| Plan Review Stops For Permit 02080376 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-12-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-12-03 |
Time |
13:38 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-12-03 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2002-12-03 00:00:00 | REVISION: 11-21-02 FRONT ENTRY/ STORE- | | | FRONT WINDOW SYSTEMJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-25 |
Time |
18:25 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-11-19 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2002-11-19 00:00:00 | | | | REVISION: DATED NOV.14/02 INDICATES THE | | | INDICATES THE LADIES RESTROOM DOOR SWING | | | CHANGED TO SWING BACK INTO THE CLEAR | | | FLOOR SPACE. | | | | | | PLAN REVIEW DATED 8/16/02 INDICATES | | | CLEAR FLOOR SPACE REQUIRED. | | | | | | PLAN REVIEW: PERMIT SET INDICATES THE | | | CORRECTION!!!!!!! | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
15:48 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2002-09-08 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-08-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-16 |
Time |
15:19 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2002-08-16 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2002-08-16 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02080376 | | | ADD: 313 5TH STREET | | | CONT: DAVIS GENERAL CONT | | | TEL: (561)820-1400 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1)11-4.1.3(1) AT LEAST ONE ACCESSIBLE | | | ROUTTE COMPLYING WITH 11-4.3 SHALL | | | CONNECT ACCESSIBLE BUILDING OR FACILITY | | | ENETRANCES WITH ALL ACCESSIBLE SPACES | | | AND ELEMENTS WITHIN THE BUILDING OR | | | FACILITY. | | | 2)11-4.22.2 DOORS. ALL DOORS TO | | | ACCESSIBLE TOLIET ROOMS SHALL COMPLY | | | WITH 11-4.13. DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE REQUIRED FOR ANY | | | FIXTURE. | | | 3) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORT, SBCCI OR DADE COUNTY | | | REPORT ARE ACCEPTED.NEW FIXED GLASS | | | WINDOW, PROVIDE LARGE MISSLE IMPACT | | | RESISTANT GLAZING OR STORM SHUTTERS. | | | PRODUCT APPROVAL SHALL STILL BE REQUIRED | | | FOR THE GLAZING UNIT (FOR WIND) IF | | | PROVIDING STORM SHUTTERS WITH PRODUCT | | | TESTING REPORT. | | | 4)1511.7 ROOF MOUNTED MECHANICAL UNIT | | | S SHALL BE MOUNTED ON CURBS RAISED A | | | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- | | | FACE, OR WHERE ROOFING MATERIALS EXTEND | | | BENEATH THE UNIT, ON RAISED EQUIPMENT | | | SUPPORTS PROVIDING A MINIMUM CLEARENCE | | | HEIGTH IN ACCORDANCE WITH TABLE 1511.7. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDEN- | | | TIFYING THE SHEET OR SPECIFICATION PAGE | | | WHERE THE CHANGES CAN BE FOUND, WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | JIM WITMER | | | PLAN REVIEW | | | TEL: (561)659-8096 EX.8412 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-05 |
Time |
15:07 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-09-05 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-22 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-08-06 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-08-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-08-09 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-08-09 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2002-08-09 00:00:00 | 1) PLEASE INDICATE ON PLANS THE | | | LOCATIONS OF EXISTING ILLUMINATED | | | EXIT SIGNS AND EMERGENCY LIGHTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-11-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-25 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-25 |
Time |
18:25 |
Sent To |
B |
|
| Notes |
| 2002-11-25 00:00:00 | TO JIM W./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-11-15 |
Time |
15:48 |
Sent To |
P |
|
| Notes |
| 2002-11-15 00:00:00 | TO PLUMB INBOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-09-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-05 |
Time |
08:54 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2002-09-05 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2002-09-09 00:00:00 | MECHANICAL PERMIT 02081372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-08-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-23 |
Time |
13:59 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-08-23 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2002-08-23 00:00:00 | DENIED: | | | | | | 1. PLEASE PROVIDE OUTSIDE AIR CALCS AS | | | PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89. | | | | | | 2. PLEASE SIZE SUPPLY DUCT SERVING THE | | | RESTROOMS. | | | | | | 3. AS PER FBC(M) 606.2.2, WHERE MULTIPLE | | | AIR HANDLING SYSTEMS SHARE COMMON | | | SUPPLY OR RETURN AIR DUCTS OR PLENUMS | | | WITH A COMBINED DESIGNED CAPACITY | | | GREATER THAN 2,000 CFM, THE RETURN & | | | SUPPLY AIR SYSTEM SHALL BE PROVIDED | | | WITH SMOKE DETECTORS IN ACCORDANCE | | | WITH SECTION 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-19 |
Time |
14:53 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-11-19 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2002-11-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) FROM PREVIOUS REVIEW PRIOR TO PERMIT | | | BEING ISSUED: DOOR TO WOMEN'S TOILET | | | ROOM SHALL NOT SWING INTO CLEAR FLOOR | | | SPACE OR UNOBSTRUCTED TURNING RADIUS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-09-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-19 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-05 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-14 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-14 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2002-08-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | | | | 1) SHT A100 SERVICE SINK AND DRINKING | | | FOUNTAIN REQUIRED. TABLE 403.1 (ALSO SEE | | | SECTION 410.1. IF BOTTLE WATER COOLER IT | | | SHALL COMPLY WITH WHI-1010.) | | | 2) SHT A100 SINK IN KITCHENETTE SHALL | | | COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. | | | DOOR SHALL NOT SWING INTO CLEAR FLOOR | | | SPACE FOR SINK SEC'S 11-4.17.5, 11-4.22. | | | 2 & 11-4.23.2 | | | 3) SHT A100 A WATER RISER IS REQUIRED. | | | WATER HAMMER ARRESTORS ARE REQUIRED PER | | | SECTION 604.9. LOCATION OF WHA'S SHALL | | | BE NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT AT THE TOP OF THE DROP. | | | MANUFACTURE INSTALLATION INSTRUCTIONS & | | | PDI-WH 201. | | | 4) SHT A100 WOMENS TOILET ROOM, DOOR | | | SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE OR UNOBSTRUCTED TURNING RADIUS OF | | | HDCP FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|