Plan Review Details - Permit 02080312
Plan Review Stops For Permit 02080312
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-31 Cont ID  
Sent By rbrown Date 2003-01-31 Time 09:48 Rev Time 0.00
Received By rbrown Date 2003-01-31 Time 09:48 Sent To  
Notes
2003-01-31 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE PREVIOUSLY SUBMITTED WAYNE DALTON
 CORP. PRODUCT APPROVAL, NOA# 01-1031.08,
 IS FOR A 'SERIES 800 SERVICE DOOR'.
 SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED REVISION TO WAYNE DALTON
 MODEL 820 ROLLING STEEL DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-10-02 Cont ID  
Sent By rbrown Date 2002-10-02 Time 15:58 Rev Time 0.00
Received By rbrown Date 2002-10-02 Time 15:57 Sent To  
Notes
2002-10-02 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 FBC 1015.2EACH NEW STAIRWAY, LANDING
 AND PLATFORM SHALL INCORPORATE GUARDING
 NOT LESS THAN 42" HIGH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-09-30 Cont ID  
Sent By rbrown Date 2002-09-30 Time 16:09 Rev Time 0.00
Received By rbrown Date 2002-09-30 Time 16:09 Sent To  
Notes
2002-09-30 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 IT IS NOTED THAT THE PLANS HAVE BEEN
 REVISED AND NOW SHOW AN INCREASED SCOPE
 OF WORK, INCLUDING REMOVAL OF THE
 EXISTING WOOD FLOOR SYSTEM, INSTALLATION
 OF NEW STAIRWAYS, PLATFORM AND LANDINGS,
 PLACEMENT OF NEW FLOOR SLAB AND
 INSTALLATION OF NEW GARAGE DOOR AND EXIT
 DOOR.
  
 --PROVISO--
 FBC 1015.2EACH NEW STAIRWAY, LANDING
 AND PLATFORM SHALL INCORPORATE GUARDING
 NOT LESS THAN 42" HIGH (PLANS SHOW 36"
 HIGH).
  
 --PROVISO--
 SUBMIT TWO COPIES OF A PRODUCT APPROVAL
 FOR THE NEW 3-0"X 6-8" STEEL EXIT DOOR
 #2 AND #3.ALSO, PROVIDE LINTEL DETAILS
  
 --PROVISO--
 THE SUBMITTED COPIES OF DRAWING SHEETS
 FOR PRODUCT APPROVAL NOA# 01-1031.08 FOR
 THE SERIES 800 SERVICE DOOR ARE POOR
 QUALITY.SUBMIT TWO LEGIBLE COPIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-23 Cont ID  
Sent By rbrown Date 2002-08-23 Time 11:52 Rev Time 0.00
Received By rbrown Date 2002-08-23 Time 11:52 Sent To  
Notes
2002-08-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) STATE THE PROPOSED OCCUPANCY OF THE
 FIRST FLOOR ON THE PLANS.
 WHAT IS THE EXISTING OCCUPANCY OF THE
 SECOND FLOOR?
  
 2) FBC* 1606.1.6DRAWING SHEET 4, 'WIND
 LOAD DESIGN CRITERIA'.THE BASIC WIND
 SPEED FOR THE CITY OF WEST PALM BEACH IS
 140 MPH NOT 130 MPH.REVISE THE STATED
 DESIGN WIND PRESSURE ACCORDINGLY.
  
 3) FBC 1606DRAWING SHEET 4, ORNAMENTAL
 METAL FASCIA ROOF.PROVIDE A CHECK
 CALCULATION FOR THE 1/4" BOLTS, THROUGH
 THE SUPPORT STRUTS, ACTING IN DOUBLE
 SHEAR WHEN SUBJECT TO THE UPLIFT
 COMPONENT OF THE WIND LOAD.NOTE THAT
 THE UPLIFT LOAD IS NOT SHARED EQUALLY,
 THE SUPPORT ADJACENT THE LOWER EDGE OF
 THE ROOF RECEIVES MORE LOAD DUE TO THE
 CANTILEVER ARRANGEMENT.
  
