFORMATION ON STUCTURAL
 AND ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-02-18 Cont ID  
Sent By shill Date 2004-02-24 Time 15:16 Rev Time 3.00
Received By dpalmer Date 2004-02-18 Time 06:13 Sent To  
Notes
2004-02-18 00:00:00************ UNSAT *************
  
 1)NOTE: SHEETS E-117,118,119 HAD NOTES
 CORRECTED FOR SD' REQUIREMENTS,HOWEVER
 OTHER SHEETS REMAIN UNCHANGED?
  
 2)NOTE: PLEASE SEE THERE ARE MANY OTHER
 SHEETS LABELED IN TITLE BLOCK AREA TO
 HAVE A VE REV AND DATED, HOWEVER PLANS
 ARE REQ'D TO BE IDENTIFIED WITH CLOUDS/
 TRIANGLESTO INDICATE CHANGE.
  
 3)NOTE: PLEASE CLARIFY: PLANS INDICATE
 ALL EM/EXT LTS STILL GOING TO EMERGENCY
 CIRCUITS. AS PER CONVERSATION WITH
 ENGINEER, THE GENERATOR/EMERGENCY BACK
 -UP SYSTEM WAS BEING PROPOSED FOR REMOVE
 -L. PLEASE NOTE: I HAVE SPOKEN TO ASST
 FIRE MARSHAL MIKE CARSILLO, AND THAT
 CONCLUSION HAS NOT YET BEEN FINALED BY
 THE FIRE MARSHALL'S OFFICE.
 IF NO BACK SYSTEM IS GOING TO BE PERMITT
 -ED, PLEASE ADJUST PLANS.
  
 4)NOTE:
 PLEASE ALSO INCLUDE ADDRESS OF JOB IN
 TITLE BLOCK. FAC 61G1-16.004
 THIS COMMENT IS FOR ALL TRADES WEATHER
 OR NOT COMMENT IS MADE.
 THIS WAS ALSO REQ'D AT THE TIME OF ORIG
 PERMIT,HOWEVER IT WAS NOT KNOWN TO THIS
 OFFICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 11:29 Rev Time 4.00
Received By dpalmer Date 2003-11-04 Time 15:40 Sent To  
Notes
2003-11-05 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SD'S AHVE BEEN
 REMOVED FROM INSIDE EACH SLEPPING RM OF
 UNITS??? PLEASE SEE THAT SD'S ARE REQ'D
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1 AND FBC 905.2
 ETC.
  
 2)NOTE: PLEASE SEE MISSIG RECEPTS FOR
 2' OF WALL SPACE .E117,E118, E-119(STUD-
 -IO 4).PLEASE SEE THAT ONE OF THE SETS
 HAVE SOME REDLINED ON THESE PAGES.
  
 3)NOTE: PLEASE SEE NOTE ON ALL PAGES FOR
 UNITS: NOTE MENTIONS, SD TO BE 3' AWAY
 FROM ALL A/C EQUIPMENT. PLEASE SEE THAT
 NFPA-72 STIPULATES TO BE 3'FROM "SUPPLY'
 REGISTERS. PLEASE SEE THAT SD'S ARE TO
 BE 5' FROM RETURN AIR. PLEASE SEE SPECS
 ON SD'S BEING INSTALLED.
  
 4)NOTE: PLEASE SHOW/IDENTIFY ALL REV'S
 BY CLOUDS ON PLANS. PLEASE SEE E201,202
 E203.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-02 Time 07:44 Rev Time 3.00
Received By dpalmer Date 2003-01-02 Time 07:14 Sent To  
Notes
2003-01-02 00:00:00PLEASE SEE FIRE REVIEW COMMENTS THAT
 MAY AFFECT ELECTRICAL PLANS.
 PLEASE NOTE ELECTRICAL PLANS JUST NEED
 TO BE STAMPED BY ELEC AFTER FIRE REVIEWS
 OK.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-10-09 Cont ID  
Sent By dpalmer Date 2002-10-09 Time 05:37 Rev Time 6.00
Received By dpalmer Date 2002-10-09 Time 05:28 Sent To  
Notes
2002-10-09 00:00:00***************** UNSAT **************
  
 1)NOTE: A FIXTURE SCHEDULE IS NOW
 SUBMITTED. PLEASE NOTE THAT THERE ARE
 FIXTURES IN HALLS ETC THAT NEED TO BE
 LABLED TO CORRELATE WITH SUBMITTED
 FIXTURE SCHEDULE. PLEASE NOTE SOME ARE
 SHOWN WITH WHAT APPEARS TO BE A CIRCUIT
 # AND DO NOT SEEM TO CORRELATE WITH THE
 PANEL SCHEDULE?
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 EMERGENCY LIGHTING CONCERNS.
 PLEASE NOTE 700-12 FOR BRANCH CIRCUITING
 PLEASE NOTE THERE ARE STILL NOTES ON
 E-11.0.11.1,11.2 THAT SHOW CIRCUIT #`S
 THAT DO NOT CORRELATE WITH PLAN LAYOUT?
  
 2)NOTE: PLEASE CLARIFY PAGE #`S CHANGING
 ? PLEASE CLARIFY IF WHAT USED TO BE
 16IS NOW 13?? ETC.
 PLEASE NOTE THAT THE REVISIONS ARE
 SHOWN/NOTED ON SIDE BUT NO TRIANLGES
 ARE SHOWN ON ANY OF THE PAGES THAT
 CHANGES WERE MADE?
  
 3)NOTE: IT IS NOTED THAT GFI`S WERE
 ADDED TO SOME PENINSULARS. PLEASE NOTE
 SOME UNITS ARE SHOWING MORETHAN ONE
 PENINSULAR?210-52C-3. IF 6" DOWN THEN
 COUNTERSPACE SHALL NOT EXCEED 6" OVER-
 HANG?
  
 4)NOTE: PLEASE NOTE SOME OUTLETS ARE
 STILL NOT BEING SHOWN WITHIN 6' OF DOOR?
 210-52 PLEASE CALL FOR THIS,CAN BE DONE
 AT FEILD INSPECTION, BUT SHOULD BE
 NOTED ON PLANS.
  
 5)NOTE: PLEASE CLARIFY RISER ONE-201
 DOES NOT SEEM TO CORRELATE W/ E-207?
 NOTE 8 BOTH RISERS? NOTE 8 MENTIONS
 1000A BUS TO WHICH 1000A DISC ON 207?
  
  
 6)NOTE; PLEASE NOTE PLANS/RISER STILL
 MISSING SOME EQUIPMENT GROUNDS.
 SIZE PER 250-122
  
  
  
  
 7)NOTE: PLEASE CLARIFY HOW FEED FROM
 FPL COMES DIRECTLY INTO EM MAIN, INSTEAD
 OF TRANSFER SWITCH?ON RISER DIAGRAM
 ON E-207?
  
 8)NOTE: PLEASE SEE E206, CLARIFY MAIN
 1 OF 6 SHOWN IN THE MIDDLE OF GENERATOR
 ROOM.???
  
 9)NOTE; PLEASE NOTE INFORMATION FOR
 OCP FOR FIR PUMP NOT SHOWN. PLEASE SEE
 695-4-B-1
  
 10)NOTE: PLEASE NOTE AICRATINGS ARE
 STILL MISSING ON SOME. 110-9/215-5
  
 11)NOTE: PLEASE SEE "S" PANELS FOR THE
 SAME COMMENT STILL STANDS FOR 50A OCP
 ON #14 AWG. CORRECTED ON ONE ONLY.
  
 12)NOTE: PLEASE NOTE STILL MISSING
 EQUIPMENT GROUNDING ON ONE-LINE.?
 SIZE PER 250-122
  
 13)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING FOR FEEDS TO UNITS.IT IS NOTED
 THAT FEEDERS ARE SHOWN ON E208.1
 CLARIFY EQUIP.GRND.
  
 14)NOTE: PLEASE SHOW WHERE ON ONE-LINE
 DOES IT SHOW FEED TO MC, SE 1/2 IS
 SHOWN.?
  
 15)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-21 Cont ID  
Sent By dpalmer Date 2002-08-21 Time 13:30 Rev Time 12.00
Received By dpalmer Date 2002-08-19 Time 14.00 Sent To  
Notes
2002-08-21 00:00:00***************** UNSAT *************
  
 PLEASE NOTE THAT PLANS ARE NOT COMPLETE
 ENOUGH FOR FULL REVIEW AND THERE MAY BE
 OTHER COMMENTS TO FOLLOW.
  
 1)NOTE: PLEASE NOTE THAT NO LIGHTING
 FIXTURE SCHEDULE WAS SUBMITTED FOR
 REVIEW AND TO CORRELATE WITH LIGHTING
 PLANS SUBMITTED.
  
 2)NOTE: PLEASE CLARIFY REQ`MENTS FOR
 700-16 FOR ELEVATOR RMS AND ANY OTHER
 AREAS THAT ONLY CONTAIN ONE FIXTURE FOR
 ILLUMINATION.
  
 3)NOTE: PLEASE NOTE THAT NOTE ON E-9.0
 MENTIONS TO SEE 1/4" SCALE ON,,,,PLEASE
 INDICATE WHER TO FIND ON PLAN. WHEN
 PLANS WERE REVIEW PAGE WAS FOUND, PLEASE
 NOTE PAGE ON E-9.
  
 4)NOTE: PLEASE NOTE E-9.1 SHOWS ELEC-
 -TRICAL PLAN FOR PIT BUT NOTHING SHOWN?
 PLEASE SHOW ANY LIGHTING/PUMP/GFI RECEPT
 THAT MAY BE REQ`D PER NEC.
  
 5)NOTE: PLEASE NOTE OUTLET SPACING IN
 MASTER BEDROOMS IN SOME UNITS FOR RECEPT
 -S WITHIN 6' OF DOOR. 210-52
  
 6)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO SHOWN AS
 GFI/GFI PROTECTED. PLEASE NOTE THAT THIS
 IS REQ`D OF ALL KITCHEN PENINSULARS AND
 ISLAND RECPETS. 210-8-A-6.
  
 7)NOTE: PLEASE NOTE SOME APT UNITS WITH
 SAME LAYOUT ARE SHOWN MORETHAN ONCE.
 PLEASE VERIFY .
  
 8)NOTE: PLEASE NOTE THAT ON 14.1 A NOTE
 BOX IS SET UP FOR CIRCUITING FOR
 CORRIDOR LIGHTING. PLEASE NOTE FOR OTHER
 CIRCUITING OF OTHER LTS ON OTHER FLOORS.
  
 9)NOTE: PLEASE SEE KEY NOTES SET FORTHON
 E 16.0 ETC NOTE #`S 3&4. PLEASE NOTE
 THOSE PARTICULAR NOTES ARE NOT SHOWN ON
 PLANS/SHEETS REFERENCED.
  
 10)NOTE: PLEASE NOTE THAT KEY NOTES ARE
 PLACED ON E205 THAT NEED TO BE ON E203,
 E201 IN ORDER TO CORRELATE W/ 207.
  
 11)NOTE: PLEASE NOTE; PER ART 230-70-A
 OF LOCAL AMENDMENTS. NO MORETHAN 8' OF
 UNPROTECTED CONDUCTORS INSIDE THE BLDG.
 PLEASE NOTE FEEDS COMING INTO 5 OF 6 AND
 METERCENTER 4 OF 6.
  
 12)NOTE: PLEASE NOTE PANEL SCHEDULE FOR
 PKV SHOWS CIRCUIT TO POOL PANEL AS PANEL
 "DD".MISPRINT? PLEASE CORRECT.
  
 13)NOTE: PLEASE NOTE THAT 1600 EM MAIN
 IS SHOWN FEEDING PANEL PKV? PLEASE
 CLARIFY. PLEASE NOTE THAT EM MAIN IS
 ONLY SHOWN AS A DISCONNECT.
  
 14)NOTE: PLEASE SHOW A DETAIL OVERVIEW
 OF MAIN ELECTRICAL ROOM, GENERATOR RM
 FIRE PUMP ROOM. PLEASE ALSO NOTE ROOM
 SEPARATION ON ONE-LINE RISER DIAGRAM.
  
 15)NOTE: PLEASE PROVIDE NOTE FOR LABEL-
 -ING OF MAIN AND SERVICES FOR EQUIPMENT
 AND ON DOORS OF TWO MAIN ELECTRICAL
 ROOMS. 230-2-E
  
 16)NOTE: PLEASE NOTE THAT ONE-LINE SHOWS
 PANEL 1HA AS 2HA. MISPRINT? PLEASE
 CORRECT.
  
 17)NOTE: PLEASE NOTE THAT OCP AND WIRE
 SIZES NEED TO CORRELATE ON SHEETS FOR
 EDP-2 600A/#1, 500A/#4, 400A/#6 ETC.
 PLEASE SEE EDP-1 ALSO FOR CORRELATION
 OF OCP/WIRE.
  
 18)NOTE:PLEASE NOTE MISSING TECHNICAL
 INFORMATION FOR PANEL ECH. NOTHING SHOWN
  
 19)NOTE: PLEASE NOTE MISPRINT FOR #`S
 FOR CIRCUITS FROM EDP-1 TO ELEV #1 SHOWN
 ON ONE-LINE.
  
