Plan Review Details - Permit 02080218
Plan Review Stops For Permit 02080218
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-12-03 Cont ID  
Sent By hpiskura Date 2002-12-03 Time 08:20 Rev Time 0.00
Received By hpiskura Date 2002-12-03 Time 08:20 Sent To  
Notes
2002-12-03 00:00:00REVIEW COMMENTS SUBJECT TO 1997 SBCCI
  
 THE WINDOW OPENING PROPOSED ON THE WEST
 SIDE IS PROHIBITTED BY SBC TABLE 600.
 SEE EXTERIOR WALLS 0'-3' FROM A
 PROPERTY LINE.PLEASE REVISE AS
 NECESSARY AND ENSURE THREE HOUR RATED
 CONSTRUCTION.
  
 THE FIRST FINANCIAL SURVEYORS SHOWS THIS
 WALL 1'-6" BEYOND THE PROPERTY LINE.
 IS THERE AN EXISTING PARTY OR FIRE WALL
 AS DEFINED IN SBC 202 TO PROVIDE
 SEPARATE BUILDINGS?
  
 THE NEW CONSTRUCTION FOR THE VESTIBULE
 ON THE SOUTH, (ALLEY SIDE) IS REQUIRED
 TO BE OF TYPE V CONSTRUCTION,
 (NON-COMBUSTIBLE) AND TWO HOUR FIRE
 RATED.SEE SBC 607 AND SBC TABLE 600.
  
 SHEET A1 SHOWS ONE AND FOUR INCH DOOR
 THRESHOLD HEIGHTS WHICH DO NOT COMPLY
 WITH THE MAXIMUM 1/2" ALLOWED BY THE
 1997 FACBC 4.13.8 FOR ENTRANCE DOORS.
  
 THE WALLS OF THE PROPOSED SECOND STORY
 ARE REQUIRED TO BE OF NON-COMBUSTIBLE
 CONSTRUCTION.SEE FBC 607.THE USE OF
 PLYWOOD SHEATHING AND WOOD TOP PLATES
 DOES NOT COMPLY.ALSO, WALLS LOCATED
 10'-20' FROM A PROPERTY LINE ARE
 REQUIRED TO BE OF TWO HOUR FIRE RATED
 CONSTRUCTION. SEE SBC TABLE 600 FOR TYPE
 V ONE HOUR PROTECTED.THE FLOOR TRUSS
 CONFIGURATION SHOWN IN DETAIL 3/A5 DOES
 NOT COMPLY WITH THE EXTERIOR WALL
 REQUIREMENTS OF TYPE V CONSTRUCTION.
  
 SHOW THE DRAFTSTOPPING IN ACCORDANCE
 WITH SBC 2305.2.2 FOR THE FLOOR CEILING
 AND ROOF CEILING ASSEMBLIES.
  
 SEE THE 8/29/02 COMMENTS RE: IMPACT
 FEES AND PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-08-29 Cont ID  
Sent By hpiskura Date 2002-08-29 Time 11:04 Rev Time 0.00
Received By hpiskura Date 2002-08-28 Time 14:36 Sent To  
Notes
2002-08-29 00:00:00THE PLANS DECLARE DESIGN TO THE 1997
 STANDARD BUILDING CODE.THE 2001
 FLORIDA BUILDING CODE IS CURRENTLY IN
 EFFECT AND WEST PALM BEACH IS IN A 140
 MPH WIND ZONE.PLEASE REVISE THE PLANS
 ACCORDINGLY.
  
 THIS BUILDING IS LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND TYPE VI
 CONSTRUCTION (WOOD FRAME) IS
 PROHIBITED.SEE APPENDIX F TO THE FBC
 AS AMENDED BY THE CITY OF WEST PALM
 BEACH.
  
 PLEASE PROVIDE A RECENT PROPERTY SURVEY.
  
 IT APPEARS THAT THE EXTERIOR WALLS ON
 THE WEST, SOUTH AND EAST ELEVATIONS
 WILL BE LESS THAN FIFTEEN FEET FROM
 PROPERTY LINES, (ASSUMED AND COMMON),
 AND AS SUCH MUST COMPLY WITH FBC TABLE
 600 FOR PERCENTAGE OF WALL AREA
 OPENINGS AND FBC 705.1 FOR PROTECTION
 OF OPENINGS.
  