 4) SUBMIT A PRODUCT APPROVAL FOR THE
 'CORRUGATED ENAMELED METAL ROOF PANELS'
  
 5) HORIZONTAL SLIDING WINDOW PRODUCT
 APPROVAL, NOA 02-0305.02.THE ANCHOR
 SPACING NOTES ON DRAWING SHEET 1 OF 3
 ARE NOT CLEAR DUE TO COPY/FAX QUALITY.
 SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT
 APPROVAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 16:01 Rev Time 0.50
Received By dpalmer Date 2003-01-06 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By dpalmer Date 2002-09-24 Time 06:17 Rev Time 0.50
Received By dpalmer Date 2002-09-24 Time 06:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By dpalmer Date 2002-08-15 Time 06:37 Rev Time 0.00
Received By dpalmer Date 2002-08-15 Time 06:28 Sent To  
Notes
2002-08-15 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SEE COMMENTS FROM FIRE
 PLAN REVIEW THAT WILL HAVE A DIRECT
 AFFECT ON THE ELECTRICAL PLANS.
 EXITS/EM/LTS.
  
 2)NOTE: PLEASE NOTE THAT SQ. FT NEEDS
 TO BE SHOWN IN LOAD CALCULATIONS,
 220-3,220-10,,,,,,
  
  
  
 3)NOTE: PLEASE NOTE THAT THE MIN OF 125%
 IS SHOWN FOR AHU ON LOAD CALCULATIONS,
 BUT HAS A 2P-50A BRKR IN PANEL FOR OCP?
 PLEASE CLARIFY
  
 4)NOTE: PLEASE NOTE THAT AREA FOR AHU
 AND HWH DOES NOT SEEM TO MEET CLEARENCE
 REQUIREMENTS FOR COMBUSTIBLES. PLEASE
 ALSO NOTE IT DOES NOT SEEM THE OPENING
 IS LARGE ENOUGH BETWEEN WALL AND AHU
 TO REPLACE HWH IF NECCESARY.??
 PLEASE VERIFY. 110-26, 424-13
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-01-30 Cont ID  
Sent By mcarsill Date 2003-01-30 Time 10:48 Rev Time 0.00
Received By mcarsill Date 2003-01-30 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-24 Cont ID  
Sent By mcarsill Date 2002-09-24 Time 09:20 Rev Time 0.00
Received By mcarsill Date 2002-09-24 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-06 Cont ID  
Sent By mcarsill Date 2002-08-06 Time 16:01 Rev Time 0.00
Received By mcarsill Date 2002-08-06 Time 16:01 Sent To  
Notes
2002-08-06 00:00:001) ADDRESS REQUIRED ON BUILDING.
  
 2) WHAT WILL THE BUILDING BE USED FOR.
 WHAT TYPE OF OCCUPANCY. WILL IT BE USED
 FOR A SINGLE OR MULTIPLE TENANT.
  
 3) ARE THE EXISTING WINDOWS OPERABLE.
  
 4) A NOTE ON THE PLANS INDICATE THAT THE
 EXISTING FIRE SPRINKLER SYSTEM WILL BE
 INSPECTED. NO MENTION OF WHETHER THE
 EXISTING FIRE SPRINKLER SYSTEM WILL BE
 MONITORED AS REQUIRED BY CODE.
  
 5) NO INDICATION OF WHAT THE FIRST FLOOR
 OF THE BUILDING WILL BE USED FOR.
  
 6) PLANS DO NOT INDICATE EMERGENCY
 LIGHTS OR ILLUMINATED EXIT SIGNS. ALSO
 NO INFORMATION PROVIDED FOR PORTABLE
 FIRE EXTINGUISHERS.
  
 7) NO DETAILS PROVIDED ON EXITING OR
 ABOUT THE EXISTING STAIRS.
  
 8) NO DOOR SHCEDULE PROVIDED WITH PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 16:00 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 16:00 Sent To  
Notes
2003-01-06 00:00:00TO COMM BAORD #8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 09:18 Sent To Z
Notes
2002-12-27 00:00:00SENT TO ZONING DUE TO REVISING PLANS
 TO INCLUDE SIGNS.
 SIGNS ARE TO BE PERMITTED SEPARATELY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-10-02 Cont ID  
Sent By pkrauss Date 2002-10-02 Time 13:44 Rev Time 0.35
Received By pkrauss Date 2002-09-25 Time 16:15 Sent To  
Notes
2002-10-02 00:00:00MECHANICAL PERMIT 02080314
  
 PLEASE PROVIDE INFORMATION ON THE
 MATERIAL, DUCT SIZE & ROUTING OF
 OUTSIDE AIR DUCT.SUBMIT PRIOR TO
 INSPECTION.
  