 20)NOTE: PLEASE NOTE KEYNNOTES ON TOP
 OF SHEET E-207.
 #7- SHOWS 6000MCM?
 #9- SHOWS 650MCM?
 #9 AND #10 ARE MISSING FROM ONE-LINE ALL
 TOGETHER.
  
 21)NOTE: PLEASE NOTE EDP-1 SHOWS ONE
 PUMP AT 30HP W/ 100A OCP AND #8? PLEASE
 CORRELATE W/ OTHER PUMP SHOWN.
  
 22)NOTE: PLEASE VERIFY OR NOTE OCP FOR
 FIRE PUMP PER 695-4-B-1.
 PLEASE SUBMIT INFORMATION IF PART OF
 A LISTED ASSEMBLY WITH BUILD IN LOCKED
 ROTOR SETTING.
  
 23)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT INCLUDING ALL PANELS AND
 DISCONNECTS AFTER MAINS. IT IS NOTE THAT
 MAINS ARE SHOWN W/ 100,000 AND 65,000
 RATINGS. 110-9/215-5
  
 24)NOTE: PLEASE SEE E209.2 PANEL "S"
 SHOWS CIRCUIT 19 WITH #14 ON A 50A BRKR?
 PLEASE CORRECT.
  
 25)NOTE: PLEASE NOTE THAT EQUIPMENT
 GROUNDING CONDUCTORS ARE MISSING ON ONE-
 LINE AND PANEL SCHEDULES? PLEASE CLARIFY
 IF ALL CONDUITS ARE RIGID AND/OR EMT
 ABOVE GROUND/SLAB AND OVERHEAD. PLEASE
 NOTE IF ANY OF THESE CONDUITS SHOWN
 ARE INDEED PVC THEN PLEASE SHOW ALL
 EQUIPMENT GRNDS SIZED PER 250-122 AND
 PER 250-24.
  
 26)NOTE: PLEASE NOTE THAT ON E-209 ALL
 FEEDERS TO PANELS ARE SHOWN AS A BLANK??
 PLEASE SUBMIT CONDUIT AND CONDUCTOR
 SIZES.
  
 27)NOTE: PLEASENOTE THAT MANY OF THE
 A/C UNIT KW RATINGS ARE MISSING ON PANEL
 SCHEDULES. PLEASE ALSO NOTE THAT SOME
 DO NOT CORRELATE W/ LOAD CALCULATIONS
 AT THE BOTTOM OF PANEL SCHEDULES. PLEASE
 NOTE SOME SHOWN AS 3970 AND 5740 ON THE
 SAME PANEL. PLEASE CORRLEATE.
  
 28)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 A/C LAODS . SHOWN AS 5.3KW W/ 1/4 HP
 MOTOR AND OTHERS SHOWN AS 3.7KW W/ 1/6
 MOTOR. PLEASE NOTE THAT DEMAND IS SHOWN
 HIGHER? PLEASE NOTE 746W PER HP. PLEASE
 CLARIFY WHERE THE EXTRA LOAD IS COMING
 FROM? A-5,A-4X,A-3X, ETC ETC.
  
 29)NOTE: PLEASE CLARIFY LOAD STUDY #1
 SHOWN ON E-208.1. PLEASE NOTE UNITS
 SE-1 AT 9 AND SE-2 AT 15 AND THEN ADDED
 TO TOTAL OF 84? PLEASE VERIFY.
  
 30)NOTE: PLEASE SUBMIT ALL INFORMATION
 ON PANELS. PLEASE NOTE PANEL SHOWN WITH
 NO INFORMATION, SIZE, TYPE ETC.
  
 31)NOTE: PLEASE NOTE AND CLARIFY THAT
 " ELECTRICAL NOTES" FOR ENTIRE PROJECT
 WERE NOT SUBMITTED FOR REVIEW. COLOR
 CODING OF CONDUCTORS, WIRE METHODS ETC
 ETC.
  
 32)NOTE: PLEASE SHOW AND NOTE ALL REQ`
 -MENTS FOR FAIR HOUSING ACT REGULATIONS,
 24 CFR 100.205.
 PLEASE NOTE ALL HEIGHTS/LOCATIONS FOR
 ALL DEVICES.
  
 33)NOTE: PLEASE NOTE, PLEASE SEE ANY
 FIRE REVIEW COMMENTS THAT MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 34)NOTE: PLEASE NOTE THAT MANY UNIT FOR
 TYPES DO NOT CORRELATE WITH UNITS FROM
 E-209 AND A.01.
  
 35)NOTE: PLEASE ALSO NOTE THAT SQ FT FOR
 UNITS ON E209 ALSO DO NOT CORRELATE
 WITH MOST OF THE UNIT SHOWN ON A.01.
 PLEASE CLARIFY AND CORRELATE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR
 IF A MEETING CAN BE SET UP TO GO OVER
 COMMENTS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2003-01-17 Cont ID  
Sent By mamini Date 2003-01-17 Time 10:25 Rev Time 0.00
Received By mamini Date 2003-01-17 Time 10:25 Sent To  
Notes
2003-01-17 00:00:00N/A :
 1. SEE PERMIT # 03010569 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2002-12-16 Cont ID  
Sent By mamini Date 2003-01-03 Time 10:21 Rev Time 1.00
Received By mamini Date 2002-12-16 Time 10:20 Sent To  
Notes
2003-01-03 00:00:00FAILED:
 1. PLEASE SEE THE PREVIOUS REVIEW
 COMMENTS DATED 9-23-02
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-09-23 Cont ID  
Sent By mamini Date 2002-09-23 Time 09:35 Rev Time 3.00
Received By mamini Date 2002-09-23 Time 09:35 Sent To  
Notes
2002-09-23 00:00:00FAILED :
 1. THE PROPOSED 6" WATER METER BOX MUST
 BE SET IN SIDEWALK PER WS-23 SHEET WS4
 OF 7 ON HIBISCUS.
 2. ALL BACKFLOW PREVENTERS ASS. MUST BE
 INSTALLED ON THE PROPERTY, AT THE BACK
 OF SIDEWALKS.
 3. A GREASE INTERCEPTER/SEPARATOR FOR
 THE PROPOSED FUTUTE CLICK CAFE IS
 REQUIRED, PLEASE CALL MR. RODNEY COMPO,
 837-4051 EXT. 4074 FOR CITY REQUIREMENT.
 4. PROPOSED FIRE HYD.
 A) IF PRIVATE, THEN A DDCV ASS. WOULD
 BE REQUIRED.
 B) IF INSTALLED BY THE CITY, THEN
 LOCATING IT SO CLOSE TO AN
 EXISTING ONE IS NOT ACCEPTABLE.
 LOCATION SHOULD BE VERIFY WITH PUBLIC
 UTILITIES ENGINEERING SERVICES,659-8040.
 5. DURING MEETING WITH PUBLIC UTILITIES,
 WE BELIEVE THAT SEWER CONNECTION WOULD
 BE AVAILABLE IN SOUTH OLIVE AVE. AND
 DEXIE HWY. ALSO, THE EXISTING SEWER LINE
 IN EXISTING ALLEY-WAY MAY BE USED BY
 UTILIZING GRAVITY LINES.THIS MAY
 ELIMINATE THE NEED FOR LIFT STATION AS
 PROPOSED.PLEASE CONTACT 659-8040 EXT.
 2306 MR. MANNY GONZALEZ FOR SUBMITTING
 PLANS FOR THEIR REVIEW AND COMMENTS.
 6. A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL/SITE UNDERGROUND
 UTILITIES AT THE TIME OF ACTUAL
 PERMITTING WILL BE REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-08-14 Cont ID  
Sent By mamini Date 2004-11-15 Time 08:24 Rev Time 0.00
Received By nmccray Date 2004-11-15 Time 09:55 Sent To  
Notes
2002-08-14 00:00:00FAILED :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR CIVIL/SITE AND
 UNDERGROUND UTILITIES AT THE TIME OF
 ACTUAL PERMITTING WILL BE REQUIRED.
 2. PLEASE PROVIDE STORM WATER CALC.
 WHICH INCLUDE TOTAL SITE, PERVIOUS AND
 IMPERVIOUS AREAS.
 3. PLEASE PROVIDE DETAILS,CALC. AND TYPE
 FOR THE PROPOSED LIFT STATION.
 4. SHEET PD1 OF 2 REFERS TO TYPE "C" AND
 "D" INLET, NO DETAILS OR INDEX NUMBER IS
 PROVIDED, PLEASE VERIFY.
 5. POLLUTION/ EROSION PLANS (BMP) MUST
 BE INCLUDED IN THE PLAN AND INSTALLED IN
 FIELD PRIOR TO ANY SITE IMPROVEMENTS
 WORKS.
 6. PLEASE STATE THAT, IF THE SITE PLAN
 AS SHOWN COORDINATES WITH F.D.O.T PLANS
 FOR RECONSTRUCTION OF DIXIE HWY AND
 SOUTH OLIVE AVE.
 7. THE REMAINING OF THE EXISTING 6" CLAY
 SEWER MAIN WITHIN ALLEY-WAY SHOULD BE
 REPLACED WITH PVC PIPE WITH MIN. OF
 SDR 26, UP TO EXISTING MANHOLE, PLEASE
 VERIFY THIS WITH THE PUBLIC UTILITIES
 ENG. SEVICES, AMNNY GONZALEZ, 659-8040.
 8. ALL CONNECTIONS TO THE CITY OF WPB
 FACILITIES AND SERVICES MUST BE APPROVED
 AND INSPECTED BY PUBLIC UTILITIES ENG.
 SEVICES, 659-8040.
 9. IN ORDER TO PROVIDE MAX. OF 150' FOR
 FDC FROM FIRE HYD. WHICH IS REQUIRED BY
 THE FIRE DEPARTMENT, THE DDCV ASSEMBLIES
 AND FIRE LINE CONNECTIONS SHOULD BE
 LOCATED AT EAST SIDE OF THE ENTRANCE ON
 TANGLEWOOD COURT, PLEASE VERIFY.
 10. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR IT IS PRIVATE
 PICKUP, IF TO BE PICKED UP BY THE CITY,
 THEN THE CONSTRUCTION AND LOCATION MUST
 BE PER CITY REQUIREMENTS.
 11. SHEET GN1 OF 1, SEWAGE COLLECTION
 SYSTEM NOTES: NO.13 NOTE REFERS TO WORD
 "CITY OF WEST PALM BEACH" SHALL BE CAST
 INTO ALL SANITARY MANHOLE LIDS, PLEASE
 NOTE THAT THIS DOES NOT APPLY TO PRIVATE
 SANITARY MANHOLE, SEE G-2 ON SHEET WS6
 OF 6.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status P Date 2005-08-31 Cont ID  
Sent By mwennerg Date 2005-08-31 Time 09:43 Rev Time 0.00
Received By mwennerg Date 2005-08-27 Time 08:03 Sent To  
Notes
2005-08-31 00:00:00SUBMITTAL OF REVISED SPECIFICATIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status F Date 2005-01-21 Cont ID  
Sent By mcarsill Date 2005-01-21 Time 09:15 Rev Time 0.00
Received By mcarsill Date 2005-01-21 Time 09:15 Sent To  
Notes
2005-01-21 00:00:00YOUR PLAN REVIEW COMMENT RESPONSE
 LETTER OF 6/23/04 HAS BEEN REVIEWED
 AND DETERMINED TO BE UNACCEPTABLE.
 AN AGREEMENT HAD BEEN REACHED THAT
 ONE ELEVATOR WOULD BE PROVIDED WITH
 EMERGENCY POWER WITH THE FIRE MARSHAL.
 AN AGREEMENT HAD BEEN REACHED AND
 THEREFORE A CHANGE AT THIS TIME
 IS NOT PALLATABLE. THE FIRE MARSHAL
 STILL EXPECTS AT LEAST ONE ELEVATOR
 TO BE PROVIDED WITH EMERGENCY POWER.
 HOW DO YOU EXPECT FIRE RESCUE TO
 REMOVE A SICK PERSON BY TRAVELING
 DOWN SEVERAL FLIGHTS OF STAIRS WHEN
 SOMEONE IS SICK OR INJURED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2004-11-16 Cont ID  
Sent By nmccray Date 2004-11-15 Time 09:57 Rev Time 0.00
Received By nmccray Date 2004-11-15 Time 09:57 Sent To  
Notes
2004-11-16 00:00:00GATE CONTROLS SUBMITTALS

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status F Date 2004-09-22 Cont ID  
Sent By nmccray Date 2004-09-22 Time 15:55 Rev Time 0.00
Received By nmccray Date 2004-09-22 Time 15:55 Sent To  
Notes
2004-09-22 00:00:00********DENIED**************************
  
 1) SHEET A.33 SHOWS DOOR # 9 SWINGING
 IN,SHOULD THIS DOOR SWING OUT.
  
