Plan Review Details - Permit 02080376
Plan Review Stops For Permit 02080376
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-12-03 Cont ID  
Sent By jwitmer Date 2002-12-03 Time 13:38 Rev Time 0.75
Received By jwitmer Date 2002-12-03 Time 13:38 Sent To  
Notes
2002-12-03 00:00:00REVISION: 11-21-02 FRONT ENTRY/ STORE-
 FRONT WINDOW SYSTEMJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 18:25 Rev Time 0.75
Received By jwitmer Date 2002-11-19 Time 16:16 Sent To  
Notes
2002-11-19 00:00:00 
 REVISION: DATED NOV.14/02 INDICATES THE
 INDICATES THE LADIES RESTROOM DOOR SWING
 CHANGED TO SWING BACK INTO THE CLEAR
 FLOOR SPACE.
  
 PLAN REVIEW DATED 8/16/02 INDICATES
 CLEAR FLOOR SPACE REQUIRED.
  
 PLAN REVIEW: PERMIT SET INDICATES THE
 CORRECTION!!!!!!!
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-08 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 15:48 Rev Time 0.33
Received By jwitmer Date 2002-09-08 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-16 Cont ID  
Sent By jwitmer Date 2002-08-16 Time 15:19 Rev Time 1.25
Received By jwitmer Date 2002-08-16 Time 15:18 Sent To  
Notes
2002-08-16 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02080376
 ADD: 313 5TH STREET
 CONT: DAVIS GENERAL CONT
 TEL: (561)820-1400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
 2)11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.NEW FIXED GLASS
 WINDOW, PROVIDE LARGE MISSLE IMPACT
 RESISTANT GLAZING OR STORM SHUTTERS.
 PRODUCT APPROVAL SHALL STILL BE REQUIRED
 FOR THE GLAZING UNIT (FOR WIND) IF
 PROVIDING STORM SHUTTERS WITH PRODUCT
 TESTING REPORT.
 4)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-05 Cont ID  
Sent By btrobaug Date 2002-09-05 Time 15:07 Rev Time 0.50
Received By btrobaug Date 2002-09-05 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-22 Cont ID  
Sent By btrobaug Date 2002-08-22 Time 08:41 Rev Time 0.00
Received By btrobaug Date 2002-08-06 Time 11:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-08-09 Cont ID  
Sent By mcarsill Date 2002-08-09 Time 14:43 Rev Time 0.00
Received By mcarsill Date 2002-08-09 Time 14:43 Sent To  
Notes
2002-08-09 00:00:001) PLEASE INDICATE ON PLANS THE
 LOCATIONS OF EXISTING ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 18:25 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 18:25 Sent To B
Notes
2002-11-25 00:00:00TO JIM W./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-19 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 15:48 Sent To P
Notes
2002-11-15 00:00:00TO PLUMB INBOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-09 Cont ID  
Sent By pkrauss Date 2002-09-05 Time 08:54 Rev Time 0.25
Received By pkrauss Date 2002-09-05 Time 08:36 Sent To  
Notes
2002-09-09 00:00:00MECHANICAL PERMIT 02081372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-08-23 Cont ID  
Sent By pkrauss Date 2002-08-23 Time 13:59 Rev Time 0.35
Received By pkrauss Date 2002-08-23 Time 13:04 Sent To  
Notes
2002-08-23 00:00:00DENIED:
  
 1. PLEASE PROVIDE OUTSIDE AIR CALCS AS
 PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 2. PLEASE SIZE SUPPLY DUCT SERVING THE
 RESTROOMS.
  
 3. AS PER FBC(M) 606.2.2, WHERE MULTIPLE
 AIR HANDLING SYSTEMS SHARE COMMON
 SUPPLY OR RETURN AIR DUCTS OR PLENUMS
 WITH A COMBINED DESIGNED CAPACITY
 GREATER THAN 2,000 CFM, THE RETURN &
 SUPPLY AIR SYSTEM SHALL BE PROVIDED
 WITH SMOKE DETECTORS IN ACCORDANCE
 WITH SECTION 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-11-19 Cont ID  
Sent By kstevens Date 2002-11-19 Time 14:53 Rev Time 0.50
Received By kstevens Date 2002-11-19 Time 14:53 Sent To  
Notes
2002-11-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW PRIOR TO PERMIT
 BEING ISSUED: DOOR TO WOMEN'S TOILET
 ROOM SHALL NOT SWING INTO CLEAR FLOOR
 SPACE OR UNOBSTRUCTED TURNING RADIUS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-05 Cont ID  
Sent By dpalmer Date 2002-11-19 Time 10:45 Rev Time 0.00
Received By kstevens Date 2002-09-05 Time 14:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-14 Cont ID  
Sent By kstevens Date 2002-08-14 Time 16:40 Rev Time 0.00
Received By kstevens Date 2002-08-14 Time 16:40 Sent To  
Notes
2002-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A100 SERVICE SINK AND DRINKING
 FOUNTAIN REQUIRED. TABLE 403.1 (ALSO SEE
 SECTION 410.1. IF BOTTLE WATER COOLER IT
 SHALL COMPLY WITH WHI-1010.)
 2) SHT A100 SINK IN KITCHENETTE SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 DOOR SHALL NOT SWING INTO CLEAR FLOOR
 SPACE FOR SINK SEC'S 11-4.17.5, 11-4.22.
 2 & 11-4.23.2
 3) SHT A100 A WATER RISER IS REQUIRED.
 WATER HAMMER ARRESTORS ARE REQUIRED PER
 SECTION 604.9. LOCATION OF WHA'S SHALL
 BE NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT AT THE TOP OF THE DROP.
 MANUFACTURE INSTALLATION INSTRUCTIONS &
 PDI-WH 201.
 4) SHT A100 WOMENS TOILET ROOM, DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OR UNOBSTRUCTED TURNING RADIUS OF
 HDCP FIXTURES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377