 IF THE TEST REPORTS AND/OR PRODUCT
 NOTICE OF ACCEPTANCE ARE NOT INCLUDED
 WITH THE PLANS FOR THE DOORS, WINDOWS
 AND ROOF COVERINGS, SEPARATE PERMITS
 AND FEES WILL BE REQUIRED FOR THAT WORK.
  
 SHOW HOW THE GLAZED OPENINGS IN THE
 EXTERIOR BUILDING ENVELOPE WILL COMPLY
 WITH THE HURRICANE MISSILE IMPACT
 RESISTANCE REQUIREMENTS.SEE THE
 ATTACHED INTERPRETATION LETTER.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY FOR THE INCREASED AREA,
 THE PERMIT PLANS STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
  
 SEE FBC 104.3.1.1 FOR THE MINIMUM PLAN
 REVIEW INFORMATION REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-08-27 Time 17:52 Rev Time 1.50
Received By btrobaug Date 2002-08-27 Time 17:52 Sent To  
Notes
2002-08-27 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE MISSING EGRESS LIGHTING
 IN BEDROOMS PER 210-70. PLEASE NOTE
 THAT PLANS SHOW FAN ONLY. PLEASE CLARIFY
  
 2)NOTE: PLEASE NOTE MISSING COUNTERSPACE
 OUTLET PER 210-52-C-1UNIT-F
  
 3)NOTE: PLEASE NOTE MISPRINT OF METER
 BANK #2 AS HOUSE PANEL AND HOUSE PANEL
 AS METER BANK.
  
 4)NOTE: PLEASE NOTE ARC FAULT PROTECTION
 PER 210-12. PLEASE LIST ON PANEL
 SCHEDULES.
  
 5)NOTE: PLEASE NOTE SQ FOOTAGE NEEDS TO
 BE SHOWN FOR EACH APT UNIT AND FOR EACH
 COMM SPACE IN LAOD CALCULATIONS. PER
 220-3,220-10,220-13 ECT
 PLEASE CLARIFY HOW EACH APT IS THE SAME
 AT 800 SQ FT? PLEASE CLARIFY NO SQ FT
 SHOWN FOR COMM UNITS.
 CLARIFY BOTH FUTURE UNITS SHOWN AS SAME
 SQ FT?
 CLARIFY HOW LOAD IS FIGURED FOR COMM
 AREAS IN RESIDENTIAL LOAD CALCULATIONS.
  
 6)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS BLDG STEEL TO BE APART OF
 GROUNDING ELECTRODE SYSTEM. PLEASE
 CLARIFY IF EXISTING FOOTER IS GOING TO
 BE CUT/CHIPPED OUT TO MEET THIS? PLEASE
 NOTETHAT CODE REQ`S FOOTER STEEL ONLY
 WHEN EXPOSED AT NEW CONSTRUCTION. 250-50
 PLEASE NOTE , IF SHOWN ON RISER THEN IT
 WILL BE REQ`D. JUST A NOTE.
  
 7)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 PLEASE NOTE THAT EM LTS AND OR EXITS
 MAY BE REQ`D FOR WORK AREAS OF RES USE?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-12-10 Cont ID  
Sent By nmccray Date 2002-12-10 Time 14:36 Rev Time 0.00
Received By nmccray Date 2002-12-10 Time 14:36 Sent To  
Notes
2002-12-10 00:00:001) SHALL COMPLY WITH FLORIDA BUILDING
 CODE 2000 EDITION AND NFPA 101 2000
 EDITION.
  
 2) PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) PORTABLE FIRE EXTINGUISHERS REGUIRED.
  
 4) ALSO UNDER PERMIT # 02022328
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-08-29 Cont ID  
Sent By mcarsill Date 2002-08-29 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2002-08-29 Time 15:00 Sent To  
Notes
2002-08-29 00:00:001) WRONG BUILDING CODE REFERENCED.
 SHOULD READ FLORIDA BUILDING CODE 2000
 EDITION NOT THE STANDARD BUILDING CODE
 1997 EDITION.
  
 2) PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 3) DO THE AIR CONDITIONING SYSTEM
 UNITS INTERFERE WITH EXIT DISCHARGE
 FROM THE STAIRS.
  