 2) ON SHEET E-6.3 LOCATED ONLY ONE EXIT
 SIGN OVER MAIN LOBBY DOORS.
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status F Date 2004-07-27 Cont ID  
Sent By mcarsill Date 2004-07-27 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2004-07-27 Time 13:11 Sent To  
Notes
2004-07-27 00:00:001) THE CORRESPONDENCE DOES NOT
 INDICATE THAT NO EMERGENCY POWER WILL
 BE PROVIDED FOR AT LEAST ONE ELEVATOR.
 THIS IS IN DIRECT CONFLICT WITH THE
 DIRECTION GIVEN BY THE FIRE MARSHAL.
 HE ADVISED THAT AT LEAST ONE ELEVATOR
 PER HIS DIRECTION MUST BE EQUIPPED
 WITH EMERGENCY POWER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2004-06-16 Cont ID  
Sent By nmccray Date 2004-06-16 Time 14:11 Rev Time 0.00
Received By nmccray Date 2004-06-16 Time 14:11 Sent To  
Notes
2004-06-16 00:00:00ELECTRICAL REVISION DATED 6-05-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status   Date 2004-06-11 Cont ID  
Sent By mcarsill Date 2004-06-11 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2004-06-11 Time 12:23 Sent To  
Notes
2004-06-11 00:00:001) THE SMOKE DETECTORS IN A-5 AND A-6
 UNITS SHALL BE LOCATED OUTSIDE THE
 SLEEPING ROOMS. THEY ARE PRESENTLY
 SHOWN IN THE SLEEPING ROOMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2004-05-05 Cont ID  
Sent By nmccray Date 2004-05-05 Time 14:32 Rev Time 0.00
Received By nmccray Date 2004-05-05 Time 14:32 Sent To  
Notes
2004-05-05 00:00:00SUBMITTALS FOR THE FIRE PUMP AND FIRE
 SPRINKLER PIPE AND FITTINGS. SEPARATE
 PERMIT APPLICATIONS AND SHOP DRAWING ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 PUMP.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2004-02-20 Cont ID  
Sent By mcarsill Date 2004-02-20 Time 15:59 Rev Time 0.00
Received By mcarsill Date 2004-02-20 Time 15:59 Sent To  
Notes
2004-02-20 00:00:001) UPPER AND LOWER ROOF LEVEL PLANS
 DISPLAY FDC'S. THESE ITEMS SHOULD BE
 LABELED ROOF MANIFOLDS. FDC'S ARE
 USED TO SUPPLY THE FIRE SPRINKLER
 SYSTEM AT GROUND LEVEL.
  
 2) PLEASE CLARIFY ABOUT THE EXISTENCE
 OF AN EMERGENCY GENERATOR. IT IS
 UNKNOWN IF ONE WILL BE AVAILABLE FOR
 THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2004-01-06 Cont ID  
Sent By mcarsill Date 2004-01-06 Time 18:06 Rev Time 0.00
Received By mcarsill Date 2004-01-06 Time 18:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status F Date 2003-11-26 Cont ID  
Sent By mcarsill Date 2003-11-26 Time 17:13 Rev Time 0.00
Received By mcarsill Date 2003-11-26 Time 17:13 Sent To  
Notes
2003-11-26 00:00:001) NO EXIT SIGNS OBSERVED IN GARAGE
 AREAS.
  
 2) SMOKE DETECTORS HAVE BEEN REMOVED
 FROM SLEEPING ROOMS. PLEASE SEE
 COMMENTS FROM ELECTRICAL PLAN
 REVIEWER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2003-07-29 Cont ID  
Sent By hpiskura Date 2003-08-15 Time 10:47 Rev Time 0.00
Received By mcarsill Date 2003-07-29 Time 17:25 Sent To  
Notes
2003-07-29 00:00:00CUT SHEETS WITH REGARDS TO THE FIRE
 SPRINKLER SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status N Date 2003-07-02 Cont ID  
Sent By nmccray Date 2003-07-02 Time 13:41 Rev Time 0.00
Received By nmccray Date 2003-07-02 Time 13:40 Sent To B
Notes
2003-07-02 00:00:00ROUTED TO DON NEELY BY FIRE 7-02-03
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:22 Rev Time 0.00
Received By mcarsill Date 2003-04-11 Time 10:32 Sent To  
Notes
2003-04-11 00:00:001) EXIT DOOR FROM GARAGE AREA NEAR N.5
 AND N.6 ON THE FOURTH LEVEL SWINGS
 INWARD. DOOR MUST SWING IN THE DIRECTION
 OF EXIT TRAVEL.
  
 2) TACTILE SIGNAGE REQUIRED AT
 STAIRWELL DOORS.
  
 3) ALL AREAS OF THE BUILDING SHALL
 BE PROVIDED WITH ADEQUATE EMERGENCY
 LIGHTING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2003-02-19 Cont ID  
Sent By mcarsill Date 2003-02-19 Time 15:17 Rev Time 0.00
Received By mcarsill Date 2003-02-19 Time 15:17 Sent To  
Notes
2003-02-19 00:00:001) SOME BUILDING FEATURES APPEAR TO
 HANG OVER THE PROPERTY LINE IN
 SEVERAL LOCALES.
  
 2) THE RECOMMENDED ACCESSIBLE PARKING
 SPACE DETAIL IS ILLEGIBLE ON PAGE A.02.
  
 3) THE COLUMN WITHIN STAIR # 5 IS NOT
 TO INTERFERE WITH ANY EXIT DISCHARGE.
 WHY IS THIS STAIR LABELED # 5.
  
 4) THE ELECTRICAL ROOM DOORS NEAR
 ELEVATORS # 2 AND 3 APPEAR TO DECREASE
 THE EXIT HALLWAY BY 50 PERCENT.
  
 5) THE BUILDING ADDRESS NOT SHOWN ON
 THE ELEVATION DRAWINGS.
  
 6) HANDRAILS ARE REQUIRED AT MONUMENTAL
 STAIR LOCATIONS.
  
 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 INFORMATION FOR 1/2 GALV.STEEL TENSION
 CABLES.
  
 8) LIFE SAFETY PLAN LS-6 DOES NOT
 APPEAR TO CORRESPOND WITH LS-7.
  
 9) LIFE SAFETY PLAN LS-2 SHOWS EXITING
 VIA A SOLID WALL ADJACENT TO TRAVEL
 DISTANCE 189. OTHER LS PLANS DISPLAY
 THE VERY SAME THING.
  
 10) PLEASE SHOW TRAVEL DISTANCES FROM
 RECREATION AREAS.
  
 11) NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 12) AN EXIT SIGN APPEARS TO BE MISSING
 DIRECTLY IN FRONT OF STAIR # 5.
  
 13) END OF LINE RESISTORS NOTED ON FIRE
 ALARM RISER DIAGRAMS. PLEASE BE ADVISED
 ONLY CLASS A, STYLE D OR FULLY
 ADDRESSABLE FIRE ALARM SYSTEMS WILL BE
 ALLOWED.
  
 14) APARTMENTS USED FOR HANDICAPPED
 PERSONS SHALL BE EQUIPPED WITH HORN
 STROBES.
  
 15) NO SMOKE DETECTOR IN ELECTRICAL
 ROOM NEAR ELEVATOR # 3.
  
 16) THERE APPEARS TO BE AT LEAST THREE
 FIRE DEPARTMENT CONNECTIONS. TWO ARE
 ONLY NEEDED. AT LEAST ONE FIRE
 DEPARTMENT CONNECTION SHALL BE WITHIN
 150 FEET OF A FIRE HYDRANT.
  
 17) PLEASE PROVIDE PRESSURE REDUCING
 VALVES NOTED IN FP 201.
  
 18) A 750 GPM FIRE PUMP IS NOT
 ACCEPTABLE. ONE STANDPIPE IS REQUIRED
 TO PROVIDE 500 GPM, AND 250 GPM FOR
 EACH ADDITIONAL STANDPIPE. EACH REQUIRED
 STAIRWELL IS REQUIRED TO HAVE A
 STANDPIPE. PLEASE REVISE THE DRAWINGS.
 ALSO A 6" PIPE CANNOT BE USED. A MINIMUM
 OF AT LEAST AN 8" PIPE IS TO BE USED.
  
 19) THE FIRE SPRINKLER SYSTEM SHALL
 HAVE QUICK RESPONSE OR RESIDENTIAL
 SPRINKLER HEADS.
  
 20) THE FIRE SPRINKLER PLANS SHALL
 CLEARLY INDICATE WHAT ROOMS THAT WILL
 NOT BE SPRINKLER PROTECTED. EXAMPLES
 COULD INCLUDE BATHROOMS AND CLOSETS.
 PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 14:39 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 14:38 Sent To  
Notes
2002-12-18 00:00:001) PLEASE EXPLAIN HOW PERSONS EXIT
 BETWEEN PARKED VEHICLES TO REACH THE
 EXIT DOOR WHERE TRAVEL DISTANCES HAVE
 BEEN OBTAINED. WHAT IS THE WIDTH THAT
 YOUR FIRM IS EXPECTING TO BE PRESENT
 BETWEEN THE PARKED VEHICLES.
  
 2) EXIT SIGNS ARE MISSING IN THE
 PARKING GARAGE ON THE ARCHITECTURAL
 DRAWINGS.
  
 3) DOOR SCHEDULE STILL CARRIES DOOR 72
 WITH PAINT INFORMATION. PLEASE REMOVE
 THE NOTE FROM THE DOOR SCHEDULE.
  
 4) ALL EXTERIOR DOORS ARE TO BE
 ACCESSIBLE TO FIRE RESCUE. LOCKING
 DEVICES ON EXIT DOORS SHALL COMPLY
 WITH DELAYED EGRESS OR ACCESS CONTROLLED
 EGRESS. IT IS IMPERATIVE THAT FIRE
 RESCUE PERSONNEL BE ABLE TO ACCESS
 THE BUILDING IN THE EVENT OF A MEDICAL
 EMERGENCY REGARDLESS OF THE STATUS
 OF THE FIRE ALARM SYSTEM. DUMMY LOCK
 INFORMATION PROVIDED WITH THE PLAN
 REVIEW NOTES STILL SEEM CONFUSING.
  
 5) GARAGE FD CONNECTION RISER ON A.80
 SHOWS A 2 1/2 FIRE DEPARTMENT CONNECTION
 ALL 2 1/2 HOSE CONNECTIONS EXCEPT THE
 FIRE DEPARTMENT CONNECTIONS SHALL HAVE
 1 1/2 REDUCERS ON THEM.
  
 6) TRAVEL DISTANCES IN THE BUILDING
 CODE AND THE FIRE CODE SHALL BE
 REVIEWED. IF TRAVEL DISTANCES ARE NOT
 THE SAME, THEN THE MOST RESTRICTIVE
 CODE WILL APPLY. PLEASE PROVIDE A
 CODE COMPARISON ON THE PLANS WITH
 REGARDS TO TRAVEL DISTANCES.
  
 7) ALL STAIRS AND RAMPS ARE REQUIRED
 TO HAVE HANDRAILS ON BOTH SIDES. THE
 AMENITY LEVEL LAYOUT PLAN ONLY DISPLAYS
 HANDRAILS ON ONE SIDE OF STAIRS.
  
 8) THE FIRE PUMP ROOM IS REQUIRED TO
 HAVE EMEREGNCY LIGHTING IN IT.
  
 9) NO FIRE LINE PIPING IS ALLOWED TO
 RUN UNDERNEATH THE BUILDING FOUNDATION.
  
 10) SOME MECHANICAL,ELECTRICAL COMMENTS
 NOT PROPERLY ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-09-26 Cont ID  
Sent By mcarsill Date 2002-09-26 Time 08:35 Rev Time 0.00
Received By mcarsill Date 2002-09-26 Time 08:35 Sent To  
Notes
2002-09-26 00:00:001) PLEASE NOTE ON THE PLANS THAT THE
 BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. COMPLIANCE WITH APPENDIX F
 OF THE LOCAL AMENDMENTS IS REQUIRED.
  
 2) TRAVEL DISTANCES TO EXCEED THE
 MINIMUM CODE REQUIREMENTS. TRAVEL
 DISTANCES SHALL NOT EXCEED 200 FEET.
 THE LIFE SAFETY PLANS REVEAL TRAVEL
 DISTANCES IN EXCESS OF 200 FEET.
  
 3) PULL STATIONS ARE NOT REQUIRED IN
 THE RETAIL SPACES LOCATED ON THE FIRST
 FLOOR.
  
 4) TWO OF THE THREE EXITS DO NOT
 DIRECTLY EXIT TO THE INTERIOR. FIFTY
 PERCENT OF THE EXITS MUST EXIT DIRECTLY
 TO THE EXTERIOR.
  
 5) END OF LINE RESISTORS NOTED ON FIRE
 ALARM RISER DIAGRAM. ONLY CLASS A,
 STYLE D CIRCUITS ARE ALLOWED. NO EOL'S
 ALLOWED IN THE FIELD.
  
 6) ELECTRONIC SWITCHES ARE REQUIRED ON
 THE BACKFLOW DEVICES.
  
 7) EXIT DISCHARGE FROM STAIR # 3 RUNS
 DIRECTLY INTO WATER METER AND TREE.
  
