Plan Review Details - Permit 02080494
Plan Review Stops For Permit 02080494
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-21 Cont ID  
Sent By btrobaug Date 2002-08-21 Time 12:29 Rev Time 0.25
Received By btrobaug Date 2002-08-21 Time 12:17 Sent To R
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-12 Cont ID  
Sent By dpalmer Date 2003-03-12 Time 06:02 Rev Time 0.00
Received By dpalmer Date 2003-03-07 Time 06:02 Sent To M
Notes
2003-03-12 00:00:00TO HM`S DESK,
 REV WAS IN RESUB'S.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2003-01-30 Time 14:44 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 12:22 Sent To R
Notes
2002-10-31 00:00:00TO JULIO./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-03-14 Cont ID  
Sent By rregueir Date 2003-03-14 Time 19:20 Rev Time 0.33
Received By rregueir Date 2003-03-14 Time 19:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-02-22 Cont ID  
Sent By dpalmer Date 2003-03-12 Time 06:02 Rev Time 0.33
Received By rregueir Date 2003-02-22 Time 12:18 Sent To  
Notes
2003-02-22 00:00:00REVISED MECH PLAN SUBMITTED 1/27/03
 RVEISED PLAN REVIEW:FAILED
 NO ENERGY CALCS PROVIDED WITH MASTER
 PLAN. FOR MORE INFORMATION SEE BUILDING
 PLAN REVIEW PROVISO.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-17 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 14:44 Rev Time 0.50
Received By hmoser Date 2002-08-17 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-17 Cont ID  
Sent By jleech Date 2002-08-17 Time 10:46 Rev Time 0.33
Received By jleech Date 2002-08-17 Time 10:46 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-11-01 Cont ID  
Sent By jgomez Date 2002-11-01 Time 17:52 Rev Time 2.50
Received By jgomez Date 2002-11-01 Time 17:52 Sent To  
Notes
2002-11-01 00:00:00APPROVED WITH PROVISO:
 1-STORM SHUTTERS: A)DESIGN PRESSURES
 SPECIFIED HAVE LIMITATIONS ON THE
 STORM PANEL MAX. SPAN. SEE PLANS FOR
 CALCULATED DESIGN PRESSURES AND REVISE
 AS REQUIRED.
 B)CLARIFY WHICH TYPE OF ANCHOR IS USED
 RAWL OR CAULK-IN?
 C)CIRCLE/IDENTIFY ON STORM PANEL DWGS
 INSTALLATION SCHEDULE ANCHOR TYPE AND
 SPACING TO BE USED.
 2-TRUSS ANCHOR SCHEDULE WAS REVISED ON
 SHEET S-3 BUT NOT ON SHEET S-2.
 3-REVISED ENERGY CALCULATIONS WERE NOT
 RE-SUBMITTED. (THERE IS NOT ADJACENT
 FRAMING, BUT MASONRY AND OWNER/AGENT
 TO DATE BOTTOM OF FORM AS WELL).

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-17 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 12:23 Rev Time 3.00
Received By jgomez Date 2002-09-17 Time 16:35 Sent To  
Notes
2002-09-17 00:00:00CHECKLIST:
 1-PROVIDE ENGINEERING ANALYSIS/CALCS
 SHOWING HOW THE FLOOR & ROOF DIAPHRAGM
 TRANSFER ALL LOADS CONSIDERING THE
 DOUBLE CEILING AREA AND FLOOR WOOD
 COLUMNS SUPPORTS WITH TOP AND BOTTOM
 CONNECTORS THAT DON'T PROVIDE RESIS-
 TANCE TO LATERAL FORCES. SEC. 1606.2.4
 FBC 2001 AND SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS. SEE LIMITATIONS ON
 PRODUCT APPROVAL SUBMITTED.
 4-PROVIDE LEGIBLE PRODUCT APPROVAL FOR
 GARAGE DOORS.
 5-SPECIFY FIREBLOCKING MATERIAL & LOCA-
 TION AT STAIRS. SEE SEC. 2305.1.4 FBC.
 6-PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEC. 2305.1.4 FBC 2001.
 7-SHEET C-1: REVISE FOUNDATION NOTE. USE
 0.006 MIL VISQUEEN. SEC. 1909.2 FBC.
 8-PROVIDE SAFETY GLASS IN WINDOW AT 1ST.
 FLOOR BATHROOM. SEC. 2405.2 FBC 2001.
 9-PROVIDE STRUCTURAL DETAIL FOR RECESSED
 WINDOWS TO ALLOW FOR STORM SHUTTERS
 INSTALLATION. SEE PRODUCT APPROVAL FOR
 REQUIRED ENGINEERING.
 10-24SH WINDOW AT MASTER BEDROOM DOESN'T
 ALLOW 24" MIN. CLEAR HEIGHT AND 5.7S.F
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC.
 11-REVISE NOTE #1 ON STAIR KEY NOTES.
 HEIGHT OF HANDRAIL TO BE BET. 34" AND
 38" HIGH MAX. SEE SEC. 1007.5.1 FBC.
 12-SHEET A-7: A)SOME INFORMATION IS OVER
 LAPPING. B)NOTE #9: REVISE SIZE OF
 LEDGER. SEE 2ND. FLOOR FRAMING PLAN.
 C)REVISE HANDRAIL HEIGHT ON STAIR
 SECTION AS WELL.
 13-SHEET S-1: A)CLARIFY REINFORCING FOR
 FOOTING F5530. B)LINTEL SCHEDULE DOES
 NOT MATCH PLANS. REVISE AS REQUIRED.
 14-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEC. 2305.4
 15-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED VALUES OR PROVIDE
 ENGINEERED CALCS FOR DIFFERENT VALUES.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-SHEET S-2: SECTION 1 AND SECTION 2
 HAVE DIFFERENT SPECS. REVISE AS REQ'D
 17-ROOF SHEATHING & NAILING STATEMENT &
 DIAPHRAGM SCHEDULE HAVE DIFFERENT
 SPECS. CLARIFY/REVISE AS REQUIRED.
 18-IDENTIFY ROOF NAILING ZONES. TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
 19-SPECIFY CONNECTORS FOR GIRDER TRUSS
 AT GARAGE ROOF FRAMING PLAN. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 20-REVISE ENERGY CALCULATIONS:
 A)THERE IS NOT ADJACENT FRAMING, BUT
 ADJACENT MASONRY.
 B)OWNER/AGENT TO DATE BOTTOM OF FORM
 WHEN SIGNING IT.
 21-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK REQUIREMENTS & REVISE
 DETAIL AS REQUIRED.
 SPECIFY SIZE OF WASHER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-SHEET S-1: CLARIFY TYP. DETAIL AT
 BOND BEAM ELEVATION CHANGE. IS IT 1#7
 OR 1#5. SEE BB SPECS.SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 23-SHEET A-2: UPDATE PLUMBING NOTE. USE
 FPC 2001.
 24-SPACY SPACING FOR WWM SUPPORTS IN
 CONCRETE SLAB. SEC. 1909.3 FBC 2001.
 25-ROOF FRAMING PLAN: SOME CONNECTORS
 DON'T RESIST THE UPLIFT LOADS THAT
 WERE CALCULATED FOR GIRDER TRUSSES.
 SEE CONNECTORS TC-5 AND TC-6.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-07 Cont ID  
Sent By sgraham Date 2002-08-07 Time 08:04 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***