| 2002-09-18 00:00:00 | CHECKLIST: |
| | 1-PROVIDE ENGINEERING ANALYSIS/CALCS AND |
| | COMPLETE SECTIONS/DETAILS/SPECS FOR |
| | DESIGN OF GABLE END AT FRONT ELEVATION |
| | CONSIDERING THAT CENTER OF GABLE END @ |
| | FRONT ELEVATION IS MASONRY AND THE TWO |
| | SIDES ARE PARTIAL GABLE END TRUSSES. |
| | CLARIFY HOW IS GABLE END WALL PUT |
| | TOGETHER TO TRANSFER THE LOADS. SEE |
| | SECTIONS 1604.2.4, 2105, 2107, 2117 & |
| | 2313 FBC 2001. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-REVISE ATTIC ACCESS SIZE. 36" MIN. NOT |
| | 30". SEC. 2309.6 FBC 2001. |
| | 4-34SH WINDOW DOESN'T PROVIDE 24" MIN. |
| | CLEAR OPENING HEIGHT. SEC. 1005.4.4. |
| | 5-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS. SEE PRODUCT APPRO- |
| | VAL FOR LIMITATIONS. |
| | 6-PROVIDE PRODUCT APPROVAL FOR SINGLE |
| | ENTRY DOOR WITH SINGLE SIDELITE AS |
| | SHOWN ON PLANS. |
| | 7-PROVIDE UL LISTING AND COMPLETE SPECS |
| | FOR ONE HR FIRE RATED GLASS BLOCK |
| | ASSEMBLY REQUIRED BY TABLE 600 FBC. |
| | **NOTE: GLASS BLOCK TO BE SAFETY GLASS |
| | IF UNIFORM FACE THICKNESS IS LESS THAN |
| | 0.25". SEC. 2405.2.2 FBC 2001. |
| | 8-REVISE GLASS BLOCK ASSEMBLY DETAIL TO |
| | MATCH UL SPECIFICATIONS SUBMITTED. |
| | **REVISE WINDOW SCHEDULE: SPECIFY REQ'D |
| | 1 HR FIRE RATED GLASS BLOCK. |
| | |
| | 9-SPECIFY SPACING FOR SUPPORTS OF WWM |
| | IN CONCRETE SLAB. SEC. 1909.3 FBC 2001 |
| | 10-PROVIDE COMPLETE DETAIL AT RECESSED |
| | WINDOWS TO ALLOW FOR STORM SHUTTERS |
| | INSTALLATION. SEE STORM SHUTTERS |
| | PRODUCT APPROVAL FOR LIMITATIONS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 11-ENERGY CALCULATIONS: |
| | A)REVISE UNDER ATTIC AREA. SEE SECTION |
| | 602.1.ABC.1.2 CHAPTER 13 FBC 2001. |
| | B)OWNER/AGENT TO DATE BOTTOM OF FORM |
| | WHEN SIGNING IT. |
| | 12-WALL SECTIONS NOTE #14 AND VENT CALCS |
| | DON'T MATCH. REVISE AS REQUIRED. |
| | 13-SHEET S-2:A) UPDATE NOTE #2: SEMCO |
| | CONNECTOR. |
| | B)UPDATE NOTE #3: REFER TO FBC 2001 FOR |
| | 140 MPH, NOT ASCE 7-93. |
| | C)CLARIFY WHY BLOCKING AT FRONT END IS |
| | SHOWN ON PARTIAL GABLE END AND NOT ALL |
| | THE WAY DOWN TO THE ENDS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 14-SHEET S-1: A) CLARIFY DIMENSION OF |
| | 4'-1 1/2" ON SECTION 5. |
| | B)PROVIDE INSTALLATION DETAIL FOR LINTEL |
| | L-7 AT FRONT PORCH. LINTEL IS NOT |
| | RESTING ON MASONRY COLUMN FOR CONTI- |
| | NUOUS VERTICAL REINFORCEMENT. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | C)REVISE LINTEL SCHEDULE TO MATCH PLANS. |
| | CHECK SIZES AND LINTEL SPECIFIED. |
| | |
| | 15-IDENTIFY ROOF ZONES ON ROOF FRAMING |
| | PLAN. TABLE 2306.1 CITY AMENDMENTS. |
| | 16-REVISE TRUSS ANCHOR SCHEDULE TO MATCH |
| | USP PUBLISHED VALUES. PROVIDE ENGI- |
| | NEERING CALCS FOR DIFFERENT VALUES. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 17-SEE PRODUCT APPROVAL FOR GARAGE DOORS |
| | STRUCTURAL BUCK REQUIREMENTS. REVISE |
| | DETAIL AS REQUIRED. |
| | **SPECIFY WASHER. |
| | 18-UPDATE FOUNDATION NOTE ON SHEET C-1: |
| | NEED 0.006 MIL VISQUEEN MIN. SECTION |
| | 1909.2 FBC 2001. |
| | 19-REVIEW ALL FLOOR PLANS AND CLEARLY |
| | KEY DETAILS AND SECTIONS THAT MATCH |
| | SHEET THEY ARE REFERENCING TO. |
| | 20-UPDATE GENERAL NOTE ON SHEET A-1: |
| | REFER TO FPC 2001, NOT SPC 1994. |
| | 21-SHEET A-3: REVISE SECTION THRU ENTRY |
| | TO MATCH MASONRY CONSTRUCTION. |
| | SEC. 2117 FBC 2001. |