 8) FIRE LINES ARE NOT PERMITTED TO BE
 RUN UNDERNEATH THE BUILDING. THE FDC
 IS TO BE WITHIN 150 FEET OF A FIRE
 HYDRANT.
  
 9) DOORS SWING INWARD ON WEST SIDE OF
 GARAGE WHERE AN EXIT SIGN IS SHOWN. ARE
 THE DOOR SWINGS PROPER.
  
 10) PARKING SPACES LOCATED DIRECTLY
 IN FRONT OF EXIT SIGNS IN PARKING
 GARAGE, THIRD LEVEL.
  
 11) WHERE ARE THE EMERGENCY LIGHTS IN
 THE CORRIDORS. THE ELECTRICAL PLANS
 DISPLAY NIGHTLITES ONLY.
  
 12) EXIT SIGN PLACEMENT CANNOT EXCEED
 200 FEET.
  
 13) PLEASE INDICATE ON THE PLANS THAT
 SMOKE DETECTORS ARE TO BE INSTALLED A
 MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
  
 14) PLEASE EXPLAIN NOTE ON DOOR SCHEDULE
 WHICH INDICATES THAT A/C CLOSET DOORS
 WILL BE PAINTED WITH FIRE RETARDANT
 PAINT TO PROVIDE C LABEL RATING AS
 PER SFBC. THE SFBC IS NOT APPLICABLE.
  
 15) PLEASE EXPLAIN KEYED HARDWARE
 LOCKSET OF STAIR DOORS.
  
 16) PLEASE EXPLAIN NOTE ON LIFE SAFETY
 PLANS, MAGNETIC LOCKS TIED INTO FIRE
 ALARM SYSTEM.
  
 17) NO ADDRESS FOR THE BUILDING COULD
 BE LOCATED ON THE ELEVATION DRAWINGS.
  
 18) IT APPEARS THAT PORTIONS OF THE
 BUILDING EXTEND OVER THE PROPERTY LINE.
  
 19) HOW DOES EXITING WORK IN THE GARAGE
 WHEN THE OVERHEAD SLIDE GATES ARE IN
 OPERATION.
  
 20) WHAT PREVENTS PERSONS FROM BEING
 HIT BY CARS IN THE 12' ALLEY NEAR
 STAIR # 2.
  
 21) NO INFORMATION PROVIDED ON GREASE
 REMOVAL FOR THE FUTURE GLICK CAFE.
  
 22) MECHANICAL PLANS MUST INDICATE A
 MINIMUM OF AT LEAST SIX AIR CHANGES
 PER HOUR FOR THE GARAGE.
  
 23) PLEASE REVIEW EXIT DISCHARGE
 CRITERIA, FBC, SECTION 1010.
  
 24) PLEASE INDICATE WHICH ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 25) AN EXIT SIGN IS LOCATED WITHIN A
 ROOM IN THE GARAGE ON THE FOURTH LEVEL.
  
 26) EXIT SIGNS ON THE FIFTH FLOOR
 ARE LOCATED BEYOND THE DOORS.
  
 27) FIRST FLOOR EXITING FROM THE GARAGE
 IS CONFUSING. EXIT SIGNS APPEAR TO
 DIRECT PERSONS TOWARDS THE AREA WHERE
 A SECURITY GATE WILL BE LOCATED. PLEASE
 EXPLAIN.
  
 28) EXIT SIGNS APPEAR TO BE MISSING
 ON THE FIRST FLOOR.
  
 29) HANDRAILS FOR STAIRS APPEAR TO
 EXCEED THE PROPERTY LINES.
  
 30) PLEASE EXPLAIN DUMMY LOCKS. THE
 FIRE RESCUE DEPARTMENT MAY NEED TO ENTER
 THE BUILDING WHEN THE FIRE ALARM SYSTEM
 IS NOT ACTIVATING.
  
 31) PLEASE REVIEW SECTIONS OF THE CODE
 WITH REGARDS TO SECURITY DEVICES ON
 EXIT DOORS.
  
 32) ALL MAINTENANCE ROOMS AND TRASH
 COLLECTION ROOMS ARE TO BE AT LEAST
 ONE HOUR SEPARATED WITH SPRINKLERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By mcarsill Date 2002-08-15 Time 17:17 Rev Time 0.00
Received By mcarsill Date 2002-08-15 Time 17:17 Sent To  
Notes
2002-08-15 00:00:001) THE BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS AND CERTAIN RESTRICTIONS
 WILL APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 2) PLEASE INDICATE CONSTRUCTION TYPE FOR
 BUILDING.
  
 3) THE PARKING SPACES BY LEVEL TOTAL
 IS INCORRECT.
  
 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 5) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 6) A KNOX-BOX WILL BE REQUIRED.
  
 7) ALL SHAFTWAYS THAT PERSONS CAN FALL
 INTO SHALL BE MARKED "SHAFTWAY" IN
 RED LETTERS ON A WHITE BACKGROUND.
  
 8) SITE PLAN DOES NOT INDICATE FIRE
 HYDRANT LOCATION.
  
 9) STAIR # 2 DOOR ON THE UPPER FLOORS
 SWINGS IN THE WRONG DIRECTION.
  
 10) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 11) PLEASE INDICATE WHICH ELEVATORS
 MEET THE STRETCHER REQUIREMENTS PER THE
 FLORIDA BUILDING CODE, SECTION 3003.4.
  
 12) PLEASE DEMONSTRATE COMPLIANCE WITH
 FLORIDA BUILDING CODE, SECTION 3003.6.
  
 13) FABRIC AWNINGS ARE TO BE FIRE
 RATED.
  
 14) BUILDING ELEVATIONS APPEAR TO BE
 INCORRECT.
  
 15) PLEASE INDICATE PRESCRIPTIVE CODE
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 16) PLANS REFLECT EXTERIOR GRADE
 PLYWOOD. AGAIN THE BUILDING IS LOCATED
 IN THE FIRE LIMITS, ONLY FIRE RATED
 PLYWOOD IS ALLOWED.
  
 17) PLEASE PROVIDE FLAME-SPREAD
 INFORMATION FOR SOUND WRAP FOR
 TRASH-CHUTE.
  
 18) IT APPEARS THAT ONE PARKING SPACE
 ON THE SECOND LEVEL INTERFERES WITH
 EXIT ACCESS FROM THE PARKING GARAGE.
  
 19) ARE THE EXIT DOORS FROM THE POOL
 LEVEL TO THE CORRIDOR SWINGING IN THE
 RIGHT DIRECTION.
  
 20) PLEASE PROVIDE INFORMATION FOR
 THE PARKING GARAGE. THE GARAGE IF
 CONSIDERED ENCLOSED, MUST HAVE
 MECHANICAL VENTILATION THAT PROVIDES
 AT LEAST SIX AIR CHANGES PER HOUR.
  
 21) PLEASE INDICATE ON THE DRAWINGS
 OTHER BUILDINGS THAT ARE IN CLOSE
 PROXIMITY TO THE SUBJECT BUILDING.
  
 22) WILL THE CLICK CAFE BE USING GREASE
 DUCTS AND IF SO WHERE WILL THEY
 TERMINATE.
  
 23) IT APPEARS THAT SOME HANDRAILS
 ARE OVER THE BUILDING'S PROPERTY LINE.
  
 24) PLEASE DEMONSTRATE COMPLIANCE THAT
 ALL ELEVATOR EQUIPMENT ROOMS HAVE
 INDEPEDENT VENTILATION OR AIR
 CONDITIONING.
  
 25) MANUAL PULL STATIONS ARE NOT
 REQUIRED IN MERCANTILE OCCUPANCIES IF
 FIRE SPRINKLER PROTECTED.
  
 26) NO FLOW OR TAMPER SWITCHES SHOWN
 ON FIRE ALARM DRAWINGS.
  
 27) A MANUAL PULL STATION WAS OBSERVED
 IN THE MIDDLE OF SOME PARKING SPACES.
  
 28) WHERE IS THE MAIN FIRE ALARM CONTROL
 PANEL LOCATED FOR THE BUILDING.
  
 29) PLEASE REVIEW TRAVEL DISTANCES TO
 EXITS IN THE FLORIDA FIRE CODE. ALSO
 IT APPEARS THAT TWO OUT OF THE THREE
 EXIT STAIRS DISCHARGE DIRECTLY INTO
 THE BUILDING. PLEASE EXPLAIN HOW THIS
 MEETS THE 50 PERCENT RULE.
  
 30) PLEASE INDICATE FIRE STANDPIPE
 LOCATIONS. ALL PORTIONS OF THE BUILDING
 MUST BE REACH WITH 100 FEET OF HOSE
 AND 30 FEET OF NOZZLE SPRAY.
  
 31) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 32) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 33) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED WHEN THE BUILDING REACHES
 THREE FLOORS OR THIRTY FEET IN HEIGHT.
  
 34) PLEASE PROVIDE EXIT DISCHARGE
 INFORMATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 11:35 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 11:35 Sent To M
Notes
2005-10-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 16:09 Sent To Z
Notes
2005-09-28 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 17:18 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 17:18 Sent To  
Notes
2005-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 17:59 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 17:59 Sent To M
Notes
2005-08-23 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 08:16 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 08:16 Sent To M
Notes
2005-08-16 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 15:16 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 15:16 Sent To E
Notes
2005-08-15 00:00:00TO "JLEAHY" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 09:26 Rev Time 0.00
Received By adarroug Date 2005-07-27 Time 09:26 Sent To  
Notes
2005-08-01 00:00:00TO "COMM" BD#51
2005-07-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 09:08 Sent To E
Notes
2005-07-21 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 13:49 Rev Time 0.00
Received By shill Date 2005-06-20 Time 13:49 Sent To M
Notes
2005-06-20 00:00:00TO HM DESK

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2005-06-09 Cont ID  
Sent By mjacobs Date 2005-06-09 Time 08:30 Rev Time 0.00
Received By mjacobs Date 2005-06-09 Time 08:30 Sent To P
Notes
2005-06-09 00:00:00TO 'P' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 16:41 Sent To E
Notes
2005-05-26 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 14:17 Sent To E
Notes
2005-05-25 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 14:15 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 11:17 Sent To M
Notes
2005-05-20 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 10:09 Sent To M
Notes
2005-05-20 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 08:50 Sent To M
Notes
2005-05-10 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 18:12 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 18:12 Sent To M
Notes
2005-05-03 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 11:13 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 11:13 Sent To M
Notes
2005-03-25 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2005-03-24 Cont ID  
Sent By adarroug Date 2005-03-24 Time 16:08 Rev Time 0.00
Received By adarroug Date 2005-03-24 Time 16:08 Sent To M
Notes
2005-03-24 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 11:23 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 11:23 Sent To E
Notes
2005-03-08 00:00:00TO "BT" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 14:37 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 14:37 Sent To E
Notes
2004-12-14 00:00:00SENT TO "DP" DESK/REV E-10.3

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 11:12 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 11:12 Sent To  
Notes
2004-12-14 00:00:00SENT TO COMM BD#21

Review Stop I INCOMING/PROCESSING
Rev No 81 Status   Date 2004-12-01 Cont ID  
Sent By mjacobs Date 2004-12-01 Time 14:50 Rev Time 0.00
Received By mjacobs Date 2004-12-01 Time 14:50 Sent To  
Notes
2004-12-01 00:00:00SENT TO "SH" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 15:26 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 15:26 Sent To B
Notes
2004-10-29 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2004-10-29 Cont ID  
Sent By csiegber Date 2004-10-29 Time 14:42 Rev Time 0.00
Received By csiegber Date 2004-10-29 Time 14:42 Sent To B
Notes
2004-10-29 00:00:00TO SH DESK/SUBMITTAL
 OH PARKING CONTROL GATES

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2004-09-23 Cont ID  
Sent By csiegber Date 2004-09-23 Time 16:37 Rev Time 0.00
Received By csiegber Date 2004-09-23 Time 16:37 Sent To  
Notes
2004-09-23 00:00:00TO HP DESK/TEMP POWER THRU UNIT TURNOVER
 PLAN

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2004-09-23 Cont ID  
Sent By csiegber Date 2004-09-23 Time 16:33 Rev Time 0.00
Received By csiegber Date 2004-09-23 Time 16:33 Sent To B
Notes
2004-09-23 00:00:00TO SH DESK/SUBMITTAL
 POOL DECK DRAWS W/ORIG PLASTIC GRATE

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 07:38 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 07:38 Sent To B
Notes
2004-09-20 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 11:49 Sent To  
Notes
2004-08-24 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2004-08-04 Cont ID  
Sent By csiegber Date 2004-08-04 Time 11:51 Rev Time 0.00
Received By csiegber Date 2004-08-04 Time 11:51 Sent To B
Notes
2004-08-04 00:00:00TO SH DESK/SUBMITTAL
 ROOF

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2004-07-29 Cont ID  
Sent By csiegber Date 2004-07-29 Time 09:05 Rev Time 0.00
Received By csiegber Date 2004-07-29 Time 09:05 Sent To B
Notes
2004-07-29 00:00:00TO SH DESK/SUBMITTAL
 SHORING & POST TENSION CABLE LETTERS
 FOR ROOF (LEVEL 9) POURS 1-7

