Plan Review Details - Permit 02080361
Plan Review Stops For Permit 02080361
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-19 Cont ID  
Sent By dpalmer Date 2002-08-19 Time 13:38 Rev Time 0.00
Received By dpalmer Date 2002-08-19 Time 13:38 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 16:51 Rev Time 0.00
Received By shernand Date 2003-04-10 Time 16:51 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-12 Cont ID  
Sent By rregueir Date 2003-04-12 Time 12:54 Rev Time 0.33
Received By rregueir Date 2003-04-12 Time 12:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-08-15 Cont ID  
Sent By shernand Date 2003-04-10 Time 16:51 Rev Time 0.50
Received By hmoser Date 2002-08-15 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By jleech Date 2002-08-06 Time 18:45 Rev Time 0.33
Received By jleech Date 2002-08-06 Time 18:45 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-10-28 Cont ID  
Sent By lhatten Date 2002-10-28 Time 18:20 Rev Time 3.00
Received By lhatten Date 2002-10-26 Time 18:19 Sent To  
Notes
2002-10-28 00:00:00REVIEW & STAMPED PLANS 10/26/2002
 CALC. FEES & PRINT CARD 10/28/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-09-06 Cont ID  
Sent By jgomez Date 2002-09-06 Time 14:22 Rev Time 3.00
Received By jgomez Date 2002-09-06 Time 14:22 Sent To  
Notes
2002-09-06 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-A)SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION @ STAIRS. INCLUDING TOP OF
 STAIRS. SEE SEC. 2305.1.4 FBC 2001.
 B)PROVIDE GENERAL SPECS FOR REQUIRED
 FIREBLOCKING AT ALL CONCEALED SPACES.
 SEE SEC. 2305.1.4 FBC 2001.
 3-DRAFSTOPPING TO BE LOCATED FOR AREAS
 NOT TO EXCEED 500 S.F. REVISE AS REQ'D
 SEE SEC. 2305.2.2 FBC 2001.
 4-SPECIFY FIRECUT REQUIREMENTS ON THE
 STRUCTURAL WALL SECTIONS. SEE SEC.
 2305.4 FBC 2001.
 5-SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 6-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION
 7-PROVIDE UPDATED PRODUCT APPROVALS FOR
 ALL EXTERIOR DOORS, WINDOWS AND WINDOW
 MULLIONS TO BE USED.
 8-REVISE STAIR KEY NOTE #1. HEIGHT OF
 STAIR HANDRAIL TO BE BET. 34" AND 38".
 SEE SECTION 1007.5.1 FBC 2001.
 9-2ND FLOOR FRAMING PLAN:
 PROVIDE DETAIL SHOWING HOW DOES USP
 HL210 WHICH IS A LIGHT GAUGE PURLING
 HANGER IS USED TO HOLD GIRDER TRUSSES.
 10-SECTION 4/S3 IS CALLED 5/S3 ON ROOF
 FRAMING PLAN. CLARIFY/REVISE AS REQ'D.
 11-REVISE DETAIL 4/S3 TO SHOW GABLE
 END. ***NOTE: GABLE END TO BE DESIGNED
 AS PER SEC. 2117 FBC 2001. PROVIDE
 DETAIL WITH COMPLETE SPECS AND SPECIFY
 ALL FASTENERS.
 12-REVISE TRUSS CONNECTOR SCHEDULE TO
 MATCH USP PUBLISHED LOADS.
 **NOTE: PROVIDE ENGINEERING CALCS FOR
 LOADS OTHER THAN THE ONES SPECIFIED ON
 USP.
 **REMAINDER: 10D NAILS NEED 1 3/4" MIN.
 PENETRATION TO GET FULL VALUE.
 DON'T MISMATCH NAIL SIZE & LOADS.
 13-THERE IS NOT CONNECTOR SPECIFIED FOR
 ROOF TRUSS WITH CALCULATED UPLIFT LOAD
 OF 2537#.
 14-CONNECTOR T-5 DOESN'T RESIST THE
 UPLIFT LOAD OF 2369# CALCULATED FOR
 THE ROOF GIRDER TRUSS. REVISE AS REQ'D
 15-ROOF SHEATHING & NAILING NOTE ON DWG
 S3 AND SECTION 4/S3 AND DIAPHRAGM
 SCHEDULE HAVE DIFFERENT SPECS. REVISE/
 CLARIFY AS REQUIRED.
 **NOTE: KEEP IN MIND THAT MEAN ROOF HT
 BET. 25' AND 35' REQUIRES 8D RING
 SHANK NAILS MIN. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.
 16-IDENTIFY NAILING ZONES IN ROOF FRAM'G
 PLAN. TABLE 2306.1 CITY AMENDMENTS.
 17-DESIGN PRESSURES FOR ENTRY DOORS ARE
 DIFFERENT ON THE FLOOR PLAN AND EXT.
 ELEVATION. REVISE AS REQUIRED.
 18-SEE GARAGE DOOR PRODUCT APPROVAL FOR
 STRUCTURAL BUCK SPECS & REVISE DETAIL
 AS REQUIRED.
 **NOTE: SPECIFY SIZE OF WASHERS.
 19-PROVIDE STRUCTURAL BUCK DETAIL FOR
 INSTALLATION OF DOUBLE 2X BUCK TO
 ACCOMMODATE THE ENTRY DOORS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 20-UPDATE DRAWING C-1. FOUNDATION NOTE
 STILL CALLS FOR 0.004 MIL VISQUEEN.
 NEED 0.006 MIL. SEC. 1909.2 FBC 2001.
 21-UPDATE NOTE #3 ON SHEET S3. REFERENCE
 FBC 2001 OR ASCE 7-98, NOT ASCE 7-93.
 22-SHEET A4: EXTERIOR ELEVATIONS ARE NOT
 SHOWN AT 1/4" SCALE. REVISE AS REQ'D.
 23-SHEET A-2: UPDATE PLUMBING NOTE #6.
 REFERENCE FPC 2001, NOT SPC 1994.
 24-SHEET A-7: A)SECT'NA/A6 TO BE SEC.
 A/A7. REVISE AS REQUIRED
 B)SPECIFY FIREBLOCKING ON SECTION A/A7.
 SEC. 2305.1.4 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-08-06 Cont ID  
Sent By sgraham Date 2002-08-06 Time 15:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***