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 11:17 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 11:16 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-09-13 Cont ID  
Sent By pkrauss Date 2002-09-13 Time 15:41 Rev Time 1.00
Received By pkrauss Date 2002-09-13 Time 15:24 Sent To  
Notes
2002-09-13 00:00:00DENIED:
  
 PLEASE NOTE, PLANS REVIEWED IN
 ACCORDANCE WITH 2001 FBC.REVISE PLANS
 TO INDICATE CURRENT CODE INSTEAD OF THE
 1997 SBC.
  
 PLAN SHEET M-1 - PLEASE CLARIFY LOCATION
 OF C.U. 1 & 3, IT APPEARS THEY MAY
 INTERFERE WITH ACCESS TO THE STORAGE
 AREA & DOORS.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 2001 FBC(M) 402.2 - NATURAL VENTILATION
 FOR OUTSIDE AIR REQUIRMENT. SHOW
 COMPLIANCE FOR THE MINIMUM OPENABLE AREA
 TO THE OUTDOORS. (4 PERCENT OF THE FLOOR
 AREA BEING VENTILATED) OR TABLE 403.3
 FOR MECHANICAL VENTILATION.
  
 PROVIDE ENERGY AND MANUAL J CALCS AS
 PER CHAPTER 13 OF THE FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-30 Cont ID  
Sent By kstevens Date 2002-08-30 Time 14:33 Rev Time 0.00
Received By kstevens Date 2002-08-30 Time 10:43 Sent To  
Notes
2002-08-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT D-1 ALL CAPPED OFF PLUMBING SHALL
 BE INSPECTED PRIOR TO COVERING.
 2) SHT SP-2 FOUNTAIN SHALL HAVE A SEPAR-
 ATE PERMIT. WILL THERE BE A DRAIN AND/0R
 WATER HOOK UP TO THE FOUNTAIN?
 3) SHT A-1 DRINKING FOUNTAIN SHALL BE A
 HIGH/LOW OR OTHER PROVISIONS SHALL MADE
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. 11-4.1.3(10)(A)
 4) SHT A-1 PER TABLE 403.1 A SERVICE
 SINK IS REQUIRED.
 5) SHT A-1 RESIDENTIAL UNITS, 1 AUTOMAT-
 IC CLOTHES WASHER CONNECTION PER DWELL-
 ING PER TABLE 403.1 - ALSO SHT A-2
 6) SHT A-6 ACCESSIBLE TOILET ROOM DETAIL
 SHOW 2'10" (34") TO FLOOD RIM OF LAV.
 SEC 11-4.19.2
 7) SHTS P-1 FLOOR PLAN AND P-3 SANITARY
 RISER DIAGRAM, PLUMBING FROM THE FUTURE
 TENANT SPACE AND SECOND FLOOR UNITS
 SHALL NOT DRAIN THROUGH THE WET VENTED
 BATHROOM ON THE FIRST FLOOR. SEC 909.1
 8) SHTS P-1 FLOOR PLAN AND P-3 SANITARY
 RISER DIAGRAM, SINK SHALL NOT DRAIN THRU
 WET VENTED TOILET ROOM IN OFFICE SPACE
 SEC 909.1. FLOOR DRAIN SHALL BE TAKEN
 OFF THE VENTED LINE.
 9) SHT P-2 PLUMBING SPECIFICATIONS #2
 CODE REFERENCE SHALL BE FBC-2001 PLUMB-
 ING NOT STANDARD CODE.
 10) BACKFLOW REQUIRED ON WATER SERVCICE.
 11) WATER RISER DIAGRAM REQUIRED FOR
 RESIDENTIAL UNITS. WATER HAMMERS ARREST-
 ORS ARE REQUIRED FOR ALL QUICK CLOSING
 VALVES PER 604.9 LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE". ARRESTORS
 REQUIRED FOR ICE MACHINE, DISHWASHERS,
 AND WASH MACHINES ECT. - REQUIRED FOR
 1ST FLOOR OFFICE WATER RISER ALSO.
 12) SHT P-3 WATER HEATERS, THE RELIEF
 VALVE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISIB-
 LE AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM. 504.7.1
 13) THERMAL EXPANSION CONTROL FOR WATER
 HEATERS PER 607.3.2. PROVIDE DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status F Date 2002-08-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 11:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-15 00:00:00DENIED, WAITING FOR SITE PLAN APPROVAL