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-27 Time 10:56 Rev Time 0.00
Received By csiegber Date 2004-07-27 Time 10:56 Sent To B
Notes
2004-07-27 00:00:00TO SH DESK/SUBMITTAL
 OVERHEAD DOOR RE-SUB W/SIND TUNNEL RPT

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2004-07-27 Cont ID  
Sent By csiegber Date 2004-07-27 Time 10:55 Rev Time 0.00
Received By csiegber Date 2004-07-27 Time 10:55 Sent To M
Notes
2004-07-27 00:00:00TO PK BOX/REV GARAGE EXHAUSTS ON 3 & 4

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:59 Sent To  
Notes
2004-07-14 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2004-07-14 Cont ID  
Sent By mjacobs Date 2004-07-14 Time 12:22 Rev Time 0.00
Received By mjacobs Date 2004-07-14 Time 12:22 Sent To M
Notes
2004-07-14 00:00:00SENT TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2004-07-09 Cont ID  
Sent By csiegber Date 2004-07-09 Time 09:38 Rev Time 0.00
Received By csiegber Date 2004-07-09 Time 09:38 Sent To B
Notes
2004-07-09 00:00:00TO SH DESK/2 SUBMITTALS/
 INSULATION PRODUCT DATA
 ROOFING SHOP DRWS & PROD DATA

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 14:24 Sent To B
Notes
2004-06-14 00:00:00TO SH DESK/OVERHEAD DOOR DATA

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-04 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-06-04 Time 15:19 Sent To  
Notes
2004-06-04 00:00:00TO COMM BD#40

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-04 Time 14:01 Rev Time 0.00
Received By csiegber Date 2004-06-04 Time 14:01 Sent To B
Notes
2004-06-04 00:00:00TO SH DESK/2 SUBMITTALS/SHORING & POST-
 TENSION CALBE LETTERS FOR ROOF (LEVEL9)
 POURS 1-7
 LETTER TO CHANGE ROOFING SUBCONTRACTOR

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 09:22 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 09:22 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2004-05-13 Cont ID  
Sent By csiegber Date 2004-05-13 Time 09:31 Rev Time 0.00
Received By csiegber Date 2004-05-13 Time 09:31 Sent To B
Notes
2004-05-13 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 14:37 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 14:37 Sent To FIRE
Notes
2004-05-04 00:00:00TO FIRE/SUBMITTAL/FIRE PUMP & FIRE
 SPRINKLER

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 14:30 Sent To B
Notes
2004-05-04 00:00:00TO SH DESK/4 SUBMITTAL/ROOF TO ANCHORS F
 APPROVAL/LOUVERS@TRANS VAULT & ELEVATOR
 MACHINE RM STATIRS/CABLE & SHORING
 LETTERS FOR LEVER 7 POUR 1, LEVEL 8
 POURS 1,4,5,6,&7/DOORS & HARDWARE &
 TOILET ACCESS

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:58 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:58 Sent To B
Notes
2004-04-22 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:16 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:16 Sent To B
Notes
2004-04-22 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 10:36 Sent To  
Notes
2004-04-14 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 11:33 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 11:33 Sent To M
Notes
2004-04-13 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 13:53 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 13:53 Sent To B
Notes
2004-04-06 00:00:00TO SH DESK/SUBMITTAL/LEIGHTWEIGHT
 CONCRETE SHOP DRAWINGS & PRODUCT DATA &
 STEEL TRUSS DRAWS & CALCS & SHORIN &
 POST TENSION LETTER FOR LEVEL 7 POURS 6
 & 7 AND LEVEL 8 POURS 2 & 3

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:48 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:48 Sent To E
Notes
2004-04-01 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 13:09 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 13:09 Sent To P
Notes
2004-04-01 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 13:00 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 13:00 Sent To B
Notes
2004-04-01 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 09:07 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 09:07 Sent To B
Notes
2004-03-26 00:00:00SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 08:44 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 08:44 Sent To Z
Notes
2004-03-22 00:00:00TO MM REV

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 12:08 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 12:08 Sent To B
Notes
2004-03-19 00:00:00TO SH DESK/8TH FLR RESHORING/PUMP MIX/
 SPA PERGOLA/TRELLIS REV B & METAL DECK

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2004-03-10 Cont ID  
Sent By csiegber Date 2004-03-10 Time 08:57 Rev Time 0.00
Received By csiegber Date 2004-03-10 Time 08:57 Sent To B
Notes
2004-03-10 00:00:00TO SH DESK/SUBMITTAL/SHORING & PT LETTER
 & ADD'L TRASH RM DOOR REV

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 10:34 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 10:34 Sent To B
Notes
2004-02-26 00:00:00TO SH DESK/SUBMITTAL/DRY-IN PLAN

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 12:24 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 12:24 Sent To B
Notes
2004-02-25 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 16:41 Sent To B
Notes
2004-02-19 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 09:37 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 09:37 Sent To  
Notes
2004-02-19 00:00:00TO DON NEELY/ALTERNATE SHORING 3 & 5

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 15:03 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 15:03 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 14:34 Sent To  
Notes
2004-02-18 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:05 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 11:05 Sent To  
Notes
2004-02-12 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:04 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 11:04 Sent To B
Notes
2004-02-12 00:00:00TO SH DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:39 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:39 Sent To P
Notes
2004-02-06 00:00:00TO KS BOX/U/G PLUMBING REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:39 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:39 Sent To Z
Notes
2004-02-06 00:00:00REV/LANDSCAPE

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 11:47 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 11:47 Sent To  
Notes
2004-02-05 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 15:21 Sent To B
Notes
2004-02-06 00:00:00TO SH DESK/REV/PAINT SPECS

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 11:29 Sent To E
Notes
2004-02-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 09:32 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 09:32 Sent To B
Notes
2003-12-30 00:00:00TO HP DESK/SUBMITTAL/RAILINGS

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2003-12-29 Cont ID  
Sent By csiegber Date 2003-12-29 Time 10:29 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 10:29 Sent To  
Notes
2003-12-29 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2003-12-18 Cont ID  
Sent By alange Date 2003-12-18 Time 15:09 Rev Time 0.00
Received By alange Date 2003-12-18 Time 15:09 Sent To B
Notes
2003-12-18 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 15:10 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 15:10 Sent To B
Notes
2003-12-16 00:00:00TO HP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 14:46 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 14:46 Sent To P
Notes
2003-12-16 00:00:00TO KS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 09:21 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 09:21 Sent To  
Notes
2003-12-12 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 16:16 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 16:16 Sent To  
Notes
2003-12-05 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 13:00 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 12:59 Sent To B
Notes
2003-11-24 00:00:00TO HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:28 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 09:28 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 14:59 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 14:59 Sent To  
Notes
2003-10-24 00:00:00TO COMM BD#52 - 3 ROLLS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:39 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 08:38 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 16:43 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 16:42 Sent To P
Notes
2003-09-10 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 15:51 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 15:51 Sent To B
Notes
2003-09-10 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 12:31 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 12:31 Sent To B
Notes
2003-09-03 00:00:00TO HP DESK REV PROD APP/SUB SHOP DRAWS

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 10:54 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 10:53 Sent To B
Notes
2003-08-13 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-08-06 Cont ID  
Sent By alange Date 2003-08-06 Time 15:12 Rev Time 0.00
Received By alange Date 2003-08-06 Time 15:12 Sent To B
Notes
2003-08-06 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:23 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:22 Sent To  
Notes
2003-07-30 00:00:00TO DON N DESK

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 13:40 Rev Time 0.00
Received By alange Date 2003-07-30 Time 13:40 Sent To B
Notes
2003-07-30 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 13:26 Rev Time 0.00
Received By alange Date 2003-07-29 Time 13:26 Sent To B
Notes
2003-07-29 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-07-29 Cont ID  
Sent By alange Date 2003-07-29 Time 13:14 Rev Time 0.00
Received By alange Date 2003-07-29 Time 13:14 Sent To B
Notes
2003-07-29 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 11:53 Rev Time 0.00
Received By alange Date 2003-07-28 Time 11:53 Sent To  
Notes
2003-07-28 00:00:00TO DON N DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 09:05 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 09:05 Sent To B
Notes
2003-07-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 15:29 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 15:29 Sent To B
Notes
2003-07-01 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 13:31 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 13:31 Sent To B
Notes
2003-06-25 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:26 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 11:25 Sent To B
Notes
2003-06-25 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:22 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 11:22 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:20 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 11:20 Sent To B
Notes
2003-06-25 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-06-11 Time 09:41 Rev Time 0.00
Received By shernand Date 2003-06-11 Time 09:41 Sent To B
Notes
2003-06-11 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-05-23 Time 13:51 Rev Time 0.00
Received By shernand Date 2003-05-23 Time 13:51 Sent To B
Notes
2003-05-23 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 13:41 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 13:41 Sent To B
Notes
2003-05-21 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:52 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:52 Sent To B
Notes
2003-05-05 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-03 Cont ID  
Sent By sgraham Date 2003-04-29 Time 11:46 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 13:55 Sent To  
Notes
2003-03-31 00:00:00COMM BOARD #6
 PLANS ON RACK; 9 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-27 Cont ID  
Sent By lmartine Date 2003-03-27 Time 17:03 Rev Time 0.00
Received By lmartine Date 2003-03-27 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2002-12-11 Time 16:00 Sent To  
Notes
2002-12-11 00:00:00ON COMM BOARD #48
 PLANS ON RACK NEXT TO CONFERENCE ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 25 Status P Date 2005-10-17 Cont ID  
Sent By hmoser Date 2005-10-17 Time 15:22 Rev Time 0.00
Received By hmoser Date 2005-10-17 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2005-10-17 Cont ID  
Sent By hmoser Date 2005-10-17 Time 14:55 Rev Time 0.00
Received By hmoser Date 2005-10-17 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2005-09-14 Cont ID  
Sent By hmoser Date 2005-09-14 Time 17:51 Rev Time 0.00
Received By hmoser Date 2005-09-14 Time 17:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2005-09-07 Cont ID  
Sent By prafter Date 2005-09-07 Time 09:33 Rev Time 1.50
Received By prafter Date 2005-09-07 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2005-08-12 Cont ID  
Sent By pkrauss Date 2005-08-12 Time 07:06 Rev Time 0.40
Received By pkrauss Date 2005-08-12 Time 06:52 Sent To  
Notes
2005-08-12 00:00:00REVISED SPECIFICATION BOOK

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 14:05 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2005-06-01 Cont ID  
Sent By hmoser Date 2005-06-01 Time 16:49 Rev Time 0.00
Received By hmoser Date 2005-06-01 Time 16:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2005-05-24 Cont ID  
Sent By hmoser Date 2005-05-24 Time 19:01 Rev Time 0.00
Received By hmoser Date 2005-05-24 Time 18:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2005-05-24 Cont ID  
Sent By hmoser Date 2005-05-24 Time 18:39 Rev Time 0.00
Received By hmoser Date 2005-05-24 Time 18:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2005-05-24 Cont ID  
Sent By hmoser Date 2005-05-24 Time 16:40 Rev Time 0.00
Received By hmoser Date 2005-05-24 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date   Cont ID  
Sent By   Date 2005-05-16 Time   Rev Time 0.00
Received By hmoser Date 2005-05-16 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2005-03-30 Cont ID  
Sent By hmoser Date 2005-03-30 Time   Rev Time 0.00
Received By hmoser Date 2005-03-30 Time 17:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2004-09-18 Cont ID  
Sent By pkrauss Date 2004-09-18 Time 07:37 Rev Time 1.10
Received By pkrauss Date 2004-09-18 Time 06:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2004-08-02 Cont ID  
Sent By pkrauss Date 2004-08-02 Time 07:51 Rev Time 1.10
Received By pkrauss Date 2004-08-02 Time 07:16 Sent To  
Notes
2004-08-02 00:00:00REVISED PLAN SHEETS AC-3.1, 3.2, 4.1 &
 4.2; ELIMINATING EXHAUST DUCT FROM THE
 THIRD FLOOR GARAGE.MOVING GVEF-5 &
 GVEF-6 FROM THE FORTH FLOOR TO THE THIRD
 FLOOR OF THE GARAGE.
  
 REVISION SUBMITTED 7-14-04; PLAN SHEET
 AC-1.2A, REVISED UNDERGROUND EXHAUST
 DUCT.