 CONTRACTOR BROUGHT IN PLANS INDICATING
 OUTSIDE AIR DUCT.O.A. CALCS ON THE
 ORIGINAL SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-05 Cont ID  
Sent By pkrauss Date 2002-09-05 Time 09:09 Rev Time 0.40
Received By pkrauss Date 2002-09-05 Time 09:05 Sent To  
Notes
2002-09-05 00:00:00DENIED:MECHANICAL PERMIT 02080314
  
 1.PROVIDE ENERGY & SIZING CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHAPTER
 13 SECTION 407.
  
 2.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.
  
 3.PLEASE INDICATE LINE SIZE & PIPING
 FOR THE LIQUID, SUCTION & CONDENSATE
 PLEASE NOTE AS PER 2001 FBC 1503.4.4
 CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12 INCHES AWAY FROM THE BUILDING
 STRUCTURE.
  
 4.PLANS INDICATE DUCT SERVING THE 1ST
 FLOOR. WILL BOTH FLOORS BE OCCUPIED
 BY THE SAME TENANT?
  
 5.PLANS INDICATE A GARAGE DOOR ON THE
 FIRST FLOOR PLEASE INDICATE WHAT THE
 OCCUPANY TYPE IS FOR THE 1ST & 2ND
 FLOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-18 Time 16:41 Rev Time 1.00
Received By kstevens Date 2003-01-18 Time 16:41 Sent To  
Notes
2003-01-18 00:00:00REVISION OK - ADDED SINK

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-09-23 Cont ID  
Sent By kstevens Date 2002-09-23 Time 18:33 Rev Time 0.00
Received By kstevens Date 2002-09-23 Time 18:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By kstevens Date 2002-08-15 Time 17:14 Rev Time 0.00
Received By kstevens Date 2002-08-15 Time 17:14 Sent To  
Notes
2002-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 3 WATER HEATER SHALL BE ACCESS-
 IBLE.
 2) SHT 4 SEC 409.1 ONLY FIXTURES WITHIN
 THE BATHROOM GROUP SHALL BE CONNECTED
 TO THE WET VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWN STREAM OF THE WET VENT.
 BAR SINK SHALL TIE IN DOWNSTREAM OF THE
 WATER CLOSET.
 3) SEPARATE PERMIT REQUIRED FOR IRR.
 SUBMIT PLANS WITH IRRIGATION APPLICATION
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2003-01-06 Cont ID  
Sent By sgraham Date 2003-01-06 Time 10:41 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-06 00:00:00APPROVED BY JOE MINICOZZI

Review Stop Z ZONING
Rev No 2 Status P Date 2002-10-02 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 09:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-09-19 Cont ID  
Sent By sgraham Date 2002-09-19 Time 11:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-09-20 00:00:001. ACCORDING TO THE CALCULATIONS (2-
 SPACES/1000 SQ FT, THEY HAVE 4475=9-
 SPACES) THEY NEED TO ADD ONE MORE
 SPACE.
 2. THE HANDICAP SPACE NEEDS TO BE
 LOCATED ON THE SITE,NOT IN THE STREET.
 3. THE HEDGES AT THE PARKING LOT NEED
 TO BE INSTALLED AT 42" AT PLANTING,
 ANDTHERE NEEDS TO BE HEDGES ALONG
 THE STREET FRONT BORDER OF THE PARKING
 LOT AT THE NW AREA OF PK LOT.
 4. THERE SHALL BE ONE SHADE TREE (NOT
 PALM) AT THE PERIMETER OF THE PARKING
 LOT FACING THE STREET FOR EVERY 3-
 SPACES
 5. IF THE EXISTING CURB CUTS ARE TO BE
 REUSED, THE S/W NEED TO BE REPAIRED/
 REPLACED WHERE THEY ARE IN POOR
 CONDITION.
 6. IF THE PARKING IS IN DISREPAIR,THE
 FIRST 1" OF STORMWATER SHOULD BE RETAIN-
 ED ON SITE. THE LANDSCAPE EDGES AS THE H
 HEDGE LINE AND THE LANDSCAPE TRIANGLE AT
 THE SOUTH OF THE SOUTH SHOULD BE USED
 FOR RUN-OFF WATER.