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2004-07-22 Cont ID  
Sent By pkrauss Date 2004-07-22 Time 15:48 Rev Time 0.40
Received By pkrauss Date 2004-07-22 Time 15:48 Sent To  
Notes
2004-07-22 00:00:00REVISION / PLAN SHEET AC-1.2.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2004-06-09 Cont ID  
Sent By pkrauss Date 2004-06-09 Time 15:37 Rev Time 1.55
Received By pkrauss Date 2004-06-09 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2004-04-26 Cont ID  
Sent By pkrauss Date 2004-04-26 Time 08:46 Rev Time 0.55
Received By pkrauss Date 2004-04-26 Time 07:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 13:04 Rev Time 0.45
Received By pkrauss Date 2004-03-03 Time 12:50 Sent To  
Notes
2004-03-03 00:00:00REVISION FOR THE ELEV MACH RMS -
 CONDENSATE FOR FCU'S IN ELEV MACHINE RMS
 P-8.0, 8.1, 8.2 (NOT SUBMITTED WITH
 REVISIONS)

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-02-25 Cont ID  
Sent By pkrauss Date 2004-02-25 Time 12:52 Rev Time 0.45
Received By pkrauss Date 2004-02-25 Time 12:52 Sent To  
Notes
2004-02-25 00:00:00PROVISO:
 PLAN SHEET AC-201 GENERAL NOTES #7 (B),
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR THE INSULATION.WILL THIS BE
 INSTALLED IN A PLENUM?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2003-12-01 Cont ID  
Sent By hmoser Date 2003-12-01 Time 18:27 Rev Time 1.00
Received By hmoser Date 2003-12-01 Time 18:27 Sent To  
Notes
2003-12-01 00:00:00PLAN DENIED
 REVISED FLOOR PLAN AND ORIGNAL FLOOR
 PLAN DO NOT MATCH .PAGE A/C 120
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-04-15 Cont ID  
Sent By pkrauss Date 2003-04-15 Time 08:11 Rev Time 1.10
Received By pkrauss Date 2003-04-14 Time 16:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-02-28 Cont ID  
Sent By pkrauss Date 2003-02-28 Time 13:47 Rev Time 3.00
Received By pkrauss Date 2003-02-28 Time 13:47 Sent To  
Notes
2003-02-28 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.PLN SHEET AC-1.2, 18" X 12" O.A.
 DUCT TO FCU-11 APPEARS TO PENETRATE A
 RATED WALL, NO FIRE DAMPER INDICATED ON
 PLAN.
  
 2.PLANS INDICATE A DRYER BOOSTER FAN
 IN SOME OF THE APARTMENTS.
 A. PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE BOOSTER FAN. (UL LISTED)
 B. PLEASE INDICATE WHAT KIND OF
 PRECAUTIONS WILL BE TAKEN SHOULD
 THE BOOSTER FAN FAIL.
  
 3.PLEASE NOTE DRYERS TO BE INSTALLED
 FOR FINAL INSPECTION.
  
 4.FCU'S # 6,7,8, & 11, DUCT SMOKE
 DETECTORS REQUIRED ON SUPPLY AIR DUCT
 AS PER 2001 FBC(M) 606.2.1. (NO DUCT
 SMOKE DETECTORS ARE IDENTIFIED ON PLAN)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-01-06 Cont ID  
Sent By pkrauss Date 2003-01-06 Time 12:54 Rev Time 4.45
Received By pkrauss Date 2003-01-06 Time 08:37 Sent To  
Notes
2003-01-06 00:00:00DENIED:
  
 RESPONSE FROM RJP DATED 10/23/02, ONLY
 ADDRESSES COMMENTS FROM NANCY DEMMARK
 DATED 8/20/02.COMMENTS FROM PATTY
 KRAUSS DATED 10/08/02 WHERE NOT
 ADDRESSED.
  
 1.DRYER SCHEDULE ON PLAN SHEET AC-201
 INDICATES MAXIMUM LENGTH AS 35 FT WITH
 3 90 DEGREE BENDS, SOME UNITS AS SHOWN
 ON PLAN SHEET AC-116 ARE 36 TO 44 FT IN
 LENGTH WHICH EXCEEDS THE MAXIMUM LENGTH
 ALLOWED.
  
 2.OUTSIDE AIR CALCULATIONS FOR THE
 APARTMENTS IS ACHIEVED THROUGH RTUS 1-7
 WITH A TOTAL OF 23,800 CFM.CLARIFY
 HOW THE OUTSIDE AIR IS INTRODUCED INTO
 THE APARTMENT.PLANS DO NOT INDICATE
 ANY DUCTWORK OR SPECIFY HOW THE OUTSIDE
 AIR REQUIREMENT IS MET.
  
 3.LIFE SAFETY PLAN SHEET 1 IS NOT
 CLEAR AS TO THE SEPARATION BETWEEN THE
 APARTMENT & THE COMMERICAL SPACE.PLAN
 DOES NOT INDICATE THE RATING OF THE
 CORRIDOR, REF. LINE I & N.3 ON LS-1.
 DUCTS DO NOT INDICATE FIRE DAMPER AT
 THE CORRIDOR PENETRATION TO FCU-11.
  
 4.SHAFTS ARE NOT INDICATED ON MECH
 PLANS FIRE DAMPERS ARE SHOWN AT FLOOR
 PENTRATIONS, THIS IS ONLY ACCEPTABLE
 WHEN DUCT PENETRATES ONE FLOOR.IF
 DUCT PENETRATES MORE THAN ONE FLOOR A
 SHAFT ENCLOSURE IS REQUIRED AS PER 2001
 FBC(M) 607.4.PLEASE INDICATE ALL SHAFT
 ENCLOSURES ON THE PLAN.
  
 PLEASE NOTE:
 ACCESS FOR FCU (HORIZONTAL) SHALL BE
 LARGE ENOUGH TO REMOVE THE LARGEST
 PIECE OF EQUIPMENT (COIL, FAN, MOTOR).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-10-08 Cont ID  
Sent By pkrauss Date 2002-10-08 Time 16:26 Rev Time 6.00
Received By pkrauss Date 2002-10-08 Time 16:26 Sent To  
Notes
2002-10-08 00:00:00DENIED:
  
 RESPONSE TO COMMENTS FROM 1ST PLAN
 REVIEW BY NANCY DENMARK:
  
 3. PROVIDE INFORMATION ON PARKING
 GARAGE. RES: REFER TO REVISED
 VENTILATION LAYOUT ON DRAWINGS.
 PLEASE CLARIFY WHAT IS EXHAUST AND
 WHAT IS AIR MAKE UP.
  
 4. PROVIDE OUTSIDE AIR CALCULATIONS FOR
 THE APARTMENTS. RES: O.A CALCS DWG
 AC-201.THE SCHEDULE SEEMS TO
 INDICATE O.A. SUPPLIED FROM THE RTU'S
 SERVING THE CORRIDOR?
  
 6. 50 CFM PER TOILET FIXTURE OR URINAL
 PER TABLE 403.3 FBC(M). RES: SEE
 REVISED VENTILATION FAN SCHEDULE, DWG
 AC-201. PLEASE NOTE, PLAN SHEET AC1.0
 INDICATES EF-1 FOR THE LOBBY RESTROOM
 & EQUIPMENT SCHEDULE ON PLAN SHEET
 AC-201 LIST EF 3 & 4. PLEASE CLARIFY.
  
 9. RES: EQUIPMENT CLEARANCE NOTES HAVE
 BEEN ADDED ON DWGS AC-1.0 & AC-2.0.
 THERE IS NO NOTE ON PLAN SHEET AC-2.0
  
 11.DRYER DUCT LENGTHS SHALL NOT EXCEED
 MANUFACTURERS SPECS OR 25'. RES:
 DRYER PERFORMANCE SPECIFICATION HAS
 BEEN REVISED. PLEASE NOTE:
 A. MANUFACTURER SUBMITTAL FOR A
 SPECIFIC DRYER WAS NOT SUBMITTED.
 B. SOME OF THE APARTMENTS HAVE 3 - 90
 DEGREE BENDS IN THE RUN. ACCORDING
 TO THE SCHEDULE THE LENGTH DOES
 NOT MEET THE SCHEDULE REQUIREMENT.
 C. PLAN SHEET AC-201 IN THE NOTE
 SECTION - NOTE #7 C. SUBPARAGRAPH
 E. STATES THE EXHAUST SHALL NOT
 EXCEED 25 FT.
  
 NEW NOTES BY PATTY KRAUSS
 1.O.A. DUCT TO FCU-11 PENETRATES A
 RATED WALL, ALSO THE SUPPLY & RETURN
 PENETRATING THE CORRIDOR WALL TO THE
 PACKAGE STO.- NO FIRE DAMPERS ARE
 SHOWN ON THE PLAN. PLEASE CLARIFY.
  
 2.CLARIFY 6" A.F.F. (3) 5'X3' 11,670
 CFM EACH, ARE THESE GRILLES GOING
 INTO A "SHAFT" ARE THEY EXHAUST OR
 FRESH AIR MAKE-UP?
  
 3.PLAN SHEET AC-1.1 DUCT PENETRATING
 "DOMESTIC WATER PUMP" ROOM - THESE
 WALLS HAVE A 2 HR RATING. NO DAMPER
  
 4.CLARIFY FIRE DAMPER AT THE FLOOR, IS
 THIS DUCT PENETRATING ONLY ONE FLOOR
 OR IN A SHAFT?
  
 5.PLEASE INDICATE ON MECHANICAL PLANS
 WHAT WILL BE RUN IN A RATED SHAFT
 I.E. DUCTS FROM RTU'S, REFRIGERATION
 LINES, PIPES, DUCTS, ETC.PLEASE
 PROVIDE A DETAIL AND UL# SHOWING
 CONTRUCTION OF SHAFT.SHOULD THE
 DETAIL BE SHOWN IN THE ARCHITECTURAL
 PLEASE REFERENCE THE PLAN SHEET.
  
 6.PLAN SHEET AC-202 ROOFTOP EQUIPMENT
 HEIGHT REQUIREMENT.SCHEDULE SHOWS
 THE HEIGHT REQUIREMENT MEASURING '
 THE LEG LENGTH OF THE STAND. THE
 CODE STATES FROM THE ROOF SURFACE.
 SEE 2001 FBC TABLE 1511.7.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR THE RTU'S SERVING THE
 COMMON CORRIDORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-20 Cont ID  
Sent By ndenmark Date 2002-08-20 Time 08:58 Rev Time 3.00
Received By ndenmark Date 2002-08-20 Time 08:58 Sent To  
Notes
2002-08-20 00:00:00DENIED:
  
 1. PROVIDE INFORMATION ON FIRST LEVEL
 COMMON AREA AND RETAIL VENTILATION.
 2. PROVIDE INFORMATION ON REQUIRED
 VENTILATION FOR SERVICE ROOMS, I.E.
 ELECTRICE, PHONE, CATV, MAINT SHOP ETC.
 3. PROVIDE INFORMATION ON PARKING GARAGE
 VENTILATION.
 4. SHOW OUTSIDE AIR SCHEDULE FOR ALL
 SPACES INCLUDING APARTMENTS AND DUCT
 PATH FOR PROVIDING AIR.
 5. PROVIDE AIR BALANCE CALCULATIONS
 SHOWING COMPLIANCE WITH 2001 FBC(M)
 601.4 AND 501.4.
 6. OUTSIDE AIR INFORMATION PROVIDED
 INDICATES OTHER THAN REQUIRED 50 CFM
 PER TOILET FIXTUR OR URINAL PER TABLE
 403.3 FBC(M).
 7. SHOW REQUIRED OUTSIDE AIR QUANTITIES
 ON EQUIPMENT SCHEDULE.
 8. AIR HANDLER SCHEDULE DOES NOT SHOW
 FCU-5 (OFFICES), FCU-6(GYM), OR
 FCU-7(RECREATION HALL). FCU-7 ON
 SCHEDULE INDICATES THIS UNIT IS FOR
 APARTMENTS.
 9. ALL EQUIPMENT SHALL BE LOCATED WITH
 RESPECT TO BUILDING CONSTRUCTION TO
 ALLOW FOR SERVICE AND REPLACEMENT,
 INCLUDING CLEARANCE FROM FIRE SPRINKLER
 LINES, PLUMBING AND ELECTRICAL. SHOW
 REQUIRED CLEARANCE AREAS ON PLAN.
 10. FBC 13 610.1.ABC.3.0.3 REQUIRES 4 "
 MINIMUM CLEARANCE AROUND AIR HANDLERS
 AND DUCT ATTACHMENT FOR ACCESS.
 11. DRYER DUCT LENGTHS SHALL NOT EXCEED
 MANUFACTURS SPECS OR 25' CODE MAX. APT.
 B-2 EXCEEDS EVEN MAUFACTURES ALLOWABLE
 SHOWN ON PLAN. PROVIDE SPECIFIC WALL
 CAP TO BE USED AND MANUFACTURES SPEC'S
 SHOWING ALLOWABLE LENGTH FOR WALL CAP.
 12. PRESSURE TEST WILL BE REQUIRED ON
 ALL REFRIGERANT LINES (NITROGEN)
 13. WHERE WILL KITCHEN HOOD GREASE DUCT
 TERMINATE, SHOW DETAILS.
 14. EMERGENCY GENERATOR WILL REQUIRE
 SEPARATE PERMIT AND PLANS AND A
 SEPARATE FUEL PERMIT.
 15. KITCHEN HOOD, WALK IN COOLERS AND
 FREEZERS AND FIRE SUPPRESSION SYSTEM
 FOR HOOD WILL REQUIRE SEPARATE PERMITS
 AND PLANS TO BE SUBMITTED.

Review Stop P PLUMBING
Rev No 14 Status F Date 2005-06-27 Cont ID  
Sent By kstevens Date 2005-06-27 Time 18:07 Rev Time 1.50
Received By kstevens Date 2005-06-27 Time 18:07 Sent To  
Notes
2005-06-27 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-120 ALL CHANGES MADE TO THE
 LAYOUT OF THE MEN'S AND WOMEN'S
 BATHROOMS SHALL BE REFLECTED IN A
 REVISION OF THE ARCHITECTURAL SHEETS.
 SECTION 104.2.1.
 2. SHT P-120 WATER PIPING ISOMETRIC:
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN FOR FIXTURE
 P-7. PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
 3. SHT P-120 WATER PIPING ISOMETRIC: THE
 DISCHARGE OF THE RELIEF VALVE SHALL NOT
 HAVE ANY TRAPPED SECTIONS, AND SHALL
 HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. SECTION 504.7.1
 4. THE STEAM GENERATORS SHALL BE
 INSTALLED IN A GALVANIZED STEEL OR OTHER
 METAL PAN OF EQUAL CORROSION RESISTANCE
 HAVING A MINIMUM THICKNESS OF 24 GUAGE.
 INDICATE THE PAN DRAIN PIPING ON
 REVISION. SECTION 504.8.
 5. INDICATE THE MATERIAL FOR THE RVD
 PIPING AND THE EMERGENCY PAN DRAIN FOR
 THE STEAM GENERATORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 13 Status P Date 2004-09-23 Cont ID  
Sent By kstevens Date 2004-09-23 Time 17:48 Rev Time 1.25
Received By kstevens Date 2004-09-23 Time 17:48 Sent To  
Notes
2004-09-23 00:00:00REVISION OK - SHTS P-1.0, P-1.3, P-206,
 AND P-208

Review Stop P PLUMBING
Rev No 12 Status P Date 2004-04-17 Cont ID  
Sent By kstevens Date 2004-04-17 Time 17:52 Rev Time 2.00
Received By kstevens Date 2004-04-17 Time 17:52 Sent To  
Notes
2004-04-17 00:00:00REVISION OK - SHTS P-5.3 & P-207 AREA
 DRAIN FOR 5TH FLOOR

Review Stop P PLUMBING
Rev No 11 Status P Date 2004-04-09 Cont ID  
Sent By kstevens Date 2004-04-09 Time 16:11 Rev Time 1.00
Received By kstevens Date 2004-04-09 Time 16:11 Sent To  
Notes
2004-04-09 00:00:00REVISION OK - SHEETS P1.13, P208.0 &
 P208.1

Review Stop P PLUMBING
Rev No 10 Status N Date 2004-02-19 Cont ID  
Sent By kstevens Date 2004-02-19 Time 17:47 Rev Time 0.25
Received By kstevens Date 2004-02-19 Time 17:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 9 Status F Date 2004-02-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 17:44 Rev Time 0.50
Received By kstevens Date 2004-02-17 Time 17:44 Sent To  
Notes
2004-02-17 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM ON SHT P-208.0
 AND FIRST LEVEL PLUMBING ON SHT P-1.3 DO
 NOT MATCH.
 - SHT P1.3 SHOWS RISERS S/35 & S/16 AT
 REVISION #7 AND SHT P-208.0 BLDG. DRAIN
 ISOMETRIC SHOW RISERS S/33 & S/29.
 PLEASE CLAIRFY.
 2) SHT P-208.1 RISER S/20 - INDICATE
 WHAT RISER "W" IS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2003-12-29 Cont ID  
Sent By kstevens Date 2003-12-29 Time 10:32 Rev Time 6.00
Received By kstevens Date 2003-12-17 Time 17:08 Sent To  
Notes
2003-12-29 00:00:00REVISION OK - SHEETS P-1.3, SHT P-208.0,
 AND SHT P-208.1 CLAIRIFICATION AND MORE
 INFORMATION REQUIRED - REVISION REQUIRED
 FOR THESE THREE SHEETS.

Review Stop P PLUMBING
Rev No 7 Status F Date 2003-12-05 Cont ID  
Sent By kstevens Date 2003-12-05 Time 13:25 Rev Time 24.00
Received By kstevens Date 2003-12-05 Time 13:24 Sent To  
Notes
2003-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS P-1.3 & P-208.0 RELIEF VENT RE-
 QUIRD FOR AAV IN TRASH ROOM. SEC 917.3.2
 2) SHT P-1.3 CLAIRFY THIRD RISER NEXT TO
 AAV AT TRASH ROOM. MAIN DRAIN ISOMETRIC
 DIAGRAM ONLY SHOWS 2/29 & S/33. SECTION
 104.2.1
 3) SHT P-3.1 IDENTIFY RISERS COL. LINE G
 SHT P-1.4 SHOWS S/3 AS CENTER RISER, BUT
 RISER DIAG. SHOWS S/8 AS CENTER RISER.
 PLEASE CLAIRFY. SEC 104.2.1
 4) SHT P-1.3 CLEANOUTS REQUIRED MINIMUM
 100'. SECTION 708.3.2
 5) SHTS P-1.4 & P-208.0 IDENTIFY RISER
 AT COL. LINE N.12. SECTION 104.2.1
 6) SHTS P-1.4 & P-208.0 SANT. RISER DOES
 NOT REFLECT THE FLOOR PLAN AT RISERS S/7
 S/7, S/3A, & S/1A. RISER SHOWS 2 RISERS,
 AND FLOOR PLAN SHOWS 1 RISER. PLEASE
 CLAIRFY. SECTION 104.2.1
 7) SHTS P-1.4 & P-208.0 RELIEF VENT REQ-
 UIRED FOR AAV IN FIRE PUMP ROOM. SECTION
 917.3.2
 8) SHT P-1.4 CLEANOUTS REQUIRED NEAR COL
 LINES S.7 & C AND S.20 & C. SEC 708.3.2.
 9) SHT P-1.5 CLEANOUT SHOWN ON RISER BUT
 NOT ON FLOOR PLAN NEAR COL. LINE S.43
 BETWEEN C & D. PLEASE CLAIRFY. 104.2.1
 10) SHTS P-1.5 & P-208.0 RISER DOES NOT
 REFLECT THE FLOOR PLAN AT TRASH ROOM.
 RISER SHOWS 2 RISERS AND NO AAV, FLOOR
 PLAN SHOWS SINGLE RISER WITH AN AAV.
 PLEASE CLAIRFY. 104.2.1 - RELIEF VENT
 REQUIRED FOR AAV. SEC 917.3.2
 11) SHT P-2.1 SANT. RISER NOT IDENTIFIED
 BETWEEN COLS. N.13 & N.14 BY STAIR #3.
 104.2.1
 12) MANY SHEETS, THE REVISION NUMBERS DO
 NOT MATCH REVISION CALLD OUT, AND MANY
 REVISIONS HAVE NO REV. NUMBER AT ALL.
 PLEASE CLAIRFY. 104.2.1
 13) MANY SHEETS SANT. RISER NUMBER IS
 SUPERIMPOSED OVER OTHER INFORMATION SO
 THE NUMBER CAN NOT BE READ. 104.2.1
 14) SHT P-2.2 STUDIOS 1, 2, & 3. SANT.
 RISERS, NEW RISERS ADDED AND SUPERIMPOS-
 ED OVER OLD RISER NUMBERS MAKING IT SO
 THE RISER NUMBERS CAN NOT BE READ.
 15) SHT P-6.2 REVISION 5 SHOWN. PLEASE
 CLAIRFY. 104.2.1
 16) SHT P-7.2 REVISION 2 SHOWN. IS THIS
 A NEW REVISION? PLEASE CLAIRFY. 104.2.1
 17) SHTS P-100 THRU P-119 INDICATE RISER
 NUMBERS FOR ALL UNITS. 104.2.1
 18) SHT P-119 STUDIO #6 SHOWS S/13A, &
 S/21. THESE RISERS ARE NOT FOUND ON THE
 RISER SHEETS. ALSO RISER S/5A SHOWS A
 KITCHEN SINK W/DISHWASHER, AND FLOOR
 PLAN SHOWS A TUB. PLEASE CLAIRFY. SECT-
 ION 104.2.1
 19) SHT P-208.0 SANITARY RISERS SHOWN UP
 TO S/17, BLDG DRAIN ISOMETRIC AND FLOOR
 PLAN SHEETS SHOW RISERS UP TO S/39. PRO-
 VIDE ALL MISSING SANT. RISER DIAGRAMS
 FOR REVIEW. SEC 104.2.1
 20) SHTS P-120, P-203, P-204, & P-205
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUFACTURE INSTALLATION INSTRUCTIONS.
 21) SHT P-200 OFFSET VENTS REQUIRED FOR
 SANT. RISERS S/1B, S/2C, & S/7A. SECTION
 915.
 22) SHT P-201, SHOW VENT SIZE FOR MAIN
 VENT FOR WASH MACHINES ON RISER S/17 PER
 TABLE 916.1.
 23) SHT P-200 SANT. RISERS S/2, S/2A, &
 S/2B, RELIEF VENTS REQUIRED FOR AAV'S
 BELOW THE 5TH FLOOR. SEC 917.3.2
 24) SHT P-200 SANT RISER S/1B RELIEF
 VENT REQUIRED FOR AAV BELOW 5TH FLOOR.
 SECTION 917.3.2
 25) SHT P-200 RISER S/5 NOT FOUND ON 1ST
 FLOOR BLDG DRAIN ISOMETRIC SHT P-208.0
 26) SHT P-202 RPZ BACKFLOW REQUIRED ON
 THE TRASH CHUTE RING. SEC 608.13.2
 27) SHT P-202 RELIEF VALVE DISCHARGE,
 (P/T) AND PAN DRAIN LINE SHALL DRAIN
 SEPARATELY. SECTION 504.7 - 504.7.1
 28) SHT P-202 RAIN WATER LEADER NOT SIZ-
 ED PROPERLY FOR HORIZONTAL OFFSETS.
 TABLE 1106.3
 29) SHT P-208.1 IDENTIFY ALL FIXTURES.
 BATHROOM BY RISER S/7B INDICATES KITCHEN
 SINK DRAINING THRU BATHROOM GROUP WET
 VENT, WHICH IS NOT ALLOWED PER SECTION
 909.1. BATHROOM BY S/8, S/11, S/5 INDI-
 CATES LAV, BUT PIPED LIKE A TUB OR SHR.
 PLEASE CLAIRFY. 104.2.1
 30) SHT P-208.0 SHOW FIXTURE UNITS ADDED
 AT THE BASE OF EACH RISER, AND AS THEY
 ACCUMULATE IN THE SANT. SYSTEM TO CHECK
 THE PIPE SIZING OF BLDG DRAIN. 104.2.1
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2003-10-07 Cont ID  
Sent By kstevens Date 2003-10-07 Time 09:56 Rev Time 2.50
Received By kstevens Date 2003-10-07 Time 09:56 Sent To  
Notes
2003-10-07 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) UNABLE TO COMPLETE REVISION REVIEW.
 MORE INFORMATION REQUIRED. ALL FLOORS
 SHALL BE REVISED TO SHOW NEW LOCATION OF
 ALL RISERS CHANGED AND NEW RISERS ADDED.
 2) SHT P-1.3 CHANGES TO THE SANITARY
 BUILDING DRAIN SHALL BE REFLECTED IN THE
 SANITARY ISOMETRIC FOR THE BLDG. DRAIN.
 SEC 104.2.1
 3) SHT P-1.3 SECTION 104.2.1.3 BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM OF 1/8
 INCH SCALE. SANITARY LINES ARE FAINT AND
 BLDG LINES ARE BOLD MAKING IN VERY HARD
 TO FOLLOW SANITARY LINES.
 4) SHT P-1.3 UNABLE TO FIND SANT. RISERS
 5, 5A, & 5B
 5) ALL SHEETS - CLOUDED CHANGES REQUIRED
 FOR REVISION
 6) SHT P200 RISERS S/2C, S/1B, & S/7A
 REQUIRE OFFSET VENTS. SECTION 915
 7) THERE MAY BE MORE COMMENTS UPON COM-
 PLETION OF SUBSEQUENT REVIEW ACCORDING
 TO INFORMATION RECIEVED NEXT REVISION
 SUBMITTAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-04-12 Cont ID  
Sent By kstevens Date 2003-04-12 Time 09:16 Rev Time 2.00
Received By kstevens Date 2003-04-12 Time 09:15 Sent To  
Notes
2003-04-12 00:00:00PASSED/PROVISO
  
 REVISIONS REQUIRED - SHT P-208.0 AND SHT
 P1.2 DO NOT MATCH. SEE RED LINES ON SHT
 P-208.0 FOR AREA OF CORRECTION.
 REVISION REQUIRED FOR SHT P-201. RISER
 S/21, SEE RED LINE FOR CHANGE REQUIRED.

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-03-12 Cont ID  
Sent By kstevens Date 2003-03-12 Time 12:22 Rev Time 6.00
Received By kstevens Date 2003-03-11 Time 18:57 Sent To  
Notes
2003-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FHA-AMEND. 98 DESIGN MANUAL
  
 1) NEW PLUMBING SHEETS FOR REVIEW - NEW
 PLAN REVIEW.
 2) SHT P.208 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLAT LAYOUT ON SHTS P-1.0,
 P-1.1 & P-1.2. SOME RISERS NOT SHOWN ON
 RISER DIAGRAM. PLEASE CORRELATE RISER
 WITH FLAT LAYOUT.
 3) SHTS P-1.0, P-1. P-1.2 & P.208 -
 CLEANOUTS REQUIRED ON HORIZONTAL BLDG
 DRAIN. MAXIMUM 100' APART. SEC 708.3.1
 AND AT CHANGE OF DIRECTION GREATER THAN
 45 DEGREES. SEC 708.3.3. ALSO REQUIRED
 AT BASE OF STACK SEC 708.3.4
 4) SHT A.112A UNITS B7, & B71, SPECIFIC-
 ATION "A" OR "B" TO BE INDICATED.
 5) SHT A.113 UNITS B6, B61, & B62, CLEAR
 FLOOR SPACE NOT SHOWN.
 6) SHTS P-203, P-204, & P-205, AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DE-
 LETE FROM WATER RISER DIAGRAMS.
 7) PLEASE SUBMIT CALCULATIONS FOR CON-
 DENSATE DISCHARGE FOR EACH A/C UNIT TO
 ESTABLISH DRAINAGE FIXTURE UNITS FOR
 CONDENSATE PIPE SIZING.
 8) SANITARY RISERS S/17 & S/21, ONLY
 THE FIXTURES FROM THE BATHROOM GROUP
 SHALL DRAIN INTO THE WET VENT. TIE
 KITCHEN SINK DOWNSTREAM OF BATHROOM
 GROUP ON THESE RISERS.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-12-30 Cont ID  
Sent By kstevens Date 2002-12-30 Time 11:36 Rev Time 1.00
Received By kstevens Date 2002-12-30 Time 11:36 Sent To  
Notes
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11 FHA
  
 1) FROM PREVIOUS REVIEWS: SHEET A-118
 BACKING FOR TUBS, SHOWERS ECT., NO MEAS-
 UREMENTS ARE SHOWN ON PAGE. PLEASE SHOW
 REQUIRED MEASUREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-10-07 Cont ID  
Sent By kstevens Date 2002-10-07 Time 15:19 Rev Time 0.00
Received By kstevens Date 2002-10-05 Time 14:04 Sent To  
Notes
2002-10-07 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FHA AMEND-98 DESIGN MANUAL
  
 1) PLANS FOR POOL TOILET ROOM FACILITIES
 WILL BE ROUTED TO THE HEALTH DEPT WHEN
 THE POOL PERMIT IS APPLIED FOR.
 2) NO GREASE TRAP REQUIRED - CLICK CAFE
 IS ONLY A COFFEE HOUSE. NO FOOD SERVICE.
 3) FROM PREVIOUS REVIEW: SHTS A.93 THRU
 A-116 ALL UNITS SHALL COMPLY WITH RE-
 QUIREMENTS 1 THRU 7 AND SPECIFY SPECIFI-
 CATION "A" OR "B" AS REQUIRED FOR EACH
 UNIT ON PLANS. FHA DESIGN MANUAL
 4) FROM PREVIOUS REVIEW: SHT A.118 BACK-
 ING FOR TUBS AND SHOWERS SHALL COMPLY
 WITH FHA-98 DESIGN MANUAL. SHOW HEIGHT
 OFF FLOOR TO BOTTOM OF BACKING& HEIGHT
 & WIDTH OF ALL BACKING.
 5) FROM PREVIOUS REVIEW: PLEASE INDICATE
 WHERE RISER (S/23) IS LOCATED. UNABLE TO
 LOCATE BACK TO BACK P-5'S SHOWN ON RISER
 DIAGRAM.
 6) FROM PREVIOUS REVIEW: PLEASE SUBMIT A
 CONDENSATE RISER DIAGRAM FOR THE HORIZON
 TAL DRAIN AND RISERS. SHOW PIPE SIZES &
 TERMINATION. CONDENSATE SHALL TIE INTO
 THE STORM SYSTEM OR CATCH BASIN OUTSIDE
 THE BLDG. PLEASE SHOW REQUIRED RELIEF
 VENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-22 Cont ID  
Sent By kstevens Date 2002-08-22 Time 17:48 Rev Time 0.00
Received By kstevens Date 2002-08-19 Time 17:30 Sent To  
Notes
2002-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PLEASE ROUTE PLANS TO THE PALM BEACH
 COUNTY HEALTH UNIT DIVISION OF ENVIRON-
 MENTAL HEALTH 901 EVERNIA STREET WPB
 (561) 355-3018 FOR REVIEW OF THE POOL
 BATHROOM FACILITIES.
 2) POOL SEPARATE PERMIT FOR POOL/PLUMB-
 ING AND ELECTRIC.
 3) BACKFLOW FOR ENTRANCE FOUNTAIN REQUIR
 ED.
 4) GREASE TRAP FOR FUTURE "CLICK CAFE"
 PLEASE CONTACT RODNEY COMPO, ENVIRONMEN-
 TAL COMPLIANCE MANAGER FOR SIZE OF TRAP.
 (561) 837-4074-WASTE ORD. #2938-96
 5) SHT A.62 POOL TANK DRAIN SHALL DRAIN
 TO SANITARY.
 6) PLEASE PROVIDE INFORMATION FOR POOL
 EQUIPMENT ROOM.
 7) SHT A.62 SUBMIT MANUF. INFO. FOR
 STEAM UNIT. SHOW PIPING FOR T/P RELIEF
 DRAIN.
 8) SHTS A.93 THRU A-116 ALL UNITS SHALL
 COMPLY WITH REQUIREMENTS 1 THRU 7 AND
 SPECIFY SPECIFICATION "A" OR "B" FOR
 EACH UNIT ON PLANS. FHA AMEND-98 DESIGN
 MANUAL.
 9) SHT A.118 BACKING FOR TUBS AND SHOW-
 ERS SHALL COMPLY WITH FHA-98 DESIGN MAN-
 UAL. SHOW HEIGHT OFF FLOOR TO BOTTOM &
 HEIGHT AND WIDTH OF ALL BACKING.
 10) SHT P-5.3 FOUNTAIN SHALL DRAIN TO
 SANITARY SYSTEM NOT TO STORM
 11) SHT P-115 UNIT B3 - 6' MAXIMUM DIS-
 TANCE FROM TRAP OF SHOWER TO VENT. TABLE
 906.1
 12) SHT P-117 5TH THRU 7TH & 8TH LEVEL
 FLOOR PLAN PIPING NOT SHOWN FOR C1 UNITS
 13) SHT P-120 PLEASE SUBMIT DETAIL FOR
 SHOWERS PER 11-4.21 AND ALL SUBSECTIONS.
 - WATER PIPE ISOMETRIC - WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" PER PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS
 NOT AT THE TOP OF DROP AS SHOWN.
 - PLEASE IDENTIFY FIXTURE P-7 - ITS NOT
 SHOWN ON SHT P-208 ON FIXTURE SCHEDULE.
 14) SHT P-200 SHTACK S/1, S/1A, & S/1C
 SHOWS P-4 (SHOWER) WITH DW DRAINING INTO
 THEM. PLEASE CLAIRFY. IF THEY ARE KITCH-
 EN SINKS, THEN 2" PIPE STACK IS NOT
 LARGE ENOUGH AND 3" IS REQUIRED. TABLE
 910.4
 15) SHTS P-4.2, P-5.0 (THREE SHEETS WITH
 SAME P NUMBER), SECOND AND THIRD, P-6.1,
 & P-7.1 DO NOT REFLECT THE SANITARY RIS-
 ER #23. RISER SHOWS BACK TO BACK TRAPS,
 BUT FLOOR PLAN DOES NOT REFLECT THIS.
 PLEASE CLAIRFY.
 16) SHTS P-102, P-103 & P-104 SHOW RISER
 S/23B, BUT NO RISER S/23B SHOWN ON RISER
 SHEETS.
 17) SHTS P-107 THRU P-119 PLEASE IDENTI-
 FY THE RISERS IN THESE UNITS.
 18) SHT P-117 NO PIPING LAYOUT SHOWN FOR
 UNITS C1A & C1A.2
 19) SHT P-203 WATER ISOMETRICS ALL UNITS
 AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMMER ARRESTORS ARE REQUIRED FOR ALL
 QUICK CLOSING VALVES PER SEC 604.9.
 (WASH MACHINES, ICE MAKERS (REFG.) &
 THE DISHWASHER.) THEY SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS AS SHOWN. PDI-WH
 201 & MANUF INSTALL. INSTRUCTIONS.
 20) SHT P-208 GENERAL PLUMBING NOTES:
 #1E 3" AND LARGER PIPE SHALL BE RUN AT
 1/8" PER FOOT AND 2-1/2" AND SMALLER
 PIPE SHALL BE RUN AT 1/8" PER FOOT. PER
 TABLE 704.1
 21) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM FOR THE BLDG DRAIN. SHOW ALL RISERS
 AND THE ACCUMULATED DFU'S, AND PIPE SIZE
 22) PLEASE PROVIDE A STORM RISER FOR THE
 HORIZONTAL DRAIN. SHOW ALL RISERS AND
 ACCUMULATED SQUARE FOOTAGE, AND SHOW
 PIPE SIZE.
 23) PLEASE PROVIDE A WATER RISER DIAGRAM
 WITH ALL PIPE SIZES. SHOW WHERE IT ENT-
 ERS THE BLDG AND ALL HORIZONTAL PIPING
 TO RISERS.
 24) PLEASE PROVIDE A CONDENSATE RISER
 DIAGRAM FOR THE CONDENSATE HORIZONTAL
 DRAIN. SHOW PIPE SIZES AND TERMINATION.
 COND. SHALL TIE INTO STORM OR CATCH
 BASIN OUTSIDE BLDG. RELIEF VENT REQD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 6 Status P Date 2005-12-01 Cont ID  
Sent By astelly Date 2005-12-01 Time 14:00 Rev Time 0.00
Received By astelly Date 2005-12-01 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2004-03-30 Cont ID  
Sent By aaponte Date 2004-03-30 Time 08:35 Rev Time 0.00
Received By aaponte Date 2004-03-30 Time 08:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2004-02-09 Cont ID  
Sent By mmclean Date 2004-02-09 Time 16:49 Rev Time 0.00
Received By mmclean Date 2004-02-09 Time 16:48 Sent To  
Notes
2004-02-09 00:00:00OK PER SHIRLY GRAHAM PLANNER 659-8031
 CALLED MIKE FILE C MM

Review Stop Z ZONING
Rev No 3 Status P Date 2003-04-29 Cont ID  
Sent By sgraham Date 2003-04-29 Time 11:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-04-15 Cont ID  
Sent By sgraham Date 2003-04-15 Time 09:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-04-15 00:00:00DENIED, SEE ATTACHED LIST
 1. SHEET A.01A- THE GROSS BLDG SQ FT
 ABOVE THE 5TH FL IS DIFFERENT ON THE
 OPEN SPACE CALUCATION FROM THE FIGURE
 USED ON THE AFFORDABLE HOUSING TABLE.
 2. SHEET A.02-SHOWS A CONTINOUS LAND-
 SCAPE AREA BETWEEN THE ARCADE ON
 HIBISCUS AND ON-STREET PARKING. SHEET
 SP-1 SHOWS NO LANDSCAPE IN THIS AREA
 PLEASE REVISE THESE SHEETS TO SHOW
 FULL S/W WITH LANDSCAPE UNITS(CAN BE IN
 POTS) AS REQUIRED IN ARTIV SECT94-113(H)
 (4).
 3.BALCONY REQUIREMENTS: PLEASE REFER TO
 PAGES 12 & 13 OF ARCHITECTURAL DESIGN
 GUIDELINES. IN ACCORDANCE WITH B3.8,
 BRACKETS MUST VISUALLY SUPPORT BALCONIES
 THAT PROJECT OUT FROM THE BLDG FACADE
 A. SHEETA-46 & A-46A. NEW SOUTH
 TANGLEWOOD ELEVATION DOES NOT SHOW ANY
 BRACKETS ON PROJECTING BALCONIES. SECT
 D/A.56 DOES NOT SHOW BRACKETS AT 2ND
 FLOOR. SECT C/A.56 DOES NOT HAVE
 BRACKETS.
 4. WINDOWS- SHOULD BE CLEAR AND NOT TINT
 ED. ARCHITECT HAD INDICATED PREVIOUSLY
 THAT A SAMPLE OF GLASS WOULD BE BROUGHT
 IN FOR REVIEW OF THIS CRITERION.

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-07 Cont ID  
Sent By sgraham Date 2002-08-07 Time 08:01 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-20 00:00:00 
 DENIED, SEE ATTACHED LIST BY AG
2002-08-07 00:00:00SEND TO ZONING FOR REVIEW LAST,URBAN
 DESIGN STAFF OUT OF THE OFFICE THIS
 WEEK.


Account Summary | Usage Policy | Privacy Policy